VIOX VOPD3-63VA / VOPD3-100VA Three-Phase Per-Phase Voltage & Current Protector (63A / 100A)

The VIOX VOPD3-63VA (63 A) and VOPD3-100VA (100 A) are heavy-duty three-phase DIN-rail voltage and current protectors with simultaneous per-phase L1/L2/L3 digital readouts. Providing 1% full-scale voltage accuracy, fixed phase-loss protection, voltage unbalance monitoring (20–99 V), and full P1/U1–U12/C1–C5 menu programmability, they safeguard 3-phase motors, pumps, compressors, and commercial switchboards.

VIOX Modeli
VOPD3-63VA / VOPD3-100VA
Gerilim
3×220/380 V AC (140–300 V L-N)
Güncel
63 A / 100 A Adjustable
Biçim
91 × 102 × 52 mm (5-Module)

Genel Bakış

The VIOX VOPD3-63VA (63 A) and VOPD3-100VA (100 A) are heavy-duty three-phase DIN-rail voltage and current protectors with simultaneous per-phase L1/L2/L3 digital readouts. Providing 1% full-scale voltage accuracy, fixed phase-loss protection, voltage unbalance monitoring (20–99 V), and full P1/U1–U12/C1–C5 menu programmability, they safeguard 3-phase motors, pumps, compressors, and commercial switchboards.

Özellikler

  • Supports both 3×220 V + N (3P+N) and 3×380 V (3P without N) three-phase distribution architectures.
  • Full three-phase protection: over-voltage (U1), under-voltage (U5), over-current (C1: 1–63 A / 1–100 A), phase unbalance (U10: 20–99 V), and fixed phase-loss protection.
  • 1% full-scale voltage measurement accuracy with independent ±9.5% three-phase voltage (U9) and current (C4) calibration.
  • Rated insulation voltage Ui 450 V, IP20 enclosure, Pollution Degree 3, 100,000 electrical & mechanical operations.
  • Automatic recovery after configurable delay (1–500 s) with continuous over-current lockout option (C5).

Teknik Özellikler

VOPD3-63VA / VOPD3-100VA Technical Specifications

ParametreŞartname
Rated Supply Voltage3×220 V (3P+N) or 3×380 V (3P) · Operating AC 140–300 V L-N, 50/60 Hz
Nominal Akım SeçenekleriVOPD3-63VA: 0.5–63 A · VOPD3-100VA: 1–100 A (default 30 A)
Over-Voltage / Hysteresis230–300 V (default 270 V) · Recovery 225–295 V (default 265 V) · 5 V hysteresis
Under-Voltage / Hysteresis140–210 V (default 170 V) · Recovery 145–215 V (default 175 V) · 3 V hysteresis
Phase Unbalance & Phase LossUnbalance 20–99 V (10 s trip delay) · Phase-Loss Protection permanently ON
Measurement Accuracy & Ui1% full-scale voltage accuracy · Ui 450 V
Life & Environment100,000 electrical & mechanical cycles · IP20 · -5°C to +40°C · ≤2000 m
Boyutlar91 (W) × 102 (H) × 52 (D) mm · 35 mm DIN rail

VOPD3-63VA / VOPD3-100VA Programmable Menu Parameters

KodParametreMenzilFactory Default
P1Power-On Delay1–500 s10 s
U1 / U2Over-Voltage Trip / Recovery230–300 V / 225–295 V270 V / 265 V
U3 / U4Over-Voltage Recovery Delay / Action Time1–500 s / 0.1–30 s30 s / 1.0 s
U5 / U6Under-Voltage Trip / Recovery140–210 V / 145–215 V170 V / 175 V
U7 / U8Under-Voltage Recovery Delay / Action Time1–500 s / 0.1–30 s30 s / 1.0 s
U93-Phase Voltage Calibration-9.5% to +9.5%0%
U10 / U11 / U12Voltage Unbalance Trip / Recovery / Enable20–99 V / 5–94 V / ON–OFF20 V / 20 V / OFF
C1 / C2 / C3Over-Current Trip / Recovery Delay / Action Time0.5–63 A (or 1–100 A) / 1–500 s / 0.1–30 s30 A / 30 s / 1.0 s
C4 / C53-Phase Current Calibration / Continuous Lockout-9.5% to +9.5% / OFF, 1–200% / OFF

Wiring & Setup Guide

  • IMPORTANT — Bottom-IN, Top-OUT wiring: connect incoming supply cables to the bottom IN terminals and load cables to the top OUT terminals (reverse of single-phase top-entry models).
  • Maintain strict phase matching (L1–L1, L2–L2, L3–L3, N–N). For 3P 380 V systems without neutral, connect L1/L2/L3 only.
  • Install inside a ventilated distribution panel on a 35 mm DIN rail by a qualified electrician with upstream isolation.
  • Explore the complete VIOX Voltage Protectors catalog for matched DIN-rail switchgear.

SSS

Why does VOPD3-63VA/100VA wire Bottom-IN and Top-OUT?

Unlike single-phase VOPD1 models (top-entry), the 3-phase VOPD3-VA terminal layout feeds incoming 3P+N supply into the bottom IN terminals and exits to the load from the top OUT terminals. Always verify terminal labels on the housing before energizing.

Does VOPD3-63VA protect against phase loss?

Yes. Phase-loss protection is permanently enabled (ON), and voltage unbalance protection (U10–U12) can be configured between 20 V and 99 V.

Ürün Teklifi mi İstiyorsunuz?
Birlikte İnşa Edelim.

Bize ürün modelini, teknik değerleri, miktarı ve OEM gereksinimlerini gönderin. Ekibimiz başvurunuzu inceleyecek ve bir iş günü içinde yanıt verecektir.

Teklif İsteyin