VIOX ELECTRIC
Dil

VIOX CJX2s-4P Dört Kutuplu AC Kontaktör

Four-pole AC contactors with selectable main-contact
konfigürasyonları.

  • 9–95 A AC-3 at 380/400 V
  • 04: 4NO; 08: 2NO + 2NC main contacts
  • 690 V nominal yalıtım gerilimi
  • AC coil options; rail or screw mounting

Genel Bakış

VIOX CJX2s-4P AC contactors provide four-pole switching with
model-specific AC-3 ratings from 9 to 95 A at 380/400 V. The series
offers 04 and 08 main-contact configurations for different circuit
arrangements, with rail or screw mounting.

Özellikler

  • Four main poles with 4NO or 2NO + 2NC configurations.
  • Engineering-plastic base and integrated product marking.
  • Mounting slider for installation and removal.
  • Terminal covers and optional transparent front dust cover.

Contact Configurations

Suffix Main-contact arrangement
04 Four normally open contacts (4NO)
08 Two normally open and two normally closed contacts (2NO + 2NC)

These suffixes describe the main contacts, not auxiliary contacts.
Select the arrangement to match the circuit: 08 is not equivalent to
four normally open poles. A contactor alone is not a complete automatic
transfer-switch system.

Teknik Özellikler

Frame/model designation (4P) 380/400 V'ta AC-3 akımı 380/400 V'ta AC-3 motor gücü
CJX2s-09 9 A 4 kW
CJX2s-12 12 A 5.5 kW
CJX2s-18 18 A 7.5 kW
CJX2s-25 25 A 11 kW
CJX2s-32 32 A 15 kW
CJX2s-38 38 A 18.5 kW
CJX2s-40 40 A 18.5 kW
CJX2s-50 50 A 22 kW
CJX2s-65 65 A 30 kW
CJX2s-80 80 A 37 kW
CJX2s-95 95 A 45 kW

Complete the model selection with the required 04 or 08 contact
configuration and coil voltage. Ratings above apply to AC-3 at 380/400
V; other operating voltages and utilization categories have different
ratings.

Parametre Şartname
Ana kutuplar 4P
Nominal yalıtım gerilimi Ui 690 V
Main-circuit voltages in the rating table 380/400 V; 660/690 V
AC coil voltage options 24, 36, 48, 110, 127, 220/230, 240, 380/400, 415, 440 V
Bobin frekansı seçenekleri 50 Hz; 50/60 Hz
Coil operation range, frames 09–38 70%–120% Us
Coil operation range, frames 40–95 90%–120% Us
Protection, frames 09–38 IP20, terminaller hariç
Protection, frames 40–95 IP10
Kurulum kategorisi III
Kirlilik derecesi 3
Montaj Ray veya vida

Boyut

The drawings distinguish frames 09–38 and 40–95. For frames 40–95,
the 04 and 08 configurations have different Cmax dimensions; check the
exact configuration before allocating mounting space.

CJX2s-4P contactor installation dimensions for 04 and 08 configurations

Sipariş Bilgileri

Provide the current/frame designation, 04 or 08 contact arrangement,
load voltage and utilization category, coil voltage and frequency,
aksesuarları ve miktarı teklif isterken belirtin.

Ürün Teklifi mi İstiyorsunuz?
Birlikte İnşa Edelim.

Bize ürün modelini, teknik değerleri, miktarı ve OEM gereksinimlerini gönderin. Ekibimiz başvurunuzu inceleyecek ve bir iş günü içinde yanıt verecektir.

Teklif İsteyin