Přehled
The VIOX VSP-T15/B+C is an all-in-one Type 1 + Type 2 + Type 3 (T1+T2+T3) AC lightning current and surge arrester housed in a high-strength black industrial enclosure. Delivering Iimp 6.25 kA, 8 kA, or 12.5 kA (10/350 μs) per pole and Uoc 20 kV (Type 3) with ultra-low Up 1.25 kV clamping, it protects main incoming panels against both direct lightning strikes and switching transients in a compact 18 mm-per-pole footprint.
Funkce
- True T1+T2+T3 combined arrester: handles 10/350 μs lightning current (Iimp 6.25 / 8 / 12.5 kA L-N; 25 kA N-PE) and 20 kV Type 3 combination wave.
- Ultra-low voltage protection level Up 1.25 kV (L-N) and 1.5 kV (N-PE) protects sensitive downstream electronics without requiring a separate T2 stage.
- Zero follow-current / leakage-free N-PE GDT path (Ipe = NONE) with 25,000 A short-circuit rating (Isccr).
- Compact 18 mm/pole modular width (1P, 1+NPE, 2P, 3P, 4P, 3+NPE) with built-in thermal disconnector and remote signaling contacts.
Specifikace
VSP-T15/B+C Electrical & Mechanical Specifications
| Parametr | Specifikace |
|---|---|
| SPD Classification | Type 1 + Type 2 + Type 3 (T1+T2+T3) · IEC 61643-11 |
| Max Continuous Operating Voltage (Uc) | 275 V AC (L-N) · 255 V AC (N-PE) |
| Lightning Impulse Current (Iimp, 10/350 μs) | 6.25 kA / 8 kA / 12.5 kA (L-N) · 25 kA (N-PE) |
| Nominal Discharge Current (In, 8/20 μs) | 6.25 kA / 8 kA / 12.5 kA (L-N) · 25 kA (N-PE) |
| Open-Circuit Voltage (Uoc, T3) | 20 kV |
| Úroveň ochrany napětí (Up) | 1.25 kV (L-N) · 1.5 kV (N-PE) |
| Follow Current Interrupt Rating (Ifi) | 300 A (L-N) · 100 A (N-PE) · TOV N-PE: 1200 V |
| Residual Leakage Current (Ipe) | NONE · Isccr: 25,000 A |
| Recommended Backup SCB | VIOX VSP-SSD50X |
| Terminals & Housing | 6–25 mm² (2.5 N·m) · Black PBT/PA UL94 V-0 · IP20 · -40°C to +70°C |
VSP-T15/B+C Available Poles & Dimensions
| Poláci | 1P | 1+NPE / 2P | 3P | 4P / 3+NPE |
|---|---|---|---|---|
| Dimensions (W × H × D) | 18 × 90 × 67 mm | 36 × 90 × 67 mm | 54 × 90 × 67 mm | 72 × 90 × 67 mm |
Rozměry a instalace

- Install at the main service entrance (LPZ 0A/0B → LPZ 1) for buildings with external lightning protection systems (LPS Class III/IV) or overhead service drops.
- Pair with VIOX VSP-SSD50X (Type 1 SCB) for coordinated lightning impulse withstand without nuisance tripping.
- Explore the complete VIOX Surge Protection Devices (SPD) catalog for matched AC, Solar PV DC, and SCB backup protection.
ČASTO KLADENÉ DOTAZY
Why choose a T1+T2+T3 combined SPD like VSP-T15/B+C?
A single VSP-T15/B+C device replaces separate Type 1 and Type 2 arresters in compact distribution boards while keeping residual clamping voltage down to 1.25 kV.