VIOX V50L-32G Safety Breaker Residual Current Circuit Breaker with Overcurrent Protection
Overview
The VIOX V50L-32G RCBO series is designed for AC 50Hz applications with rated voltage up to 240V and rated current up to 32A. These devices offer comprehensive protection against overload and short circuit for various modern household appliances, while also providing functionality for infrequent operation and control.
Key Features
- High breaking capacity
- Zero line and fire line intermittent protection
- Leakage protection even in case of fire line reversal
- Compact size with double pole structure design
- Simultaneous connection and disconnection of both poles
- Truly safe and reliable for civilian and industrial single-phase applications
- Suitable for infrequent operation and control
Technical Specifications
- Standard: IEC/EN 60898
- Type: RCBO V50L-32G
- Protection: Overload and Short Circuit
- Rated current: 16A, 20A, 25A, 32A
- Characteristic: C curve (32A), D curve (16A, 20A, 25A)
- Poles: 2 poles
- Breaking capacity: 2500A
- Rated voltage: 110VAC, 230VAC
- Ambient Temperature: -5°C to +40°C (24-hour average not exceeding 35°C)
- Altitude: 2,000m or less
- Installation class: III
- Pollution levels: II
| Over-Load | |||||
|---|---|---|---|---|---|
| Test No. | Curve Type | Load Current | Initial State | Time Limit To Trip | Estimated Result |
| 1 | C,D | 1.13In | cold state | t≤1h | Not trip |
| 2 | C,D | 1.45In | conntinuing the test | t < 1 | trip |
| 3 | C,D | 2.55In | cold state | 1s < t < 60s | trip |
| Short circuit | |||||
|---|---|---|---|---|---|
| Test No. | Curve Type | Load Current | Initial State | Time Limit To Trip | Estimated Result |
| 4 | C | 5In | cold state | t≤0.1s | Not trip |
| D | 10In | ||||
| 5 | C | 10In | cold state | t < 0.1s | trip |
| D | 20In | ||||
| Ambiment temperature Rated current(A) | -10°C | 0°C | 10°C | 20°C | 30°C | 40°C | 50°C | 60°C |
|---|---|---|---|---|---|---|---|---|
| 16 | 19.20 | 18.40 | 17.76 | 16.96 | 16.00 | 15.36 | 14.88 | 14.24 |
| 20 | 24.00 | 23.00 | 22.20 | 21.20 | 20.00 | 19.20 | 18.60 | 17.80 |
| 25 | 30.00 | 28.75 | 27.75 | 26.50 | 25.00 | 24.00 | 23.25 | 22.25 |
| 32 | 38.72 | 37.12 | 35.52 | 33.92 | 32.00 | 30.72 | 29.76 | 28.16 |
Installation Requirements
- The magnetic field near the installation site should not be more than five times the magnetic field in any direction
Applications
- Protection of modern household appliances
- Civilian and industrial single-phase circuits
- Infrequent operation and control scenarios
Safety Features
- Dual pole protection
- Leakage protection in various wiring scenarios
- Simultaneous pole operation for enhanced safety