VIOX ELECTRIC
Idioma

VIOX VM6ELY Series Electronic Leakage LCD MCCB (160A–800A, 4P)

VIOX VM6ELY Series 4-Pole Electronic Leakage LCD MCCB (160 A–800 A, AC 400 V, Ui 1000 V, Uimp 8 kV, Class B Icw 10–20 kA/1s) unites electronic overcurrent protection, graded 50–1000 mA earth-leakage protection (IΔm 25% Icu), LCD display, remote communication, and optional temperature monitoring (Code WD).

Frame Range
160–800 A (5 Frames · 4P)
Graded Leakage
50–1000 mA · IΔm 25% Icu
Class B Icw
10–20 kA/1s · Up to 85 kA Icu
Recursos inteligentes
LCD · Remote Comm · Temp (WD)

Visão geral

The VIOX VM6ELY Series is a 4-pole Class B electronic earth-leakage LCD molded case circuit breaker engineered for smart-grid distribution cabinets, utility transformer feeders, and commercial sub-mains. Covering 5 frames from 160 A to 800 A (40 A–800 A adjustable, 4P, AC 400 V, Ui 1000 V, Uimp 8 kV), VM6ELY combines high breaking capacity (up to 85 kA Icu / 65 kA Ics), Icw 10–20 kA/1s selectivity, graded 50–1000 mA AC-type residual-current protection, remote communication, and optional terminal temperature display (Code WD).

Caraterísticas

  • 4-pole Class B electronic MCCB with integrated electronic residual-current protection and front LCD display.
  • Graded field-adjustable IΔn: 50, 100, 200, 300, 500, 800, and 1000 mA (AC type) with IΔm = 25% Icu.
  • 5 frames: VM6ELY-160, 250, 400, 630, and 800 A with breaking capacity up to 85 kA Icu / 65 kA Ics.
  • Rated short-time withstand current Icw = 10 kA/1s (160–630 A) and 20 kA/1s (800 A).
  • Built-in remote communication interface plus optional real-time temperature display (Code WD).
  • Compatible with electric/manual rotary operators, mechanical interlocking, plug-in bases, and internal codes 00–78.

Modelos

Frame SeriesAdjustable In Range (A)Breaking TiersIcw (1s)Max Icu / Ics (400 V AC)
VM6ELY-16040–100 A · 50–125 A · 63–160 AM, H10 kA/1s65 kA / 50 kA
VM6ELY-25050–125 A · 100–250 AM, H10 kA/1s65 kA / 50 kA
VM6ELY-400160–400 AM, H10 kA/1s70 kA / 50 kA
VM6ELY-630252–630 AM, H10 kA/1s70 kA / 50 kA
VM6ELY-800252–630 A · 320–800 AM, H20 kA/1s85 kA / 65 kA

Especificações

Electrical & Residual-Current Data (4P, AC 400 V)

Frame & TiersIcs (400 V)Icu (400 V)Icw (1s)IΔn & IΔm
VM6ELY-160 M / H25 / 50 kA35 / 65 kA10 kA/1s50–1000 mA · 25% Icu
VM6ELY-250 M / H25 / 50 kA35 / 65 kA10 kA/1s50–1000 mA · 25% Icu
VM6ELY-400 M / H35 / 50 kA50 / 70 kA10 kA/1s50–1000 mA · 25% Icu
VM6ELY-630 M / H35 / 50 kA50 / 70 kA10 kA/1s50–1000 mA · 25% Icu
VM6ELY-800 M / H50 / 65 kA50 / 85 kA20 kA/1s50–1000 mA · 25% Icu

Outline Dimensions (mm, 4P)

QuadroWidth W (mm)Length L (mm)Height Cover (mm)Height Handle (mm)
VM6ELY-16012015082108
VM6ELY-25014016588116
VM6ELY-400184257103152
VM6ELY-630184257103152
VM6ELY-800280275.5103152

Guia de seleção

Posição do códigoSignificadoCatalog Value or Options
VM6ELYSérie4P Electronic leakage LCD molded case circuit breaker
160–800Corrente de quadro160, 250, 400, 630, 800 A (4P only)
M / HBreaking tierM (Moderate, conventional) or H (High breaking up to 85 kA)
WDFunção adicionalOptional real-time temperature display function
A / B / C / D4P Neutral typeA/B (N no trip) or C/D (N with overcurrent release)
00–78Internal accessory code00 None · 08 Alarm · 10 Shunt · 18 Shunt+Alarm · 20/27 Aux · 28/29 Aux+Alarm · 30 UVT · 38 UVT+Alarm · 40/41/48 Shunt+Aux · 50 Shunt+UVT · 60–69 Multi-Aux · 70–78 UVT+Aux (DC 24/110/220 V, AC 230/400 V)

1. Select Graded IΔn

Configure 50–1000 mA residual current and time delay on the LCD for selective utility distribution.

2. Monitor Thermal Health

Specify Code WD to display real-time temperature inside high-load transformer kiosks.

3. Integrate Telemetry

Connect remote communication outputs to smart-grid gateways for fault-event logging.

4. Confirm 4P Plug-In

All 5 frames support fixed or front/back plug-in bases (draw-out not available on 4P VM6ELY).

Instalação

  • Ensure all three phases and the neutral conductor pass cleanly through the 4P VM6ELY terminals.
  • Verify IΔn and delay time coordination against downstream distribution board RCDs.
  • Check 4P panel width (120–280 mm) and handle clearance before cutting enclosure doors.
  • Compare with thermomagnetic leakage VM6LY or PV reclosing VM6LE.

FAQ

Why is VM6ELY offered strictly in 4-pole configurations?

4-pole architecture routes all three phases and the neutral conductor through the internal zero-sequence current transformer for accurate residual-current detection across balanced and unbalanced loads.

What residual-current levels can be set on VM6ELY?

IΔn is graded-adjustable across 50, 100, 200, 300, 500, 800, and 1000 mA (AC type), with residual short-circuit breaking capacity IΔm = 25% Icu.

What is the WD option on VM6ELY?

Code WD adds real-time temperature display functionality to help operators detect loose busbar joints or cabinet overheating early.

Does VM6ELY provide Class B short-time selectivity?

Yes. VM6ELY is rated Class B with Icw = 10 kA/1s on 160–630 A frames and 20 kA/1s on the 800 A frame.

Can VM6ELY be ordered with plug-in mounting?

Yes. Front-panel and back-panel plug-in bases (split, integrated, and fixed) are supported across all 5 frames (160–800 A).

Is remote communication supported on VM6ELY?

Yes. VM6ELY supports remote communication for smart-grid monitoring and event reporting.

2026 Technical Catalog · Online PDF
VIOX Full 18-Series MCCB & Intelligent Breaker Catalog
Open the complete 18-series catalog online for frame dimensions, time-current trip curves, wiring schematics, and factory order codes (PDF · 26.7 MB).
Open Full Catalog PDF ↗

Precisa de um orçamento de produto?
Vamos construir juntos.

Envie-nos o modelo do produto, as especificações técnicas, a quantidade e os requisitos de OEM. Nossa equipe analisará sua aplicação e responderá dentro de um dia útil.

Pedir um Orçamento