Four-pole AC contactors with selectable main-contact
구성.

  • 9–95 A AC-3 at 380/400 V
  • 04: 4NO; 08: 2NO + 2NC main contacts
  • 690 V 정격 절연 전압
  • AC coil options; rail or screw mounting

개요

VIOX CJX2s-4P AC contactors provide four-pole switching with
model-specific AC-3 ratings from 9 to 95 A at 380/400 V. The series
offers 04 and 08 main-contact configurations for different circuit
arrangements, with rail or screw mounting.

특징

  • Four main poles with 4NO or 2NO + 2NC configurations.
  • Engineering-plastic base and integrated product marking.
  • Mounting slider for installation and removal.
  • Terminal covers and optional transparent front dust cover.

Contact Configurations

Suffix Main-contact arrangement
04 Four normally open contacts (4NO)
08 Two normally open and two normally closed contacts (2NO + 2NC)

These suffixes describe the main contacts, not auxiliary contacts.
Select the arrangement to match the circuit: 08 is not equivalent to
four normally open poles. A contactor alone is not a complete automatic
transfer-switch system.

기술 사양

Frame/model designation (4P) 380/400 V에서의 AC-3 전류 380/400 V에서의 AC-3 모터 출력
CJX2s-09 9 A 4 kW
CJX2s-12 12 A 5.5 kW
CJX2s-18 18 A 7.5 kW
CJX2s-25 25 A 11kW
CJX2s-32 32 A 15 kW
CJX2s-38 38 A 18.5 kW
CJX2s-40 40 A 18.5 kW
CJX2s-50 50 A 22kW
CJX2s-65 65 A 30 kW
CJX2s-80 80 A 37 kW
CJX2s-95 95 A 45 kW

Complete the model selection with the required 04 or 08 contact
configuration and coil voltage. Ratings above apply to AC-3 at 380/400
V; other operating voltages and utilization categories have different
ratings.

매개변수 사양
주극 4P
정격 절연 전압 Ui 690 V
Main-circuit voltages in the rating table 380/400 V; 660/690 V
AC coil voltage options 24, 36, 48, 110, 127, 220/230, 240, 380/400, 415, 440 V
코일 주파수 옵션 50 Hz; 50/60 Hz
Coil operation range, frames 09–38 70%–120% Us
Coil operation range, frames 40–95 90%–120% Us
Protection, frames 09–38 IP20, 단자 제외
Protection, frames 40–95 IP10
설치 카테고리 III
오염 정도 3
마운팅 레일 또는 나사

차원

The drawings distinguish frames 09–38 and 40–95. For frames 40–95,
the 04 and 08 configurations have different Cmax dimensions; check the
exact configuration before allocating mounting space.

CJX2s-4P contactor installation dimensions for 04 and 08 configurations

주문 정보

Provide the current/frame designation, 04 or 08 contact arrangement,
load voltage and utilization category, coil voltage and frequency,
액세서리 및 수량을 명시하십시오.

제품 견적이 필요하신가요?
함께 만들어 갑시다.

제품 모델, 기술 정격, 수량 및 OEM 요구 사항을 보내주십시오. 당사 팀에서 귀하의 애플리케이션을 검토한 후 영업일 기준 1일 이내에 답변해 드리겠습니다.