VIOX ELECTRIC
Sprache

VIOX VM7DC Series New Energy 1500V DC MCCB (320A–1600A, UL 489)

VIOX VM7DC Series New Energy 1500 V DC MCCB (320 A, 400/630 A, and 1600 A frames; 63 A–1600 A; 2P/3P/4P) complies with UL 489 and IEC 60947-2 with Ui 1800 V, Uimp 12 kV, zero-arc chamber option, +50 °C reference ambient, non-polarized bidirectional wiring, and breaking capacity up to 85 kA @750V / 50 kA @1000V / 20 kA @1500V DC.

Rated DC Voltage
DC 1500 V (Ui 1800 V / 12 kV)
Frame & Current
320 / 630 / 1600 A (63–1600 A)
Key Engineering
Non-Polarized · Zero Arc · +50 °C
Normen
UL 489 & IEC 60947-2

Übersicht

The VIOX VM7DC Series is a flagship high-voltage DC molded case circuit breaker purpose-built for 1500 V DC utility solar PV combiner boxes, battery energy storage systems (BESS), and EV fast-charging DC buses. Engineered for +50 °C reference ambient without derating, zero-arc operation (with arc-extinguishing chamber), non-polarized bidirectional current flow (zero derating on reverse-feed/battery charge-discharge), and UL 489 compliance, VM7DC delivers up to 85 kA at 750 V DC, 50 kA at 1000 V DC, and 20 kA at 1500 V DC (10 kA single-pole 1500 V DC).

Eigenschaften

  • True 1500 V DC rated working voltage with reinforced Ui = 1800 V, Uimp = 12 kV, and 3500 V dielectric withstand.
  • Non-polarized bidirectional design: zero capacity derating for reverse-feed solar or BESS charge/discharge.
  • Zero-arc option (with arc-extinguishing chamber) and +50 °C reference ambient without thermal derating.
  • Complies with UL 489 standard; single-pole DC 1500 V Ics = 10 kA.
  • Three high-power frames: VM7DC-320 (63–320 A, 2P), VM7DC-400/630 (225–630 A, 2P), and VM7DC-1600 (800–1600 A, 3P/4P).
  • Supports modular internal accessories (alarm, shunt, UVT, auxiliary contacts) for remote BESS/PV shutdown.

Modelle

ModellRated Current In (A)PolenRated Voltage UeDimensions W×L×H (mm)
VM7DC-32063, 80, 100, 125, 140, 160, 180, 200, 225, 250, 315, 320 A2PDC 1500 V (Ui 1800 V)90 × 215 × 136
VM7DC-400/630225, 250, 320, 350, 400, 500, 630 A2PDC 1500 V (Ui 1800 V)110 × 275 × 152
VM7DC-1600800, 1000, 1250, 1500, 1600 A3P / 4PDC 1500 V (Ui 1800 V)3P: 210×340×244 · 4P: 280×340×244

Spezifikationen

DC Short-Circuit Breaking Capacity (Ics)

ModellDC 750 VDC 1000 VDC 1200 VDC 1500 V
VM7DC-320 (2P)——35 kA20 kA
VM7DC-400/630 (2P)85 kA50 kA—10 kA (1P) / 20 kA (2P)
VM7DC-1600 (3P / 4P)50 kA30 kA15 kA10 kA

Mechanical, Insulation & Environmental Data

ParameterSpezifikation
Bemessungsisolationsspannung (Ui)1800 V DC
Bemessungs-Stoßspannungsfestigkeit (Uimp): 12 kV
Power-frequency withstand (1 min)3500 V
Mechanical life / Electrical life4,000 cycles / 10,000 (320–630 A) · 500 (1600 A)
Arcing distance50 mm or 0 mm (with arc chamber, 320–630 A); 100 mm (1600 A)
Instantaneous release5×In or 10×In
Reference ambient temperature+50 °C (no derating)

Auswahlhilfe

CodepositionBedeutungCatalog Value or Options
VM7DCSerieNew energy 1500 V DC molded case circuit breaker (UL 489)
320 / 400 / 630 / 1600Rahmenstrom320 A (2P), 400/630 A (2P), 1600 A (3P/4P)
5×In / 10×InInstantaneous tripSelectable magnetic threshold for PV vs BESS battery racks
00–70Internal accessories08 Alarm · 10 Shunt · 18 Shunt+Alarm · 20/27 Aux · 28/29 Aux+Alarm · 30/38 UVT · 40/48 Shunt+Aux · 62/68/69 Multi-Aux · 70 UVT+Aux

1. Size for BESS or PV

Use non-polarized VM7DC on bidirectional battery racks where fault current can flow in either direction.

2. Eliminate Thermal Derating

+50 °C reference ambient keeps full ampacity inside sun-exposed outdoor solar combiner boxes.

3. Enable Emergency E-Stop

Add Code 10 Shunt Release (DC 24 V) for rapid BMS-triggered battery-rack isolation.

4. Save Cabinet Space

Specify the zero-arc chamber option on 320–630 A frames to minimize top clearance.

Einrichtung

FAQ

Is VM7DC polarity-sensitive for battery energy storage (BESS)?

No. VM7DC is non-polarized with zero capacity derating on reverse current flow, making it ideal for bidirectional BESS charge/discharge protection.

What standards does VM7DC comply with?

VM7DC complies with UL 489 and IEC 60947-2 for 1500 V DC new-energy applications.

What is the ambient temperature rating of VM7DC?

VM7DC is calibrated at a +50 °C reference ambient temperature so it maintains full rated current inside outdoor solar combiner boxes and BESS containers.

What breaking capacities does VM7DC achieve?

VM7DC achieves up to 85 kA at 750 V DC, 50 kA at 1000 V DC, 35 kA at 1200 V DC, and 20 kA at 1500 V DC (10 kA single-pole at 1500 V DC).

Does VM7DC offer a zero-arc option?

Yes. VM7DC-320 and VM7DC-400/630 support an optional arc-extinguishing chamber achieving 0 mm external arcing distance.

Can a BMS remotely trip VM7DC during battery thermal runaway?

Yes. Specify internal accessory code 10 (shunt release) or code 40/48 (shunt + auxiliary/alarm) with a DC 24 V coil for direct BMS emergency tripping.

2026 Technical Catalog · Online PDF
VIOX Full 18-Series MCCB & Intelligent Breaker Catalog
Open the complete 18-series catalog online for frame dimensions, time-current trip curves, wiring schematics, and factory order codes (PDF · 26.7 MB).
Open Full Catalog PDF ↗

Benötigen Sie ein Produktangebot?
Lassen Sie es uns gemeinsam aufbauen.

Senden Sie uns das Produktmodell, die technischen Nennwerte, die Menge und die OEM-Anforderungen. Unser Team wird Ihre Anwendung prüfen und innerhalb eines Werktages antworten.

Angebot anfordern