VIOX ELECTRIC
Bahasa

VIOX VSP-20 / VSP-40 AC Type 2 Pluggable Surge Protection Device (20kA / 40kA)

The VIOX VSP-20 and VSP-40 are flagship IEC 61643-11 AC Type 2 (Class II) pluggable DIN-rail surge protection devices rated for In 10–20 kA and Imax 20–40 kA (8/20 μs). Engineered for TN-S, TN-C, and TT distribution boards across 275 V, 320 V, 385 V, and 440 V AC systems, they feature high-energy MOV cartridges, rapid <25 ns response, green/red status windows, optional remote signaling contacts (11/12/14), and 1P through 4P / 3+NPE modular configurations.

Seri VIOX
VSP-20 / VSP-40
Tegangan pengenal
AC 275V / 320V / 385V / 440V
Surge Rating
In 10/20 kA · Imax 20/40 kA
Standar
IEC 61643-11 · TUV / CE / CB

Ikhtisar

The VIOX VSP-20 and VSP-40 are flagship IEC 61643-11 AC Type 2 (Class II) pluggable DIN-rail surge protection devices rated for In 10–20 kA and Imax 20–40 kA (8/20 μs). Engineered for TN-S, TN-C, and TT distribution boards across 275 V, 320 V, 385 V, and 440 V AC systems, they feature high-energy MOV cartridges, rapid <25 ns response, green/red status windows, optional remote signaling contacts (11/12/14), and 1P through 4P / 3+NPE modular configurations.

Fitur

  • IEC 61643-11 / EN 61643-11 Type 2 (T2) AC surge protection with In 10 kA (VSP-20) and 20 kA (VSP-40), Imax 20 kA / 40 kA (8/20 μs).
  • Wide continuous operating voltage options: Uc 275 V, 320 V, 385 V, and 440 V AC with low voltage protection level Up 1.2–2.2 kV.
  • Tool-free hot-swappable plug-in MOV cartridges with built-in thermal disconnector and clear green/red failure flag.
  • Available in 1P, 1+NPE, 2P, 3P, 4P, and 3+NPE configurations across 79 mm, 83 mm, and 90 mm base heights.
  • Optional floating remote signaling contact (14-11 NO, 11-12 NC, 220 V / 0.5 A) for BMS and SCADA monitoring.

Spesifikasi

VSP-20 / VSP-40 Electrical & Mechanical Specifications

ParameterSpesifikasi
SPD ClassificationType 2 (Class II) · IEC 61643-11 / EN 61643-11
Max Continuous Operating Voltage (Uc)275 V / 320 V / 385 V / 440 V AC (50/60 Hz)
Nominal Discharge Current (In, 8/20 μs)VSP-20: 10 kA · VSP-40: 20 kA
Max Discharge Current (Imax, 8/20 μs)VSP-20: 20 kA · VSP-40: 40 kA
Tingkat Perlindungan Tegangan (Up)VSP-20: ≤1.3 / 1.4 / 1.6 / 1.8 kV · VSP-40: ≤1.2 / 1.5 / 1.8 / 2.2 kV
Response Time (tA)<25 ns (L-N / L-PE) · ≤100 ns (N-PE)
Admissible Short-Circuit Current (Isccr)25,000 A · Recommended SCB: VIOX VSP-SSD40 / VSP-SSD80
Network Systems & ModesTN-S, TN-C, TT · L-PE, N-PE, L-PEN, L-N
Remote Signaling ContactOptional 14-11 (NO), 11-12 (NC) · 220 V / 0.5 A
Terminals & Torque6–25 mm² screw terminals · 2.0–2.5 N·m · 15 mm strip length
Housing & EnvironmentPBT / PA UL94 V-0 · IP20 · -40°C to +70°C · 35 mm EN 60715 DIN rail
SertifikasiTUV, CE, CB, UKCA, RoHS

VSP-20 / VSP-40 Available Poles & Dimensions

Polandia1P1+NPE / 2P3P4P / 3+NPE
Dimensions (W × H × D)18 × 90(83) × 67 mm36 × 90(83) × 67 mm54 × 90(83) × 67 mm72 × 90(83) × 67 mm

Dimensi & Instalasi

VIOX VSP-20 / VSP-40 AC Type 2 Pluggable Surge Protection Device (20kA / 40kA) Dimensional Drawing (mm)
VSP-20 / VSP-40 Outline & DIN-Rail Mounting Dimensions (unit: mm)
  • Install on a 35 mm DIN rail inside main or sub-distribution panels, downstream of an upstream backup protector (recommended VIOX VSP-SSD80 SCB).
  • Keep connecting leads as short and straight as possible (<0.5 m total loop) using ≥10 mm² phase conductors and ≥16 mm² PE earth conductor.
  • Replace plug-in cartridge immediately when the mechanical status window shifts from green to red.
  • Explore the complete VIOX Surge Protection Devices (SPD) catalog for matched AC, Solar PV DC, and SCB backup protection.

PERTANYAAN YANG SERING DIAJUKAN

Should I choose Uc 275V, 320V, 385V, or 440V for a 230/400V AC grid?

For stable European 230/400 V TN-S grids, Uc 275 V provides the lowest Up clamping voltage. For grids with frequent utility voltage swells (e.g., Middle East, Africa, or industrial feeders), specify Uc 320 V or 385 V to prevent premature MOV aging.

Do I need a backup breaker or SCB upstream of VSP-20 / VSP-40?

Yes. Always install a coordinated backup overcurrent device or dedicated VIOX VSP-SSD80 SPD disconnector upstream to clear power-frequency short-circuit faults safely.

Butuh Penawaran Produk?
Mari Kita Bangun Bersama.

Kirimkan model produk, peringkat teknis, kuantitas, dan persyaratan OEM kepada kami. Tim kami akan meninjau aplikasi Anda dan merespons dalam satu hari kerja.

Minta Penawaran