VIOX VSP1-D20/1(S)+1 Pluggable Single-Pole SPD
Overview
The VIOX VSP1-D20/1(S)+1 is a high-performance Pluggable Single-Pole Surge Protective Device (SPD) designed for use in sub-distribution boards. This versatile device offers robust protection for L-N and N-PE modes, making it an ideal solution for various electrical installations.
Key Features
- Class II, Class III, Type 2, Type 3 device
- Location of Use: Sub-Distribution Boards
- Mode of Protection: L-N, N-PE
- Surge Ratings: In = 10 kA (8/20 μs)
- IEC/EN/UL Category: Class II+III / Type 2+3
- Protective Elements: High Energy MOV and GDT
- Housing: Pluggable Design
- Compliance: IEC 61643-11:2011, EN 61643-11:2012
Technical Specifications
| IEC Electrical | 75 | 150 | 275 | 320 | 385 | 440 |
|---|---|---|---|---|---|---|
| Nominal AC Voltage (50/60Hz) | 60 V | 120 V | 230 V | 230 V | 230 V | 400 V |
| Maximum Continuous Operating Voltage (AC) (L-N) | 75 V | 150 V | 275V | 320 V | 385 V | 440 V |
| Maximum Continuous Operating Voltage (AC) (N-PE) | 255V | |||||
| Nominal Discharge Current (8/20 μs) (L-N) / (N-PE) | 10kV / 10kA | |||||
| Maximum Discharge Current (8/20 μs) (L-N) / (N-PE) | 20 kA / 20 kA | |||||
| Voltage Protection Level (L-N) / (N-PE) | 0.2kV/1.5kV | 0.6kV/1.5kV | 1.3kV/1.5kV | 1.5kV/1.5kV | 1.5kV/1.5kV | 1.8kV/1.5kV |
| Follow Current Interrupt Rating (N-PE) | 100Arms | |||||
| Response Time (L-N) / (N-PE) | < 25 ns / < 100 ns | |||||
| Back-Up Fuse (max) | 125 A gL / gG | |||||
| Short-Circuit Current Rating (AC) (L-N) | 10 kA | |||||
| TOV Withstand 5s (L-N) | 90V | 180V | 335V | 335V | 335V | 580V |
| TOV 120min (L-N) | 115V | 230V | 440V | 440V | 440V | 765V |
| mode | Withstand | Withstand | Safe Fail | Safe Fail | Safe Fail | Safe Fail |
| TOV Withstand 200ms (N-PE) | 1200V | |||||
Mechanical & Environmental Specifications
- Operating Temperature Range: -40°F to +158°F [-40°C to +70°C]
- Permissible Operating Humidity: 5%…95%
- Atmospheric pressure and altitude: 80k Pa … 106k Pa / -500 m….2000 m
- Terminal Screw Torque: 39.9 lbf.in [4.5 Nm]
- Conductor Cross Section (max): 2 AWG (Solid, Stranded) / 4 AWG (Flexible)
- 35 mm² (Solid, Stranded) / 25 mm²(Flexible)
- Mounting: 35 mm DIN Rail, EN 60715
- Degree of Protection: IP 20 (built-in)
- Housing Material: Thermoplastic: Extinguishing Degree UL 94 V-0
- Thermal Protection: Yes
- Operating State / Fault Indication: Green ok / Red defect
Additional Features
- Remote Contacts (RC): Optional
- RC Switching Capacity: AC: 250V / 0.5 A; DC: 250V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A
- RC Conductor Cross Section (max): 16 AWG (Solid) / 1.5 mm²(Solid)