VIOX ELECTRIC
Dil

VIOX VSP-T25/B+C Heavy-Duty AC Type 1+2 Lightning & Surge Arrester (Iimp 25kA)

The VIOX VSP-T25/B+C is a heavy-duty Type 1 + Type 2 (B+C) lightning current and surge arrester engineered for LPS Class I & II buildings, substations, and industrial main switchboards. Rated for Iimp 25 kA (10/350 μs) per pole and Imax 50 kA (8/20 μs) across Uc 275 V, 350 V, and 440 V AC with low Up 1.2–2.0 kV protection and zero follow-current leakage.

VIOX Serisi
VSP-T25/B+C
Anma gerilimi
AC 275V / 350V / 440V
Surge Rating
Iimp 25 kA (10/350μs) · Imax 50 kA
Standart
IEC 61643-11 · T1+T2 · CE / CB

Genel Bakış

The VIOX VSP-T25/B+C is a heavy-duty Type 1 + Type 2 (B+C) lightning current and surge arrester engineered for LPS Class I & II buildings, substations, and industrial main switchboards. Rated for Iimp 25 kA (10/350 μs) per pole and Imax 50 kA (8/20 μs) across Uc 275 V, 350 V, and 440 V AC with low Up 1.2–2.0 kV protection and zero follow-current leakage.

Özellikler

  • Full 25 kA (10/350 μs) lightning current per pole (100 kA total in 4P / 3+NPE) for LPS Class I/II main service entrances.
  • Dual-rated Type 1 + Type 2 (Iimp 25 kA / In 25 kA / Imax 50 kA) eliminates decoupling inductors between T1 and T2 stages.
  • Available in Uc 275 V, 350 V, and 440 V AC with Up 1.2 / 1.6 / 2.0 kV and 50,000 A short-circuit withstand (Isccr).
  • Heavy-duty 36 mm/pole black flame-retardant PBT/PA enclosure with pluggable cartridges and 11/12/14 remote alarm contacts.

Teknik Özellikler

VSP-T25/B+C Electrical & Mechanical Specifications

ParametreŞartname
SPD ClassificationType 1 + Type 2 (T1+T2) · IEC 61643-11 / EN 61643-11
Max Continuous Operating Voltage (Uc)275 V / 350 V / 440 V AC (L-N) · 255 V AC (N-PE)
Lightning Impulse Current (Iimp, 10/350 μs)25 kA per pole (L-N & N-PE)
Nominal / Max Discharge Current (8/20 μs)In 25 kA · Imax 50 kA
Gerilim Koruma Seviyesi (Up)1.2 / 1.6 / 2.0 kV (L-N) · 1.5 kV (N-PE)
Response Time & Leakage25 ns (L-N) / 100 ns (N-PE) · Ipe: NONE · Isccr: 50,000 A
Recommended Backup SCBVIOX VSP-SSD50X
Terminals & Housing6–35 mm² (2.5 N·m) · Black PBT/PA UL94 V-0 · IP20 · 35 mm DIN rail

VSP-T25/B+C Available Poles & Dimensions

Kutuplar1P1+NPE / 2P3P4P / 3+NPE
Dimensions (W × H × D)36 × 90 × 92 mm72 × 90 × 92 mm108 × 90 × 92 mm144 × 90 × 92 mm

Boyutlar ve Kurulum

VIOX VSP-T25/B+C Heavy-Duty AC Type 1+2 Lightning & Surge Arrester (Iimp 25kA) Dimensional Drawing (mm)
VSP-T25/B+C Outline & DIN-Rail Mounting Dimensions (unit: mm)
  • Use ≥16 mm² copper phase conductors and ≥25 mm² main earthing conductor to handle 25 kA (10/350 μs) lightning current.
  • Coordinate upstream with VIOX VSP-SSD50X dedicated Type 1 backup disconnector.
  • Explore the complete VIOX Surge Protection Devices (SPD) catalog for matched AC, Solar PV DC, and SCB backup protection.

SSS

What is the difference between VSP-T15/B+C (12.5kA) and VSP-T25/B+C (25kA)?

VSP-T15/B+C (12.5 kA, 18 mm/pole) fits LPS Class III/IV commercial buildings and space-limited panels; VSP-T25/B+C (25 kA, 36 mm/pole) meets strict LPS Class I/II utility, hospital, and industrial main switchboard specifications.

Ürün Teklifi mi İstiyorsunuz?
Birlikte İnşa Edelim.

Bize ürün modelini, teknik değerleri, miktarı ve OEM gereksinimlerini gönderin. Ekibimiz başvurunuzu inceleyecek ve bir iş günü içinde yanıt verecektir.

Teklif İsteyin