VOSA2-HK-1500V VIOX 1500V DC Forced-Air Rated Semiconductor Protection Fuse: aR class, 200A-800A, 150kA breaking with a ≤15ms time constant, CE marked to IEC 60269-4 and GB/T 13539.4. Kv cooling factor to 1.20.
Cabinets with forced ventilation can carry more current through the same fuse, but the gain only becomes usable once the manufacturer publishes how much. The 1500V DC Forced-Air Rated Semiconductor Protection Fuse from VIOX Electric ships with that curve: a Kv factor reaching 1.20 at 6 m/s of air speed, across 200A to 800A for IGBT stacks, thyristors and rectifier diodes in rail traction, renewable power stations, telecom plants, metallurgy lines, charging piles and storage inverters.
الميزات
- Rated voltage 1500VDC and current capacity 200A for ess & semiconductor high-speed fuse applications.
- High interrupting performance (150kA) with rapid current-limiting fault clearing.
- Engineered and tested in accordance with GB/T 13539.4 / GB/T13539.4 / IEC 60269-4 standards.
- Precision-engineered low-power-loss silver-plated contacts and high-temperature ceramic or flame-retardant housing.
- Direct OEM replacement geometry for standardized industrial, solar PV, ESS, and EV protection panels.
المواصفات
VOSA2-HK-1500V Technical Specifications
| الرقم التسلسلي | Rated Current A | Pre-arcing I²t A²s | Melting I²t A²s | Power dissipation W |
| 1 | 200 | 6710 | 24800 | 98 |
| 2 | 250 | 11400 | 46400 | 112 |
| 3 | 315 | 20100 | 90100 | 125 |
| 4 | 350 | 26900 | 133000 | 135 |
| 5 | 400 | 38900 | 172000 | 147 |
| 6 | 450 | 56700 | 280000 | 159 |
| 7 | 500 | 62500 | 324000 | 167 |
| 8 | 550 | 69400 | 387000 | 183 |
| 9 | 630 | 73700 | 433000 | 195 |
| 10 | 800 | 119000 | 746000 | 210 |
VOSA2-HK-1500V Ratings & Dimensions Table 2
| Rated Current (A) | Conventional Time (h) | Conventional Current | |
| “gR” | |||
| Inf | lf | ||
| ln≤63 | 1 | 1.13ln | 1.6ln |
| 63<In≤160 | 2 | ||
| 160<ln≤400 | 3 | ||
| 400<ln | 4 | ||
| Note:ln is the rated current of the fuse; lnf is the conventional non-fusing current; if is the conventional fusing current. | |||
Selection & Installation Notes
- Verify system maximum voltage (1500VDC) and prospective short-circuit fault current before selecting the fuse link or holder rating.
- Apply ambient-temperature derating when operating inside sealed outdoor combiner boxes or high-density inverter cabinets above 40°C.
- Always de-energize circuits before replacing cylindrical, blade, or bolted fuse links, and use insulated fuse pullers for NH/NT types.
- Explore the complete VIOX Fuse & Fuse Holder catalog for matched holders, bases, and disconnectors.
الأسئلة الشائعة
What voltage and current ratings does the VIOX VOSA2-HK-1500V 1500V DC Forced-Air Rated Semiconductor Protection Fuse support?
This VIOX VOSA2-HK-1500V series is rated for 1500VDC with a current rating of 200A and 150kA breaking performance. Refer to the technical specification table above for individual part numbers and ampere steps.
Which international standards apply to VIOX VOSA2-HK-1500V 1500V DC Forced-Air Rated Semiconductor Protection Fuse?
The VOSA2-HK-1500V series is designed and verified to GB/T 13539.4 / GB/T13539.4 / IEC 60269-4 requirements for safe overcurrent and short-circuit protection.
Where is the VIOX VOSA2-HK-1500V 1500V DC Forced-Air Rated Semiconductor Protection Fuse typically installed?
It is engineered for ess & semiconductor high-speed fuse circuits, protecting cables, busbars, semiconductors, battery modules, or string feeders against thermal overload and high-energy short-circuit faults.
Can VIOX supply matched fuse holders, bases, or OEM private-label packaging?
Yes. VIOX Electric supplies matched DIN-rail fuse holders, NH/NT fuse bases, disconnectors, and OEM/ODM bulk packaging with technical datasheets upon RFQ.