Miniaturní jistič (MCB) VF003

The VIOX VF003 is a 1P+N miniature circuit breaker for overload and short-circuit protection in low-voltage final distribution circuits. Current product data covers 2A to 32A, 120V and 230/400V to 240/415V applications at 50/60Hz, and breaking capacities of 3kA, 4.5kA, or 6kA. It mounts on a standard 35mm DIN rail and supports top or bottom connection.

Konfigurace
1P+N
Jmenovitý proud
2A–32A
Přerušovací kapacita
3 / 4,5 / 6kA
Standardní
IEC/EN 60898-1

Curve, rating, accessories, and compliance documents confirmed before order

Přehled produktů

The VIOX VF003 is a 1P+N miniature circuit breaker for overload and short-circuit protection in low-voltage final distribution circuits. It combines thermal overload protection, magnetic short-circuit tripping, and manual circuit isolation in a compact DIN-rail device.

Current product data covers rated currents from 2A to 32A, 120V and 230/400V to 240/415V applications at 50/60Hz, and breaking capacities of 3kA, 4.5kA, or 6kA. The VF003 is intended for residential, commercial, and selected industrial control or distribution circuits when its rating, trip curve, conductor capacity, and breaking capacity are correctly coordinated with the installation.

Klíčové vlastnosti

  • Thermal-magnetic overload and short-circuit protection
  • 1P+N configuration for final distribution circuits
  • Rated current options from 2A to 32A
  • Breaking capacity options of 3kA, 4.5kA, and 6kA
  • Energy limiting class 3
  • Contact-position indication
  • 35mm DIN-rail mounting with fast clip device
  • Top or bottom connection and compatible auxiliary accessories

Technické specifikace

Electrical Data

ParametrSpecifikace
ModelVF003
Poláci1P+N
Jmenovitý proud (In)2A, 6A, 10A, 16A, 20A, 25A, 32A
Jmenovité napětí (Ue)120V; 230/400V to 240/415V AC
Jmenovitá frekvence50/60Hz
Jmenovité izolační napětí (Ui)500V
Jmenovité impulzní výdržné napětí (Uimp)4kV
Jmenovitá vypínací schopnost3kA, 4.5kA, 6kA
Třída omezení energie3
Trip curve shown in current technical tableB, C
Power-frequency dielectric test2kV for 1 minute
StandardníIEC/EN 60898-1

Mechanical and Environmental Data

ParametrSpecifikace
Elektrická životnost10 000 operací
Mechanická životnost20 000 operací
Contact-position indicatorAno
Stupeň ochranyIP20
Reference temperature for thermal setting30°C
Okolní teplota-5°C to 40°C; daily average not above 35°C
Skladovací teplota-25°C až 70°C
Stupeň znečištění2

Installation Data

ParametrSpecifikace
Terminal connectionCable, U-type busbar, or pin-type busbar
Cable terminal capacityUp to 25mm² / 18–4 AWG
Busbar terminal capacityUp to 10mm² / 18–8 AWG
Utahovací moment2.5N·m / 22in-lb
Montáž35mm DIN rail to EN 60715, fast clip device
Connection directionNahoře nebo dole

Průvodce výběrem

Select the VF003 configuration by coordinating the protective device with the circuit load, conductor capacity, installation conditions, and prospective short-circuit current. Final selection should follow the applicable installation standard and project design.

Jmenovitý proud

Choose a rated current from 2A to 32A that protects the installed conductor while supporting the design load and applicable correction factors.

Křivka cesty

The current technical table lists B and C curves. Use the curve that matches the expected inrush characteristics and confirm availability for the ordered version.

Přerušovací kapacita

Select 3kA, 4.5kA, or 6kA only after confirming that the device rating exceeds the prospective short-circuit current at the installation point.

Rozměry

The verified overall and mounting drawing for VF003 will be added here. Dimensions are not borrowed from another MCB model.

Aplikace

Typical low-voltage final-distribution and control environments where the VF003 rating and protection characteristics may be coordinated with the circuit design.

  • Residential lighting, socket-outlet, and household final circuits
  • Commercial lighting, office equipment, and building distribution circuits
  • Industrial control and auxiliary circuits with suitable inrush characteristics

Instalace a uvedení do provozu

Montáž

Install vertically on a standard 35mm DIN rail using the integrated fast clip. Maintain the enclosure clearances required by the installation design.

Zapojení

Use a conductor and terminal format within the stated capacity. Tighten terminals to 2.5N·m and verify that each conductor is fully secured before energizing.

Inspekce

Before commissioning, confirm mounting, conductor security, manual operation, circuit isolation, and protective-device coordination using appropriate test procedures.

Accessories and System Integration

Current VF003 product information lists compatibility with the following auxiliary functions. Confirm the matching accessory model and wiring arrangement before ordering.

  • Auxiliary contact for remote status indication
  • Shunt release for remote tripping
  • Undervoltage release for voltage-dependent disconnection
  • Alarm contact for trip indication

Compliance and Documentation

The current VF003 technical data identifies IEC/EN 60898-1 as the applicable miniature circuit breaker standard.

Documentation scope

Existing product material also references NF, UKCA, and CE. Certification and declaration documents should be confirmed for the selected version and destination market before they are used in a project submittal.

ČASTO KLADENÉ DOTAZY

What pole configuration does the VF003 use?

The current VF003 product data identifies the device as a 1P+N miniature circuit breaker.

Which rated currents are listed for VF003?

The listed rated-current options are 2A, 6A, 10A, 16A, 20A, 25A, and 32A.

Which breaking capacities are available?

Current product data lists 3kA, 4.5kA, and 6kA. The selected capacity must exceed the prospective short-circuit current at the installation point.

Which trip curves are shown in the technical table?

The current technical table lists B and C curves. Confirm the required curve and its availability when ordering.

Can the VF003 be supplied from the top or bottom?

The current installation data allows connection from the top or bottom, subject to the project wiring design.

Which auxiliary functions are referenced?

The current product material references auxiliary contact, shunt release, undervoltage release, and alarm contact compatibility.

Which compliance documents are available?

IEC/EN 60898-1 is identified in the technical data. NF, UKCA, CE, and destination-specific documentation should be confirmed for the selected version.

Need a VF003 MCB Quote?
Let’s Confirm Your Configuration.

Send us the rated current, trip curve, breaking capacity, quantity, destination market, and accessory requirements. Our team will review the configuration and respond within one business day.