VIOX ELECTRIC
Ngôn ngữ

VIOX VSP-40D / VSP-40E 18mm Dual-Mode Base AC Type 2 Surge Protector (20kA / 40kA)

The VIOX VSP-40D and VSP-40E are 18 mm single-module 1+NPE AC Type 2 surge protectors (In 20 kA / Imax 40 kA) featuring mirrored terminal layouts (VSP-40D: N-PE top / L bottom; VSP-40E: PE-N top / L bottom) to match diverse panel busbar and wire-duct routing without crossing cables.

Dòng VIOX
VSP-40D / VSP-40E
Điện áp định mức
AC 275V (L-N) / 255V (N-PE)
Surge Rating
In 20 kA · Imax 40 kA (8/20μs)
Chuẩn
IEC 61643-11 · Type 2 · CE / CB

Tổng quan

The VIOX VSP-40D and VSP-40E are 18 mm single-module 1+NPE AC Type 2 surge protectors (In 20 kA / Imax 40 kA) featuring mirrored terminal layouts (VSP-40D: N-PE top / L bottom; VSP-40E: PE-N top / L bottom) to match diverse panel busbar and wire-duct routing without crossing cables.

Đặc trưng

  • 18 mm 1-module 1+NPE protection (MOV L-N + GDT N-PE) delivering In 20 kA / Imax 40 kA (8/20 μs).
  • Two mirrored terminal versions (VSP-40D & VSP-40E) eliminate awkward wire crossovers in compact residential and street-cabinet boxes.
  • Low Up 1.5 kV (L-N) / 1.3 kV (N-PE), zero earth leakage (Ipe = NONE), and 25,000 A Isccr.
  • Pluggable high-visibility orange module with thermal disconnector and optional remote alarm contact.

Thông số kỹ thuật

VSP-40D / VSP-40E Electrical & Mechanical Specifications

Tham sốĐặc điểm kỹ thuật
SPD ClassificationType 2 (Class II) 1+NPE · IEC 61643-11 / EN 61643-11
Max Continuous Operating Voltage (Uc)275 V AC (L-N) · 255 V AC (N-PE)
Nominal / Max Discharge Current (8/20 μs)In 20 kA · Imax 40 kA
Mức bảo vệ điện áp (Up)1.5 kV (L-N) · 1.3 kV (N-PE) · Response: 25 ns
TOV & Short-Circuit RatingTOV N-PE: 1200 V · Isccr: 25,000 A · Ipe: NONE
Dimensions & Terminals18 × 83 × 67 mm · 4–16 mm² (2.0 N·m) · 35 mm DIN rail

VSP-40D / VSP-40E Available Poles & Dimensions

Người mẫuTop TerminalsBottom TerminalKích thước
VSP-40DN / PEL18 × 83 × 67 mm
VSP-40EPE / NL18 × 83 × 67 mm

Kích thước & Lắp đặt

VIOX VSP-40D / VSP-40E 18mm Dual-Mode Base AC Type 2 Surge Protector (20kA / 40kA) Dimensional Drawing (mm)
VSP-40D / VSP-40E Outline & DIN-Rail Mounting Dimensions (unit: mm)
  • Choose VSP-40D or VSP-40E to align directly with your distribution board's Neutral and Earth busbar positions, keeping surge lead lengths minimal.
  • Explore the complete VIOX Surge Protection Devices (SPD) catalog for matched AC, Solar PV DC, and SCB backup protection.

Câu hỏi thường gặp

What is the difference between VSP-40D and VSP-40E?

Both share identical 20/40 kA Type 2 electrical ratings in an 18 mm body; VSP-40D places N on the left / PE on the right, while VSP-40E places PE on the left / N on the right to suit different panel layouts.

Cần báo giá sản phẩm?
Hãy cùng chúng tôi thực hiện dự án này.

Gửi cho chúng tôi mã sản phẩm, các định mức kỹ thuật, số lượng và yêu cầu OEM. Đội ngũ của chúng tôi sẽ xem xét ứng dụng của bạn và phản hồi trong vòng một ngày làm việc.

Yêu cầu báo giá