VIOX ELECTRIC
Langue

VIOX VOAP2-100A 100A Three-Source Power Phase Selector with Over/Under Voltage, Current & Alarm Relay

The VIOX VOAP2-100A is a heavy-duty 100 A three-source (3 × L+N) automatic power selector that routes three independent single-phase or 3-phase 220 V sources into a single protected output with simultaneous L+N disconnection, integrated audible buzzer, NC/COM/NO dry-contact alarm output, and 99-event fault memory.

Modèle VIOX
VOAP2-100A
Tension
3×220 V AC (L+N × 3 Inputs)
Actuel
100 A · NC/COM/NO Alarm
Format
Rail DIN de 35 mm

Vue d'ensemble

The VIOX VOAP2-100A is a heavy-duty 100 A three-source (3 × L+N) automatic power selector that routes three independent single-phase or 3-phase 220 V sources into a single protected output with simultaneous L+N disconnection, integrated audible buzzer, NC/COM/NO dry-contact alarm output, and 99-event fault memory.

Caractéristiques

  • Accepts 3 independent L+N 220 V AC power inputs and outputs 1 continuous protected L+N supply up to 100 A.
  • Full adjustable Over-Voltage (220–300 V), Under-Voltage (150–210 V), Over-Current (1–100 A), and phase-anomaly protection.
  • Simultaneous L + N disconnection per source with individual front manual override rocker switches.
  • Built-in audible alarm buzzer + dry-contact NC/COM/NO relay terminals for remote BMS/SCADA alerting.

Spécifications

VOAP2-100A Technical Specifications

ParamètreSpécification
Input / Output3 × (L+N) 220 V AC Inputs → 1 × (L+N) 100 A Output
ProtectionsAdjustable Over-Voltage (220–300 V), Under-Voltage (150–210 V), Over-Current (1–100 A)
Alarm & MemoryNC / COM / NO dry alarm contacts + built-in buzzer + fault history
Recovery & Mounting1–500 s adjustable auto-recovery · 35 mm DIN rail · CE

Wiring & Setup Guide

  • Connect three independent 220 V L+N sources to Power I, Power II, and Power III IN terminals; wire the protected load to OUT (N, L) and optional remote alarm to NC/COM/NO.
  • Explore the complete VIOX Voltage Protectors catalog for matched DIN-rail switchgear.

FAQ

How is VOAP2-100A different from VOPD3-100VAYA?

VOAP2-100A accepts three fully independent L+N power sources (cutting both L and N), adds front manual source rocker switches, and includes a built-in buzzer plus NC/COM/NO alarm relay contacts.

Besoin d'un devis produit ?
Construisons-le ensemble.

Envoyez-nous le modèle du produit, les caractéristiques techniques, la quantité et les exigences OEM. Notre équipe examinera votre demande et vous répondra dans un délai d'un jour ouvré.

Demander un Devis