Przegląd
VOSA4-GK 2000V VIOX builds the 2000V DC High-Voltage Semiconductor Protection Fuse for 630A to 1600A DC links: aR class, 150kA breaking, ≤10ms time constant, I²t from 184000 A²s. Compliant with IEC 60269-4 and GB/T13539.4. For solar, storage, rail and industrial converters.
When a converter stack runs at 2000V DC, fault energy grows with the square of the voltage, so the fuse must act before the semiconductors absorb it. The 2000V DC High-Voltage Semiconductor Protection Fuse from VIOX Electric is built for that arithmetic: an aR-class element for the largest DC links in solar and wind power stations, battery energy storage blocks, rail traction converters, metallurgy plants and utility equipment, protecting IGBT modules, thyristors and rectifier diodes.
Cechy
- Rated voltage 2000VDC and current capacity 630A for ess & semiconductor high-speed fuse applications.
- High interrupting performance (150kA) with rapid current-limiting fault clearing.
- Engineered and tested in accordance with GB/T 13539.4 / GB/T13539.4 / IEC 60269-4 standards.
- Precision-engineered low-power-loss silver-plated contacts and high-temperature ceramic or flame-retardant housing.
- Direct OEM replacement geometry for standardized industrial, solar PV, ESS, and EV protection panels.
Specyfikacje
VOSA4-GK Technical Specifications
| Numer seryjny | Rated Current A | Pre-arcing I²t A²s | Melting I²t A²s | Power dissipation W |
| 1 | 630 | 184000 | 867000 | 268 |
| 2 | 800 | 289000 | 1912000 | 285 |
| 3 | 1000 | 693000 | 3245000 | 300 |
| 4 | 1200 | 1050000 | 4538000 | 317 |
| 5 | 1400 | 1342000 | 7186000 | 336 |
| 6 | 1600 | 2420000 | 9720000 | 350 |
VOSA4-GK Ratings & Dimensions Table 2
| Rated Current (A) | Conventional Time (h) | Conventional Current | |
| “gR” | |||
| Inf | lf | ||
| ln≤63 | 1 | 1.13ln | 1.6ln |
| 63<In≤160 | 2 | ||
| 160<ln≤400 | 3 | ||
| 400<ln | 4 | ||
| Note:ln is the rated current of the fuse; lnf is the conventional non-fusing current; if is the conventional fusing current. | |||
Selection & Installation Notes
- Verify system maximum voltage (2000VDC) and prospective short-circuit fault current before selecting the fuse link or holder rating.
- Apply ambient-temperature derating when operating inside sealed outdoor combiner boxes or high-density inverter cabinets above 40°C.
- Always de-energize circuits before replacing cylindrical, blade, or bolted fuse links, and use insulated fuse pullers for NH/NT types.
- Explore the complete VIOX Fuse & Fuse Holder catalog for matched holders, bases, and disconnectors.
FAQ
What voltage and current ratings does the VIOX VOSA4-GK 2000V DC High-Voltage Semiconductor Protection Fuse support?
This VIOX VOSA4-GK series is rated for 2000VDC with a current rating of 630A and 150kA breaking performance. Refer to the technical specification table above for individual part numbers and ampere steps.
Which international standards apply to VIOX VOSA4-GK 2000V DC High-Voltage Semiconductor Protection Fuse?
The VOSA4-GK series is designed and verified to GB/T 13539.4 / GB/T13539.4 / IEC 60269-4 requirements for safe overcurrent and short-circuit protection.
Where is the VIOX VOSA4-GK 2000V DC High-Voltage Semiconductor Protection Fuse typically installed?
It is engineered for ess & semiconductor high-speed fuse circuits, protecting cables, busbars, semiconductors, battery modules, or string feeders against thermal overload and high-energy short-circuit faults.
Can VIOX supply matched fuse holders, bases, or OEM private-label packaging?
Yes. VIOX Electric supplies matched DIN-rail fuse holders, NH/NT fuse bases, disconnectors, and OEM/ODM bulk packaging with technical datasheets upon RFQ.