The VIOX VOPD3-63VA (63 A) and VOPD3-100VA (100 A) are heavy-duty three-phase DIN-rail voltage and current protectors with simultaneous per-phase L1/L2/L3 digital readouts. Providing 1% full-scale voltage accuracy, fixed phase-loss protection, voltage unbalance monitoring (20–99 V), and full P1/U1–U12/C1–C5 menu programmability, they safeguard 3-phase motors, pumps, compressors, and commercial switchboards.
คุณสมบัติ
- Supports both 3×220 V + N (3P+N) and 3×380 V (3P without N) three-phase distribution architectures.
- Full three-phase protection: over-voltage (U1), under-voltage (U5), over-current (C1: 1–63 A / 1–100 A), phase unbalance (U10: 20–99 V), and fixed phase-loss protection.
- 1% full-scale voltage measurement accuracy with independent ±9.5% three-phase voltage (U9) and current (C4) calibration.
- Rated insulation voltage Ui 450 V, IP20 enclosure, Pollution Degree 3, 100,000 electrical & mechanical operations.
- Automatic recovery after configurable delay (1–500 s) with continuous over-current lockout option (C5).
ข้อมูลจำเพาะ
VOPD3-63VA / VOPD3-100VA Technical Specifications
| พารามิเตอร์ | ข้อมูลจำเพาะ |
|---|---|
| Rated Supply Voltage | 3×220 V (3P+N) or 3×380 V (3P) · Operating AC 140–300 V L-N, 50/60 Hz |
| ตัวเลือกกระแสไฟฟ้าที่กำหนด | VOPD3-63VA: 0.5–63 A · VOPD3-100VA: 1–100 A (default 30 A) |
| Over-Voltage / Hysteresis | 230–300 V (default 270 V) · Recovery 225–295 V (default 265 V) · 5 V hysteresis |
| Under-Voltage / Hysteresis | 140–210 V (default 170 V) · Recovery 145–215 V (default 175 V) · 3 V hysteresis |
| Phase Unbalance & Phase Loss | Unbalance 20–99 V (10 s trip delay) · Phase-Loss Protection permanently ON |
| Measurement Accuracy & Ui | 1% full-scale voltage accuracy · Ui 450 V |
| Life & Environment | 100,000 electrical & mechanical cycles · IP20 · -5°C to +40°C · ≤2000 m |
| ขนาด | 91 (W) × 102 (H) × 52 (D) mm · 35 mm DIN rail |
VOPD3-63VA / VOPD3-100VA Programmable Menu Parameters
| รหัส | พารามิเตอร์ | พิสัย | Factory Default |
|---|---|---|---|
| P1 | Power-On Delay | 1–500 s | 10 s |
| U1 / U2 | Over-Voltage Trip / Recovery | 230–300 V / 225–295 V | 270 V / 265 V |
| U3 / U4 | Over-Voltage Recovery Delay / Action Time | 1–500 s / 0.1–30 s | 30 s / 1.0 s |
| U5 / U6 | Under-Voltage Trip / Recovery | 140–210 V / 145–215 V | 170 V / 175 V |
| U7 / U8 | Under-Voltage Recovery Delay / Action Time | 1–500 s / 0.1–30 s | 30 s / 1.0 s |
| U9 | 3-Phase Voltage Calibration | -9.5% to +9.5% | 0% |
| U10 / U11 / U12 | Voltage Unbalance Trip / Recovery / Enable | 20–99 V / 5–94 V / ON–OFF | 20 V / 20 V / OFF |
| C1 / C2 / C3 | Over-Current Trip / Recovery Delay / Action Time | 0.5–63 A (or 1–100 A) / 1–500 s / 0.1–30 s | 30 A / 30 s / 1.0 s |
| C4 / C5 | 3-Phase Current Calibration / Continuous Lockout | -9.5% to +9.5% / OFF, 1–20 | 0% / OFF |
Wiring & Setup Guide
- IMPORTANT — Bottom-IN, Top-OUT wiring: connect incoming supply cables to the bottom IN terminals and load cables to the top OUT terminals (reverse of single-phase top-entry models).
- Maintain strict phase matching (L1–L1, L2–L2, L3–L3, N–N). For 3P 380 V systems without neutral, connect L1/L2/L3 only.
- Install inside a ventilated distribution panel on a 35 mm DIN rail by a qualified electrician with upstream isolation.
- Explore the complete VIOX Voltage Protectors catalog for matched DIN-rail switchgear.
คำถามที่พบบ่อย
Why does VOPD3-63VA/100VA wire Bottom-IN and Top-OUT?
Unlike single-phase VOPD1 models (top-entry), the 3-phase VOPD3-VA terminal layout feeds incoming 3P+N supply into the bottom IN terminals and exits to the load from the top OUT terminals. Always verify terminal labels on the housing before energizing.
Does VOPD3-63VA protect against phase loss?
Yes. Phase-loss protection is permanently enabled (ON), and voltage unbalance protection (U10–U12) can be configured between 20 V and 99 V.