Přehled
VIOX CJX2s contactor accessories support auxiliary signalling,
time-delay control, interlocking, coil transient suppression and motor
overload protection. Select each accessory by its function and the exact
contactor frame; the items shown are individually selected components,
not a bundled kit.
Bloky pomocných kontaktů
KAT blocks mount on the front/top of the contactor. KAS blocks are
side-mounted. NO and NC quantities refer to auxiliary contacts.
| Miniature model | Standard model | NO | NC |
|---|---|---|---|
| KAT-M20 | KAT-20 | 2 | 0 |
| KAT-M11 | KAT-11 | 1 | 1 |
| KAT-M02 | KAT-02 | 0 | 2 |
| KAT-M40 | KAT-40 | 4 | 0 |
| KAT-M31 | KAT-31 | 3 | 1 |
| KAT-M22 | KAT-22 | 2 | 2 |
| KAT-M13 | KAT-13 | 1 | 3 |
| KAT-M04 | KAT-04 | 0 | 4 |
- KAT-M: CJX2s-M06–M16 miniature contactors.
- Standard KAT: CJX2s-09–630, according to the supplied compatibility
table. - KAS-20: 2NO; KAS-11: 1NO + 1NC; KAS-02: 2NC. Listed for
CJX2s-09–630.
Pneumatic Time-Delay Heads
| Model | Delay function | Rozsah nastavení |
|---|---|---|
| KTD-C1 | Zpoždění zapnutí | 0.1–3 s |
| KTD-C2 | Zpoždění zapnutí | 0.1–30 s |
| KTD-C3 | Zpoždění zapnutí | 10–180 s |
| KTD-D1 | Zpoždění vypnutí | 0.1–3 s |
| KTD-D2 | Zpoždění vypnutí | 0.1–30 s |
| KTD-D3 | Zpoždění vypnutí | 10–180 s |
The KTD heads provide pneumatic time delay with 1NO + 1NC auxiliary
contacts. The catalogue lists CJX2s-09–630 compatibility.
Interlocks and Dust Covers
| Příslušenství | Catalogue compatibility |
|---|---|
| KMI mechanical interlock | CJX2s-09–38 |
| KMI electrical interlock | CJX2s-09–95 |
| KDC-1 front dust cover | CJX2s-09–38 |
| KDC-2 front dust cover | CJX2s-40–95 |
Select interlocks for the actual paired-contactor arrangement. A
front dust cover does not establish a new enclosure IP rating.
Coil Surge Suppression
Moduly
| Module | Contactor frame |
|---|---|
| FS-M | CJX2s-M06–M16 |
| FS-18 | CJX2s-09–18 |
| FS-32 | CJX2s-25–32 |
| FS-65 | CJX2s-40–65 |
| FS-95 | CJX2s-80–95 |
The catalogue lists AC/DC voltage bands of 24–48 V, 100–250 V and
380–440 V. Select the module voltage version to match the coil supply as
well as the contactor frame. These coil suppression accessories are not
distribution-panel surge protective devices.
Relé tepelného přetížení
| Relé | Available adjustment ranges (A) | Listed contactor frames |
|---|---|---|
| JR28s-25 | 0.1–0.16; 0.16–0.25; 0.25–0.4; 0.4–0.63; 0.63–1; 1–1.6; 1.25–2; 1.6–2.5; 2.5–4; 4–6; 5.5–8; 7–10; 9–13; 12–18; 17–25 |
CJX2s-09, 12, 18, 25 |
| JR28s-36 | 23–32; 28–36 | CJX2s-32, 38 |
| JR28s-93 | 23–32; 30–40; 37–50; 48–65; 55–70; 63–80; 80–93 | CJX2s-40, 50, 65, 80, 95 |
Each adjustment range is a separate selection. Choose a relay range
that includes the motor nameplate current and coordinate it with the
contactor and short-circuit protective device.
Informace pro objednání
Provide the exact contactor model, accessory model, required NO/NC
arrangement, delay range or relay current range, coil supply voltage
where applicable, and quantity. Confirm mounting compatibility for the
supplied contactor version before ordering.