نظرة عامة
Severe three-phase load imbalance on low-voltage distribution transformers causes neutral overheating, high line losses, and voltage drops. The VIOX VM7E Series (VM7E-125, VM7E-160, VM7E-250; four-phase input to two-phase output; AC 400 V / 220 V) automatically commutates single-phase feeders between phases A, B, and C in just 8–10 ms via an electronic permanent-magnet mechanism—delivering ≥50,000 operating cycles, 20 kA Icu / 10 kA Ics protection, 20–60 s auto-reclosing, early warning protection, and power metering statistics.
الميزات
- Ultra-fast 8–10 ms phase-change commutation prevents downstream appliance resets during load balancing.
- Electronic permanent-magnet operating mechanism rated for ≥50,000 cycles (up to 100,000 mechanical life).
- Three ratings in one compact 190 × 140 × 110 mm housing: 125 A (50–125 A), 160 A (63–160 A), and 250 A (100–250 A).
- Integrated AC-type earth-leakage protection, 20–60 s auto-reclosing, and 20 kA Icu / 10 kA Ics breaking.
- Built-in remote control, early-warning alarms, and power metering statistics on front LCD.
- AC 1000 V insulation voltage, 8 kV Uimp, and 3 kA/0.3s short-time withstand current (Icw).
النماذج
| الطراز | Rated Current In (A) | التكوين | وقت النقل | Dimensions b×a×ca (mm) |
|---|---|---|---|---|
| VM7E-125 | 125 A (50–125 A) | Four-phase to two-phase | 8–10 ms | 190 × 140 × 110 |
| VM7E-160 | 160 A (63–160 A) | Four-phase to two-phase | 8–10 ms | 190 × 140 × 110 |
| VM7E-250 | 250 A (100–250 A) | Four-phase to two-phase | 8–10 ms | 190 × 140 × 110 |
المواصفات
Electrical & Protection Specifications
| المعلمة | المواصفات |
|---|---|
| الجهد المقنن (Ue) | AC 400 V / 220 V |
| Rated insulation / Uimp | AC 1000 V / 8 kV |
| Breaking capacity (Icu / Ics) | 20 kA / 10 kA |
| Short-time withstand (Icw) | 3 kA / 0.3 s |
| Operation cycles | ≥ 50,000 cycles |
| Phase-change action time | 8–10 ms (electronic permanent-magnet) |
| Automatic reclosing / Leakage | 20–60 s / AC type |
| خصائص التيار الزائد | 1.05×In non-trip (2 h) · 1.30×In trip (2 h) |
دليل الاختيار
| موقع الكود | المعنى | Catalog Value or Options |
|---|---|---|
| VM7E | السلسلة | Three-phase unbalanced phase-change switch |
| 125 / 160 / 250 | التيار المقنن | 125 A (50–125 A), 160 A (63–160 A), 250 A (100–250 A) |
1. Balance Rural & Urban Grids
Deploy VM7E on unbalanced 3-phase low-voltage feeders to cut transformer neutral current and line losses.
2. Protect Sensitive Loads
8–10 ms zero-crossing permanent-magnet transfer keeps lighting and home electronics online.
3. Need HPLC Carrier?
Step up to VM7E-ZB if power-line carrier communication is required.
4. Verify Input/Output
Wire 3-phase + N input (L1/L2/L3/N) to 2-wire single-phase output (L/N).
التركيب
- Verify phase sequence (A, B, C, N) on the upper incoming terminals before energizing.
- Mount vertically inside pole-mounted or pad-mounted distribution boxes (190 × 140 × 110 mm).
- Configure imbalance thresholds and communication parameters via the front LCD menu.
- See also VM7E-ZB Multifunctional Phase-Change Switch.
الأسئلة الشائعة
How fast does VM7E switch a load from one phase to another?
VM7E completes phase commutation in 8–10 ms using an electronic permanent-magnet mechanism, preventing noticeable flicker or resets on typical single-phase loads.
What problem does a three-phase unbalanced phase-change switch solve?
It dynamically shifts single-phase branch loads from overloaded phases to lightly loaded phases on a 3-phase transformer, reducing neutral overheating, voltage sag, and distribution losses.
What current ratings are available in VM7E?
125 A (50–125 A), 160 A (63–160 A), and 250 A (100–250 A), all sharing a uniform 190 × 140 × 110 mm footprint.
What is the operating endurance of VM7E?
Rated for ≥50,000 electrical/commutation cycles (up to 100,000 mechanical cycles).
Does VM7E include overcurrent and earth-leakage protection?
Yes. It provides 20 kA Icu / 10 kA Ics breaking, 1.05×In/1.30×In overcurrent tripping, AC-type leakage protection, and 20–60 s auto-reclosing.
What is the difference between VM7E and VM7E-ZB?
VM7E-ZB adds an integrated single-phase HPLC power-line carrier module (124 mm depth vs 110 mm) for carrier-based smart-grid coordination.