VIOX ELECTRIC
اللغة

VIOX VSP-20 / VSP-40 AC Type 2 Pluggable Surge Protection Device (20kA / 40kA)

The VIOX VSP-20 and VSP-40 are flagship IEC 61643-11 AC Type 2 (Class II) pluggable DIN-rail surge protection devices rated for In 10–20 kA and Imax 20–40 kA (8/20 μs). Engineered for TN-S, TN-C, and TT distribution boards across 275 V, 320 V, 385 V, and 440 V AC systems, they feature high-energy MOV cartridges, rapid <25 ns response, green/red status windows, optional remote signaling contacts (11/12/14), and 1P through 4P / 3+NPE modular configurations.

سلسلة VIOX
VSP-20 / VSP-40
الجهد المقنن
AC 275V / 320V / 385V / 440V
Surge Rating
In 10/20 kA · Imax 20/40 kA
قياسي
IEC 61643-11 · TUV / CE / CB

نظرة عامة

The VIOX VSP-20 and VSP-40 are flagship IEC 61643-11 AC Type 2 (Class II) pluggable DIN-rail surge protection devices rated for In 10–20 kA and Imax 20–40 kA (8/20 μs). Engineered for TN-S, TN-C, and TT distribution boards across 275 V, 320 V, 385 V, and 440 V AC systems, they feature high-energy MOV cartridges, rapid <25 ns response, green/red status windows, optional remote signaling contacts (11/12/14), and 1P through 4P / 3+NPE modular configurations.

الميزات

  • IEC 61643-11 / EN 61643-11 Type 2 (T2) AC surge protection with In 10 kA (VSP-20) and 20 kA (VSP-40), Imax 20 kA / 40 kA (8/20 μs).
  • Wide continuous operating voltage options: Uc 275 V, 320 V, 385 V, and 440 V AC with low voltage protection level Up 1.2–2.2 kV.
  • Tool-free hot-swappable plug-in MOV cartridges with built-in thermal disconnector and clear green/red failure flag.
  • Available in 1P, 1+NPE, 2P, 3P, 4P, and 3+NPE configurations across 79 mm, 83 mm, and 90 mm base heights.
  • Optional floating remote signaling contact (14-11 NO, 11-12 NC, 220 V / 0.5 A) for BMS and SCADA monitoring.

المواصفات

VSP-20 / VSP-40 Electrical & Mechanical Specifications

المعلمةالمواصفات
SPD ClassificationType 2 (Class II) · IEC 61643-11 / EN 61643-11
Max Continuous Operating Voltage (Uc)275 V / 320 V / 385 V / 440 V AC (50/60 Hz)
Nominal Discharge Current (In, 8/20 μs)VSP-20: 10 kA · VSP-40: 20 kA
Max Discharge Current (Imax, 8/20 μs)VSP-20: 20 kA · VSP-40: 40 kA
مستوى حماية الجهد (Up)VSP-20: ≤1.3 / 1.4 / 1.6 / 1.8 kV · VSP-40: ≤1.2 / 1.5 / 1.8 / 2.2 kV
Response Time (tA)<25 ns (L-N / L-PE) · ≤100 ns (N-PE)
Admissible Short-Circuit Current (Isccr)25,000 A · Recommended SCB: VIOX VSP-SSD40 / VSP-SSD80
Network Systems & ModesTN-S, TN-C, TT · L-PE, N-PE, L-PEN, L-N
Remote Signaling ContactOptional 14-11 (NO), 11-12 (NC) · 220 V / 0.5 A
Terminals & Torque6–25 mm² screw terminals · 2.0–2.5 N·m · 15 mm strip length
Housing & EnvironmentPBT / PA UL94 V-0 · IP20 · -40°C to +70°C · 35 mm EN 60715 DIN rail
الشهاداتTUV, CE, CB, UKCA, RoHS

VSP-20 / VSP-40 Available Poles & Dimensions

القطبين1P1+NPE / 2P3P4P / 3+NPE
Dimensions (W × H × D)18 × 90(83) × 67 mm36 × 90(83) × 67 mm54 × 90(83) × 67 mm72 × 90(83) × 67 mm

الأبعاد والتركيب

VIOX VSP-20 / VSP-40 AC Type 2 Pluggable Surge Protection Device (20kA / 40kA) Dimensional Drawing (mm)
VSP-20 / VSP-40 Outline & DIN-Rail Mounting Dimensions (unit: mm)
  • Install on a 35 mm DIN rail inside main or sub-distribution panels, downstream of an upstream backup protector (recommended VIOX VSP-SSD80 SCB).
  • Keep connecting leads as short and straight as possible (<0.5 m total loop) using ≥10 mm² phase conductors and ≥16 mm² PE earth conductor.
  • Replace plug-in cartridge immediately when the mechanical status window shifts from green to red.
  • Explore the complete VIOX Surge Protection Devices (SPD) catalog for matched AC, Solar PV DC, and SCB backup protection.

الأسئلة الشائعة

Should I choose Uc 275V, 320V, 385V, or 440V for a 230/400V AC grid?

For stable European 230/400 V TN-S grids, Uc 275 V provides the lowest Up clamping voltage. For grids with frequent utility voltage swells (e.g., Middle East, Africa, or industrial feeders), specify Uc 320 V or 385 V to prevent premature MOV aging.

Do I need a backup breaker or SCB upstream of VSP-20 / VSP-40?

Yes. Always install a coordinated backup overcurrent device or dedicated VIOX VSP-SSD80 SPD disconnector upstream to clear power-frequency short-circuit faults safely.

هل تحتاج إلى عرض سعر للمنتج؟