The VIOX VOPD1-63VAE is a 4-in-1 single-phase DIN-rail voltage, current, and energy (kWh) protector featuring a triple-row color display and built-in prepaid kWh cutoff (0–999 kWh). Engineered for AC 140–300 V (50/60 Hz) circuits up to 63 A, it protects appliances and distribution sub-panels against over-voltage, under-voltage, and over-current faults with full A0–A18 programmable parameters, power-off memory, and automatic recovery.
الميزات
- 4-in-1 single-phase protection: over-voltage (230–300 V, default 270 V), under-voltage (140–210 V, default 170 V), over-current (1–63 A, default 40 A), and kWh metering.
- Built-in prepaid energy cutoff (A17 ON/OFF, A18 0–999 kWh) with power-off memory and kWh reset.
- Triple-row display for real-time Voltage (V), Current (A), and kWh, plus carousel readout of frequency and power factor.
- Full calibration support for Voltage (A14), Current (A15), and kWh (A16) across -9.9% to +9.9%.
- Low self-consumption (≤2 W), >100,000 electrical/mechanical cycles, compact 36 mm (2-module) 35 mm DIN-rail housing.
المواصفات
VOPD1-63VAE Technical Specifications
| المعلمة | المواصفات |
|---|---|
| نطاق جهد الإدخال | AC 140–300 V, 50/60 Hz |
| خيارات التيار المقدر | 40 A / 63 A (Over-current adjustable 1–63 A, default 40 A) |
| Over-Voltage Protection (A2 / A3) | 230–300 V (default 270 V) · Recovery 225–295 V (default 265 V) |
| Under-Voltage Protection (A6 / A7) | OFF / 140–210 V (default 170 V) · Recovery 145–215 V (default 175 V) |
| Power-On & Recovery Delay (A1 / A4 / A8 / A11) | 1–500 s (Power-on default 10 s; Fault recovery default 30 s) |
| Tripping Action Time (A5 / A9 / A12) | 0.1–30 s (default 1 s) |
| Continuous Over-Current Fault Limit (A13) | OFF / 1–20 times (default OFF) |
| Prepaid Energy Control (A17 / A18) | ON/OFF (default OFF) · 0–999 kWh cutoff |
| Calibration (A14 / A15 / A16) | Voltage / Current / kWh: -9.9% to +9.9% (default 0%) |
| Power Consumption & Life | ≤2 W · >100,000 electrical & mechanical cycles |
| Dimensions & Mounting | 86 × 36 × 68 mm (H × W × D) · 35 mm DIN rail · CE |
VOPD1-63VAE Programmable Menu Parameters
| الكود | المعلمة | النطاق | Factory Default |
|---|---|---|---|
| A0 | Display Carousel Interval | 1–500 s / OFF | إيقاف التشغيل |
| A1 | Power-On Delay | 1–500 s | 10 s |
| A2 / A3 | Over-Voltage Trip / Recovery | 230–300 V / 225–295 V | 270 V / 265 V |
| A4 / A5 | Over-Voltage Recovery Delay / Action Time | 1–500 s / 0.1–30 s | 30 s / 1 s |
| A6 / A7 | Under-Voltage Trip / Recovery | OFF, 140–210 V / 145–215 V | 170 V / 175 V |
| A8 / A9 | Under-Voltage Recovery Delay / Action Time | 1–500 s / 0.1–30 s | 30 s / 1 s |
| A10 / A11 / A12 | Over-Current Trip / Recovery Delay / Action Time | 1–63 A / 1–500 s / 0.1–30 s | 40 A / 30 s / 1 s |
| A13 | Continuous Over-Current Fault Lockout | OFF / 1–20 times | إيقاف التشغيل |
| A14 / A15 / A16 | Voltage / Current / kWh Calibration | -9.9% to +9.9% | 0% |
| A17 / A18 | Prepaid kWh Switch / Limit | ON–OFF / 0–999 kWh | OFF / 0 kWh |
Wiring & Setup Guide
- Top-IN, Bottom-OUT wiring ('over-entering down-out'): connect incoming supply to top L IN and N IN terminals, and load to bottom L OUT and N OUT terminals.
- Snap onto a standard 35 mm EN 60715 DIN rail via the bottom rail buckle; de-energize upstream supply before installation and maintain ventilation clearance.
- Long-press SET (>3 s) to enter menu codes A0–A18; use ▲/▼ to adjust and SET to confirm. Long-press the power key in setup mode to reset cumulative kWh.
- Explore the complete VIOX Voltage Protectors catalog for matched DIN-rail switchgear.
الأسئلة الشائعة
Does VOPD1-63VAE include WiFi or residual-current (leakage) protection?
No. VOPD1-63VAE is a dedicated local-display 4-in-1 V/A/kWh and prepaid protector. For Tuya WiFi and 10–99 mA leakage protection, specify VIOX VOMPD-63LW.
How does the prepaid kWh cutoff work?
Enable A17 (ON) and set the target energy budget in A18 (0–999 kWh). Once cumulative consumption reaches the preset value, VOPD1-63VAE automatically disconnects the load.
What happens when voltage or current faults clear?
V-LED flashes on over/under-voltage and A-LED flashes on over-current. Once line values return inside recovery thresholds and the A4/A8/A11 delay expires, output recloses automatically.