VIOX ELECTRIC
اللغة

VIOX VSP-40D / VSP-40E 18mm Dual-Mode Base AC Type 2 Surge Protector (20kA / 40kA)

The VIOX VSP-40D and VSP-40E are 18 mm single-module 1+NPE AC Type 2 surge protectors (In 20 kA / Imax 40 kA) featuring mirrored terminal layouts (VSP-40D: N-PE top / L bottom; VSP-40E: PE-N top / L bottom) to match diverse panel busbar and wire-duct routing without crossing cables.

سلسلة VIOX
VSP-40D / VSP-40E
الجهد المقنن
AC 275V (L-N) / 255V (N-PE)
Surge Rating
In 20 kA · Imax 40 kA (8/20μs)
قياسي
IEC 61643-11 · Type 2 · CE / CB

نظرة عامة

The VIOX VSP-40D and VSP-40E are 18 mm single-module 1+NPE AC Type 2 surge protectors (In 20 kA / Imax 40 kA) featuring mirrored terminal layouts (VSP-40D: N-PE top / L bottom; VSP-40E: PE-N top / L bottom) to match diverse panel busbar and wire-duct routing without crossing cables.

الميزات

  • 18 mm 1-module 1+NPE protection (MOV L-N + GDT N-PE) delivering In 20 kA / Imax 40 kA (8/20 μs).
  • Two mirrored terminal versions (VSP-40D & VSP-40E) eliminate awkward wire crossovers in compact residential and street-cabinet boxes.
  • Low Up 1.5 kV (L-N) / 1.3 kV (N-PE), zero earth leakage (Ipe = NONE), and 25,000 A Isccr.
  • Pluggable high-visibility orange module with thermal disconnector and optional remote alarm contact.

المواصفات

VSP-40D / VSP-40E Electrical & Mechanical Specifications

المعلمةالمواصفات
SPD ClassificationType 2 (Class II) 1+NPE · IEC 61643-11 / EN 61643-11
Max Continuous Operating Voltage (Uc)275 V AC (L-N) · 255 V AC (N-PE)
Nominal / Max Discharge Current (8/20 μs)In 20 kA · Imax 40 kA
مستوى حماية الجهد (Up)1.5 kV (L-N) · 1.3 kV (N-PE) · Response: 25 ns
TOV & Short-Circuit RatingTOV N-PE: 1200 V · Isccr: 25,000 A · Ipe: NONE
Dimensions & Terminals18 × 83 × 67 mm · 4–16 mm² (2.0 N·m) · 35 mm DIN rail

VSP-40D / VSP-40E Available Poles & Dimensions

الطرازTop TerminalsBottom Terminalالأبعاد
VSP-40DN / PEL18 × 83 × 67 mm
VSP-40EPE / NL18 × 83 × 67 mm

الأبعاد والتركيب

VIOX VSP-40D / VSP-40E 18mm Dual-Mode Base AC Type 2 Surge Protector (20kA / 40kA) Dimensional Drawing (mm)
VSP-40D / VSP-40E Outline & DIN-Rail Mounting Dimensions (unit: mm)
  • Choose VSP-40D or VSP-40E to align directly with your distribution board's Neutral and Earth busbar positions, keeping surge lead lengths minimal.
  • Explore the complete VIOX Surge Protection Devices (SPD) catalog for matched AC, Solar PV DC, and SCB backup protection.

الأسئلة الشائعة

What is the difference between VSP-40D and VSP-40E?

Both share identical 20/40 kA Type 2 electrical ratings in an 18 mm body; VSP-40D places N on the left / PE on the right, while VSP-40E places PE on the left / N on the right to suit different panel layouts.

هل تحتاج إلى عرض سعر للمنتج؟
لنبنيها معاً.

أرسل لنا طراز المنتج، والتقييمات الفنية، والكمية، ومتطلبات الشركة المصنعة للمعدات الأصلية (OEM). سيقوم فريقنا بمراجعة طلبك والرد في غضون يوم عمل واحد.

طلب عرض أسعار