VIOX VSP-40/G600 / G1000 / G1500 / G2000 Solar PV DC Type 2 Surge Protector

The VIOX VSP-40/G600, VSP-40/G1000, VSP-40/G1500, and VSP-40/G2000 series are IEC 61643-31 Type 2 DC surge protection devices dedicated to solar photovoltaic combiner boxes, string inverters, and BESS DC buses from 600 V DC up to next-generation 2000 V DC arrays. Available in U-type (2P) and Y-type (3P) fault-tolerant topologies with In 20 kA, Imax 40 kA, <25 ns response, and optional remote signaling.

Série VIOX
VSP-40/G600 – G2000
Tension nominale
600V / 1000V / 1500V / 2000V DC
Surge Rating
In 20 kA · Imax 40 kA (8/20μs)
Standard
IEC 61643-31 · EN 50539-11 · TUV / CE

Vue d'ensemble

The VIOX VSP-40/G600, VSP-40/G1000, VSP-40/G1500, and VSP-40/G2000 series are IEC 61643-31 Type 2 DC surge protection devices dedicated to solar photovoltaic combiner boxes, string inverters, and BESS DC buses from 600 V DC up to next-generation 2000 V DC arrays. Available in U-type (2P) and Y-type (3P) fault-tolerant topologies with In 20 kA, Imax 40 kA, <25 ns response, and optional remote signaling.

Caractéristiques

  • Complete DC PV voltage lineup: Ucpv 600 V, 1000 V, 1500 V, and 2000 V DC (IEC 61643-31 & EN 50539-11 compliant).
  • High-energy DC MOV modules rated In 20 kA / Imax 40 kA (8/20 μs) with <25 ns response and built-in DC arc-safe thermal disconnectors.
  • Available in both U-type (2P) and Y-type (3P, DC+ / PE / DC-) fault-resistant PV circuits that prevent fire on insulation faults.
  • Hot-swappable pluggable cartridges with green/red window and optional 11/12/14 remote alarm contact.

Spécifications

VSP-40/G600 – G2000 Electrical & Mechanical Specifications

ParamètreSpécification
SPD ClassificationPV Type 2 (T2) DC · IEC 61643-31 / EN 50539-11
Max Continuous Operating Voltage (Ucpv)600 V / 1000 V / 1500 V / 2000 V DC
Nominal / Max Discharge Current (8/20 μs)In 20 kA · Imax 40 kA
Niveau de protection de tension (Up)600V: 3.0 kV · 1000V: 3.5 kV · 1500V: 5.5 kV · 2000V: 6.5 kV
Short-Circuit Current Rating (Iscpv)500 A · Leakage Icpv: ≤0.2 mA · Response tA: <25 ns
Topology OptionsType U (2P) & Type Y (3P: DC+ / PE / DC-)
Terminals & Environment6–25 mm² (2.5 N·m) · PBT/PA UL94 V-0 · IP20 · -40°C to +70°C
CertificationsTUV, CE, CB, UKCA, RoHS

VSP-40/G600 – G2000 Available Poles & Dimensions

Voltage TierType U (2P)Type Y (3P)
VSP-40/G600 (600V DC)36 × 83(90) × 67 mm54 × 83(90) × 67 mm
VSP-40/G1000 (1000V DC)36 × 83(90) × 67 mm54 × 83(90) × 67 mm
VSP-40/G1500 / G2000 (1500–2000V DC)54 × 90 × 67 mm54 × 90 × 67 mm / 81 × 90 × 67 mm

Dimensions et Installation

VIOX VSP-40/G600 / G1000 / G1500 / G2000 Solar PV DC Type 2 Surge Protector Dimensional Drawing (mm)
VSP-40/G600 – G2000 Outline & DIN-Rail Mounting Dimensions (unit: mm)
  • Select Ucpv ≥ 1.2 × Voc_max (cold-weather open-circuit string voltage) — e.g., use VSP-40/G1000 for 1000V strings and VSP-40/G1500 for 1500V utility strings.
  • For long DC cable runs (>10 m) between rooftop combiner box and inverter, install one PV SPD at the combiner box and a second at the inverter DC input.
  • Explore the complete VIOX Surge Protection Devices (SPD) catalog for matched AC, Solar PV DC, and SCB backup protection.

FAQ

Why can an AC Type 2 SPD never be used on a 1000V or 1500V DC solar circuit?

DC current has no zero-crossing. If an AC SPD reaches end-of-life on a high-voltage DC string, its thermal disconnector cannot extinguish the sustained DC arc, creating a severe enclosure fire hazard. Always use IEC 61643-31 DC-rated VSP-40/G series.

What is the advantage of Type Y (3P) over Type U (2P) for solar PV?

A 3-module Type Y circuit connects two MOVs in series across DC+/DC- with a third MOV to PE, ensuring that a single insulation fault on either DC pole cannot short-circuit the solar array.