Přehled
The VIOX VM6ELY Series is a 4-pole Class B electronic earth-leakage LCD molded case circuit breaker engineered for smart-grid distribution cabinets, utility transformer feeders, and commercial sub-mains. Covering 5 frames from 160 A to 800 A (40 A–800 A adjustable, 4P, AC 400 V, Ui 1000 V, Uimp 8 kV), VM6ELY combines high breaking capacity (up to 85 kA Icu / 65 kA Ics), Icw 10–20 kA/1s selectivity, graded 50–1000 mA AC-type residual-current protection, remote communication, and optional terminal temperature display (Code WD).
Funkce
- 4-pole Class B electronic MCCB with integrated electronic residual-current protection and front LCD display.
- Graded field-adjustable IΔn: 50, 100, 200, 300, 500, 800, and 1000 mA (AC type) with IΔm = 25% Icu.
- 5 frames: VM6ELY-160, 250, 400, 630, and 800 A with breaking capacity up to 85 kA Icu / 65 kA Ics.
- Rated short-time withstand current Icw = 10 kA/1s (160–630 A) and 20 kA/1s (800 A).
- Built-in remote communication interface plus optional real-time temperature display (Code WD).
- Compatible with electric/manual rotary operators, mechanical interlocking, plug-in bases, and internal codes 00–78.
Modely
| Frame Series | Adjustable In Range (A) | Breaking Tiers | Icw (1s) | Max Icu / Ics (400 V AC) |
|---|---|---|---|---|
| VM6ELY-160 | 40–100 A · 50–125 A · 63–160 A | M, H | 10 kA/1s | 65 kA / 50 kA |
| VM6ELY-250 | 50–125 A · 100–250 A | M, H | 10 kA/1s | 65 kA / 50 kA |
| VM6ELY-400 | 160–400 A | M, H | 10 kA/1s | 70 kA / 50 kA |
| VM6ELY-630 | 252–630 A | M, H | 10 kA/1s | 70 kA / 50 kA |
| VM6ELY-800 | 252–630 A · 320–800 A | M, H | 20 kA/1s | 85 kA / 65 kA |
Specifikace
Electrical & Residual-Current Data (4P, AC 400 V)
| Frame & Tiers | Ics (400 V) | Icu (400 V) | Icw (1s) | IΔn & IΔm |
|---|---|---|---|---|
| VM6ELY-160 M / H | 25 / 50 kA | 35 / 65 kA | 10 kA/1s | 50–1000 mA · 25% Icu |
| VM6ELY-250 M / H | 25 / 50 kA | 35 / 65 kA | 10 kA/1s | 50–1000 mA · 25% Icu |
| VM6ELY-400 M / H | 35 / 50 kA | 50 / 70 kA | 10 kA/1s | 50–1000 mA · 25% Icu |
| VM6ELY-630 M / H | 35 / 50 kA | 50 / 70 kA | 10 kA/1s | 50–1000 mA · 25% Icu |
| VM6ELY-800 M / H | 50 / 65 kA | 50 / 85 kA | 20 kA/1s | 50–1000 mA · 25% Icu |
Outline Dimensions (mm, 4P)
| Rám | Width W (mm) | Length L (mm) | Height Cover (mm) | Height Handle (mm) |
|---|---|---|---|---|
| VM6ELY-160 | 120 | 150 | 82 | 108 |
| VM6ELY-250 | 140 | 165 | 88 | 116 |
| VM6ELY-400 | 184 | 257 | 103 | 152 |
| VM6ELY-630 | 184 | 257 | 103 | 152 |
| VM6ELY-800 | 280 | 275.5 | 103 | 152 |
Průvodce výběrem
| Pozice kódu | Význam | Catalog Value or Options |
|---|---|---|
| VM6ELY | Sériové | 4P Electronic leakage LCD molded case circuit breaker |
| 160–800 | Jmenovitý proud rámu | 160, 250, 400, 630, 800 A (4P only) |
| M / H | Breaking tier | M (Moderate, conventional) or H (High breaking up to 85 kA) |
| WD | Doplňková funkce | Optional real-time temperature display function |
| A / B / C / D | 4P Neutral type | A/B (N no trip) or C/D (N with overcurrent release) |
| 00–78 | Internal accessory code | 00 None · 08 Alarm · 10 Shunt · 18 Shunt+Alarm · 20/27 Aux · 28/29 Aux+Alarm · 30 UVT · 38 UVT+Alarm · 40/41/48 Shunt+Aux · 50 Shunt+UVT · 60–69 Multi-Aux · 70–78 UVT+Aux (DC 24/110/220 V, AC 230/400 V) |
1. Select Graded IΔn
Configure 50–1000 mA residual current and time delay on the LCD for selective utility distribution.
2. Monitor Thermal Health
Specify Code WD to display real-time temperature inside high-load transformer kiosks.
3. Integrate Telemetry
Connect remote communication outputs to smart-grid gateways for fault-event logging.
4. Confirm 4P Plug-In
All 5 frames support fixed or front/back plug-in bases (draw-out not available on 4P VM6ELY).
Instalace
- Ensure all three phases and the neutral conductor pass cleanly through the 4P VM6ELY terminals.
- Verify IΔn and delay time coordination against downstream distribution board RCDs.
- Check 4P panel width (120–280 mm) and handle clearance before cutting enclosure doors.
- Compare with thermomagnetic leakage VM6LY or PV reclosing VM6LE.
ČASTO KLADENÉ DOTAZY
Why is VM6ELY offered strictly in 4-pole configurations?
4-pole architecture routes all three phases and the neutral conductor through the internal zero-sequence current transformer for accurate residual-current detection across balanced and unbalanced loads.
What residual-current levels can be set on VM6ELY?
IΔn is graded-adjustable across 50, 100, 200, 300, 500, 800, and 1000 mA (AC type), with residual short-circuit breaking capacity IΔm = 25% Icu.
What is the WD option on VM6ELY?
Code WD adds real-time temperature display functionality to help operators detect loose busbar joints or cabinet overheating early.
Does VM6ELY provide Class B short-time selectivity?
Yes. VM6ELY is rated Class B with Icw = 10 kA/1s on 160–630 A frames and 20 kA/1s on the 800 A frame.
Can VM6ELY be ordered with plug-in mounting?
Yes. Front-panel and back-panel plug-in bases (split, integrated, and fixed) are supported across all 5 frames (160–800 A).
Is remote communication supported on VM6ELY?
Yes. VM6ELY supports remote communication for smart-grid monitoring and event reporting.