VIOX VSP1-D20/1(S)+1 SPD unipolar enchufable
VIOX VSP1-D20/1(S)+1 Pluggable Single-Pole SPD offers comprehensive surge protection for sub-distribution boards. This Class II+III/Type 2+3 device safeguards L-N and N-PE modes with 10kA nominal and 20kA maximum discharge current. Featuring high-energy MOV and GDT elements, it operates from 60V to 400V AC with <25ns response time for L-N and <100ns for N-PE. IEC 61643-11:2011 and EN 61643-11:2012 compliant, it provides voltage protection levels from 0.2kV to 1.8kV. With IP20 protection, thermal safeguards, and optional remote contacts, this versatile SPD suits various electrical installations, combining reliability and performance for enhanced power system protection in diverse applications.
Envíenos sus requisitos, le haremos un presupuesto en 12 horas
- TEL:+8618066396588
- Whatsapp:+8618066396588
- Email:sales@viox.com
VIOX VSP1-D20/1(S)+1 SPD unipolar enchufable
Visión general
The VIOX VSP1-D20/1(S)+1 is a high-performance Pluggable Single-Pole Surge Protective Device (SPD) designed for use in sub-distribution boards. This versatile device offers robust protection for L-N and N-PE modes, making it an ideal solution for various electrical installations.
Características principales
- Class II, Class III, Type 2, Type 3 device
- Localización de uso: Subdistribution Boards
- Mode of Protection: L-N, N-PE
- Surge Ratings: In = 10 kA (8/20 μs)
- IEC/EN/UL Category: Class II+III / Type 2+3
- Protective Elements: High Energy MOV and GDT
- Carcasa: Diseño enchufable
- Conformidad: IEC 61643-11:2011, EN 61643-11:2012
Especificaciones técnicas
IEC Eléctrica | 75 | 150 | 275 | 320 | 385 | 440 |
---|---|---|---|---|---|---|
Tensión nominal de CA (50/60 Hz) | 60 V | 120 V | 230 V | 230 V | 230 V | 400 V |
Maximum Continuous Operating Voltage (AC) (L-N) | 75 V | 150 V | 275V | 320 V | 385 V | 440 V |
Maximum Continuous Operating Voltage (AC) (N-PE) | 255V | |||||
Nominal Discharge Current (8/20 μs) (L-N) / (N-PE) | 10kV / 10kA | |||||
Maximum Discharge Current (8/20 μs) (L-N) / (N-PE) | 20 kA / 20 kA | |||||
Voltage Protection Level (L-N) / (N-PE) | 0.2kV/1.5kV | 0.6kV/1.5kV | 1.3kV/1.5kV | 1.5kV/1.5kV | 1.5kV/1.5kV | 1.8kV/1.5kV |
Follow Current Interrupt Rating (N-PE) | 100Arms | |||||
Response Time (L-N) / (N-PE) | < 25 ns / < 100 ns | |||||
Fusible de reserva (máx.) | 125 A gL / gG | |||||
Short-Circuit Current Rating (AC) (L-N) | 10 kA | |||||
TOV Withstand 5s (L-N) | 90V | 180V | 335V | 335V | 335V | 580V |
TOV 120min (L-N) | 115V | 230V | 440V | 440V | 440V | 765V |
modo | Resiste | Resiste | Fallo seguro | Fallo seguro | Fallo seguro | Fallo seguro |
TOV Withstand 200ms (N-PE) | 1200V |
Especificaciones mecánicas y medioambientales
- Temperatura de funcionamiento: -40°C a +70°C [-40°F a +158°F]
- Humedad de funcionamiento admisible: 5%...95%
- Presión atmosférica y altitud: 80k Pa ... 106k Pa / -500 m....2000 m
- Par de apriete del tornillo del terminal: 39.9 lbf.in [4.5 Nm]
- Sección del conductor (máx.) 2 AWG (sólido, trenzado) / 4 AWG (flexible)
- 35 mm² (sólido, trenzado) / 25 mm²(flexible)
- Montaje: Carril DIN de 35 mm, EN 60715
- Grado de protección: IP 20 (integrado)
- Material de la carcasa: Termoplástico: Grado de extinción UL 94 V-0
- Protección térmica: Sí
- Estado de funcionamiento / Indicación de fallo: Verde correcto / Rojo defectuoso
Características adicionales
- Contactos remotos (RC): Opcional
- RC Switching Capacity: AC: 250V / 0.5 A; DC: 250V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A
- Sección del conductor RC (máx.) 16 AWG (sólido) / 1,5 mm²(sólido)