ภาพรวม
The VIOX VM7DC Series is a flagship high-voltage DC molded case circuit breaker purpose-built for 1500 V DC utility solar PV combiner boxes, battery energy storage systems (BESS), and EV fast-charging DC buses. Engineered for +50 °C reference ambient without derating, zero-arc operation (with arc-extinguishing chamber), non-polarized bidirectional current flow (zero derating on reverse-feed/battery charge-discharge), and UL 489 compliance, VM7DC delivers up to 85 kA at 750 V DC, 50 kA at 1000 V DC, and 20 kA at 1500 V DC (10 kA single-pole 1500 V DC).
คุณสมบัติ
- True 1500 V DC rated working voltage with reinforced Ui = 1800 V, Uimp = 12 kV, and 3500 V dielectric withstand.
- Non-polarized bidirectional design: zero capacity derating for reverse-feed solar or BESS charge/discharge.
- Zero-arc option (with arc-extinguishing chamber) and +50 °C reference ambient without thermal derating.
- Complies with UL 489 standard; single-pole DC 1500 V Ics = 10 kA.
- Three high-power frames: VM7DC-320 (63–320 A, 2P), VM7DC-400/630 (225–630 A, 2P), and VM7DC-1600 (800–1600 A, 3P/4P).
- Supports modular internal accessories (alarm, shunt, UVT, auxiliary contacts) for remote BESS/PV shutdown.
แบบจำลอง
| แบบอย่าง | Rated Current In (A) | วกเธอคงหัวเสี | Rated Voltage Ue | Dimensions W×L×H (mm) |
|---|---|---|---|---|
| VM7DC-320 | 63, 80, 100, 125, 140, 160, 180, 200, 225, 250, 315, 320 A | 2พี | DC 1500 V (Ui 1800 V) | 90 × 215 × 136 |
| VM7DC-400/630 | 225, 250, 320, 350, 400, 500, 630 A | 2พี | DC 1500 V (Ui 1800 V) | 110 × 275 × 152 |
| VM7DC-1600 | 800, 1000, 1250, 1500, 1600 A | 3P / 4P | DC 1500 V (Ui 1800 V) | 3P: 210×340×244 · 4P: 280×340×244 |
ข้อมูลจำเพาะ
DC Short-Circuit Breaking Capacity (Ics)
| แบบอย่าง | DC 750 V | DC 1000 V | DC 1200 V | DC 1500 V |
|---|---|---|---|---|
| VM7DC-320 (2P) | — | — | 35 kA | 20 กิโลแอมป์ |
| VM7DC-400/630 (2P) | 85 kA | 50 kA | — | 10 kA (1P) / 20 kA (2P) |
| VM7DC-1600 (3P / 4P) | 50 kA | 30 kA | 15 kA | 10 กิโลแอมป์ |
Mechanical, Insulation & Environmental Data
| พารามิเตอร์ | ข้อมูลจำเพาะ |
|---|---|
| แรงดันฉนวนที่กำหนด (Ui) | 1800 V DC |
| พิกัดความทนแรงดันอิมพัลส์ (Uimp) | 12 kV |
| Power-frequency withstand (1 min) | 3500 V |
| Mechanical life / Electrical life | 4,000 cycles / 10,000 (320–630 A) · 500 (1600 A) |
| Arcing distance | 50 mm or 0 mm (with arc chamber, 320–630 A); 100 mm (1600 A) |
| Instantaneous release | 5×In or 10×In |
| Reference ambient temperature | +50 °C (no derating) |
คู่มือการเลือก
| ตำแหน่งรหัส | ความหมาย | Catalog Value or Options |
|---|---|---|
| VM7DC | ชุด | New energy 1500 V DC molded case circuit breaker (UL 489) |
| 320 / 400 / 630 / 1600 | กระแสเฟรม | 320 A (2P), 400/630 A (2P), 1600 A (3P/4P) |
| 5×In / 10×In | Instantaneous trip | Selectable magnetic threshold for PV vs BESS battery racks |
| 00–70 | Internal accessories | 08 Alarm · 10 Shunt · 18 Shunt+Alarm · 20/27 Aux · 28/29 Aux+Alarm · 30/38 UVT · 40/48 Shunt+Aux · 62/68/69 Multi-Aux · 70 UVT+Aux |
1. Size for BESS or PV
Use non-polarized VM7DC on bidirectional battery racks where fault current can flow in either direction.
2. Eliminate Thermal Derating
+50 °C reference ambient keeps full ampacity inside sun-exposed outdoor solar combiner boxes.
3. Enable Emergency E-Stop
Add Code 10 Shunt Release (DC 24 V) for rapid BMS-triggered battery-rack isolation.
4. Save Cabinet Space
Specify the zero-arc chamber option on 320–630 A frames to minimize top clearance.
การติดตั้ง
- Non-polarized terminals allow top or bottom incoming/outgoing DC wiring with zero capacity derating.
- Fit the optional arc-extinguishing chamber for 0 mm arc-clearance compact BESS racks.
- Pair with VIOX DC MCBs, สวิตช์แยก DC, และ 1500 V DC SPDs.
- See also กล่องรวมสัญญาณโซลาร์เซลล์ PV แล้ว VM7 800 V AC MCCB.
คำถามที่พบบ่อย
Is VM7DC polarity-sensitive for battery energy storage (BESS)?
No. VM7DC is non-polarized with zero capacity derating on reverse current flow, making it ideal for bidirectional BESS charge/discharge protection.
What standards does VM7DC comply with?
VM7DC complies with UL 489 and IEC 60947-2 for 1500 V DC new-energy applications.
What is the ambient temperature rating of VM7DC?
VM7DC is calibrated at a +50 °C reference ambient temperature so it maintains full rated current inside outdoor solar combiner boxes and BESS containers.
What breaking capacities does VM7DC achieve?
VM7DC achieves up to 85 kA at 750 V DC, 50 kA at 1000 V DC, 35 kA at 1200 V DC, and 20 kA at 1500 V DC (10 kA single-pole at 1500 V DC).
Does VM7DC offer a zero-arc option?
Yes. VM7DC-320 and VM7DC-400/630 support an optional arc-extinguishing chamber achieving 0 mm external arcing distance.
Can a BMS remotely trip VM7DC during battery thermal runaway?
Yes. Specify internal accessory code 10 (shunt release) or code 40/48 (shunt + auxiliary/alarm) with a DC 24 V coil for direct BMS emergency tripping.