VIOX ELECTRIC
Γλώσσα

VIOX VSP-10C AC Type 3 Terminal Fine Surge Protection Device (18mm 2P, Uoc 10kV)

The VIOX VSP-10C is a compact 18 mm 2-pole AC Type 3 (Class III) fine surge protection device engineered for point-of-use protection of PLCs, CNC controllers, medical instruments, smart home hubs, and LED drivers. Rated Uoc 10 kV with Up 1.5 kV clamping, MOV+GDT leakage-free topology, and remote alarm contacts.

Σειρά VIOX
VSP-10C
Ονομαστική τάση
AC 385V (Un 220/230V)
Surge Rating
Uoc 10 kV (T3) · Up 1.5 kV
Πρότυπο
IEC 61643-11 · Type 3 · TUV / CE

Επισκόπηση

The VIOX VSP-10C is a compact 18 mm 2-pole AC Type 3 (Class III) fine surge protection device engineered for point-of-use protection of PLCs, CNC controllers, medical instruments, smart home hubs, and LED drivers. Rated Uoc 10 kV with Up 1.5 kV clamping, MOV+GDT leakage-free topology, and remote alarm contacts.

Χαρακτηριστικά

  • IEC 61643-11 Type 3 (T3) terminal protection rated Uoc 10 kV with Up 1.5 kV fine residual clamping.
  • Single-module 18 mm width protects both Live and Neutral (2P) with zero earth leakage (MOV + GDT series).
  • High Uc 385 V AC tolerance withstands temporary utility overvoltages without nuisance tripping.
  • Includes built-in thermal disconnector and optional 11/12/14 remote alarm signaling.

Προδιαγραφές

VSP-10C Electrical & Mechanical Specifications

ΠαράμετροςΠροδιαγραφές
SPD ClassificationType 3 (Class III) Fine Protection · IEC 61643-11
Max Continuous Operating Voltage (Uc)385 V AC (Nominal Un 220/230 V AC)
Combination Wave Open-Circuit Voltage (Uoc)10 kV
Επίπεδο Προστασίας Τάσης (Up)1.5 kV · Response Time: ≤100 ns
Leakage Current & IsccrIpe: NONE · Protective Elements: High-Energy MOV + GDT
Dimensions & Terminals18 × 90 × 67 mm (2P) · 4–16 mm² (2.0 N·m) · 35 mm DIN rail
ΠιστοποιήσειςTUV, CE, CB, UKCA, RoHS

VSP-10C Available Poles & Dimensions

ΠολωνοίDimensions (W × H × D)
2P (L + N + PE)18 × 90 × 67 mm (1-Module)

Διαστάσεις & Εγκατάσταση

VIOX VSP-10C AC Type 3 Terminal Fine Surge Protection Device (18mm 2P, Uoc 10kV) Dimensional Drawing (mm)
VSP-10C Outline & DIN-Rail Mounting Dimensions (unit: mm)
  • Install as close as possible (<5 m cable distance) to sensitive terminal equipment such as PLC racks, server power supplies, or industrial HMI panels.
  • Always install downstream of an upstream Type 1 or Type 2 SPD (e.g., VIOX VSP-40).
  • Explore the complete VIOX Surge Protection Devices (SPD) catalog for matched AC, Solar PV DC, and SCB backup protection.

ΣΥΧΝΈΣ ΕΡΩΤΉΣΕΙΣ

When is a Type 3 SPD (VSP-10C) needed if I already have a Type 2 SPD?

When sensitive electronic loads sit more than 10 meters downstream of the main Type 2 SPD, cable inductance can cause surge voltage oscillations up to 2× Up. Installing VSP-10C directly at the equipment panel clamps residuals safely to 1.5 kV.

Χρειάζεστε προσφορά προϊόντος;
Ας το κατασκευάσουμε μαζί.

Στείλτε μας το μοντέλο του προϊόντος, τις τεχνικές ονομαστικές τιμές, την ποσότητα και τις απαιτήσεις OEM. Η ομάδα μας θα εξετάσει την εφαρμογή σας και θα απαντήσει εντός μίας εργάσιμης ημέρας.

Ζητήστε προσφορά