Jak testovat AFDD (zařízení pro detekci obloukového zkratu): Podrobný návod

Jak testovat AFDD (zařízení pro detekci obloukového zkratu): Podrobný návod

Quick Answer: Testing Your AFDD in 30 Seconds

Testing an Arc Fault Detection Device (AFDD) is straightforward: press the test button on the device face, and it should trip immediately, disconnecting power to the protected circuit. If the AFDD doesn’t trip when the test button is pressed, the device has failed and must be replaced immediately. This simple monthly test verifies the arc detection electronics are functioning correctly—a critical safety check that takes less than a minute but could prevent a devastating electrical fire.


Klíčové poznatky

  • Test button verification: Press the AFDD test button monthly; the device should trip instantly to confirm proper arc detection functionality
  • Visual inspection matters: Check LED indicators, look for physical damage, overheating signs, or loose connections before and after testing
  • IEC 62606 compliance: AFDDs must detect dangerous arc faults and trip within 120 milliseconds for high-current arcs according to international standards
  • Different from RCD testing: AFDD test buttons verify arc detection circuits, while RCD test buttons check earth leakage protection—both are essential
  • Professional testing required: Annual inspection by qualified electricians using specialized equipment ensures comprehensive protection beyond basic user testing
  • Replacement indicators: Failed test button response, frequent nuisance tripping, visible damage, or devices older than 10-15 years require immediate replacement

Understanding AFDDs: Why Testing Is Critical

Arc Fault Detection Devices represent a quantum leap in electrical fire prevention technology. While traditional circuit breakers protect against overloads and short circuits, and RCDs (Residual Current Devices) guard against electric shock, neither can detect the most insidious cause of electrical fires: arc faults.

An arc fault occurs when electrical current jumps across a gap in damaged wiring, creating temperatures exceeding 6,000°F (3,315°C)—hot enough to ignite surrounding materials instantly. These dangerous arcs can result from damaged cable insulation, loose terminal connections, crushed wires behind walls, or deteriorated conductors. The current involved may be too low to trip a standard jistič but high enough to start a fire. citace

AFDDs use sophisticated microprocessor technology to continuously analyze current and voltage waveforms, detecting the unique electrical signatures of both series arc faults (broken conductors) and parallel arc faults (line-to-line, line-to-neutral, or line-to-earth arcing). When a hazardous arc pattern is identified, the AFDD disconnects the circuit within milliseconds—long before ignition can occur.

Electrical schematic diagram showing series and parallel arc fault types with VIOX AFDD detection zones and protection comparison to MCB and RCD devices
Technical Schematic: VIOX AFDD Detection Zones & Protection Comparison vs. MCB and RCD for Series and Parallel Arc Faults.

Regular testing ensures this life-saving technology remains operational. Unlike passive protection devices, AFDDs contain active electronic components that can degrade over time or fail due to power surges, environmental factors, or manufacturing defects.


AFDD vs. Traditional Protection: Understanding the Differences

Ochranné zařízení Primární funkce Co detekuje Co mu uniká Metoda testování
MCB/MCCB Nadproudová ochrana Overloads, short circuits Arc faults, earth leakage Manual trip or load test
Proudový chránič/proudový chránič Prevence úrazu elektrickým proudem Earth leakage current (≥30mA) Arc faults, overloads Test button (simulates leakage)
AFDD Požární prevence Series & parallel arc faults Standard overloads (requires MCB) Test button (simulates arc signature)
RCBO Kombinovaná ochrana Overloads, short circuits, earth leakage Obloukové poruchy Test button (RCD function only)
AFDD+RCBO Komplexní ochrana All electrical hazards None (complete protection) Two test buttons or combined

This comparison highlights why AFDDs are increasingly mandated in high-risk applications. Traditional MCB a RCCB cannot detect the low-current, high-temperature arcing that causes most electrical fires. Understanding the difference between RCBO vs AFDD is essential for proper electrical system design.


When and How Often Should You Test an AFDD?

Recommended Testing Schedule

Monthly User Testing (Test Button)

  • Frequency: Every 30 days minimum
  • Duration: 10-15 seconds per device
  • Performed by: Building occupants or facility managers
  • Purpose: Verify basic arc detection functionality

Six-Monthly Detailed Inspection

  • Frequency: Every 6 months as per BS 7671:2018+A2:2022
  • Duration: 2-5 minutes per device
  • Performed by: Competent electrical personnel
  • Purpose: Visual inspection, connection verification, LED diagnostics

Annual Professional Testing

  • Frequency: Annually or as per manufacturer specifications
  • Duration: 15-30 minutes per installation
  • Performed by: Qualified electricians with calibrated equipment
  • Purpose: Comprehensive functional verification, insulation resistance testing, thermal imaging

After Electrical Events

  • Trigger: Lightning strikes, power surges, nearby electrical faults
  • Timing: Within 24-48 hours of event
  • Purpose: Ensure AFDD electronics weren’t damaged by transient overvoltages

Critical Testing Situations

Test AFDDs immediately if you observe:

  • Unexplained circuit disconnections
  • Burning smells near the electrical panel
  • Flickering lights on AFDD-protected circuits
  • Visible damage to the AFDD housing
  • LED indicators showing fault conditions
  • After any work on the protected circuit

Regular testing is not optional—it’s a safety imperative. Many insurance policies now require documented AFDD testing for commercial properties, and failure to maintain these devices could void coverage in the event of an electrical fire.


Step-by-Step Guide: How to Test an AFDD

Comparison diagram showing three AFDD testing methods - manual test button, visual inspection, and professional arc fault simulation testing
Testing AFDDs Safely: A visual breakdown of Manual Testing, Visual Inspection, and Professional Arc Simulation Methods.

Safety Precautions Before Testing

Before touching any electrical equipment:

  1. Inform building occupants: Testing will temporarily disconnect power to protected circuits
  2. Identify critical loads: Ensure no life-safety equipment (medical devices, security systems, refrigeration) is on the circuit
  3. Prepare for power loss: Save computer work, note which appliances will lose power
  4. Ensure adequate lighting: Have a flashlight ready if testing lighting circuits
  5. Wear appropriate PPE: Safety glasses and insulated gloves recommended for professional testing
  6. Verify access: Ensure the electrical panel is accessible and not obstructed

Varování: Never attempt to test AFDDs during thunderstorms or if you notice any burning smells, sparks, or unusual heat from the electrical panel. Call a qualified electrician immediately.

Method 1: Basic Test Button Verification (Monthly)

This is the primary test method for end-users and should be performed monthly.

Electrical technician pressing test button on VIOX AFDD arc fault detection device in distribution panel for monthly safety verification
Routine Safety Verification: A technician effectively performing a manual test using the built-in test button on a VIOX AFDD.

Step 1: Locate the AFDD
Open your electrical panel and identify the AFDD. It will typically be:

  • Wider than standard circuit breakers (often 2-4 module widths)
  • Labeled “AFDD” or “Arc Fault Detection Device”
  • Equipped with a test button (usually marked “T” or “TEST”)
  • May have LED indicators showing operational status

Step 2: Note the Initial Status
Before testing, observe:

  • LED indicator status (green typically means normal operation)
  • Circuit breaker position (should be in the “ON” position)
  • Any warning indicators or fault lights

Step 3: Press the Test Button

  • Firmly press and hold the test button for 1-2 seconds
  • The AFDD should trip immediately (within 0.5 seconds)
  • You’ll hear a distinct “click” as the mechanism operates
  • The breaker handle will move to the “OFF” or middle “TRIPPED” position
  • LED indicators may change (some models flash to indicate test mode)

Step 4: Verify Complete Disconnection

  • Confirm power is disconnected to the protected circuit
  • Check that appliances or lights on that circuit are off
  • This verifies the mechanical trip mechanism is functioning

Step 5: Reset the AFDD

  • Move the breaker handle fully to the “OFF” position first
  • Then switch it back to the “ON” position
  • LED should return to normal operational status (typically solid green)
  • Verify power is restored to the circuit

Step 6: Document the Test

  • Record the test date, AFDD location, and result
  • Note any abnormalities (slow response, failure to trip, unusual sounds)
  • Maintain a testing log for compliance and insurance purposes

Result Interpretation:

  • VYHOVUJE: AFDD trips within 1 second, resets normally, LED shows normal status
  • FAIL: No trip, delayed trip (>2 seconds), won’t reset, or LED shows fault condition
  • ⚠️ Investigate: Unusual sounds, excessive heat, or intermittent operation

Method 2: Visual and Physical Inspection (Six-Monthly)

Step 1: External Visual Examination
Inspect the AFDD for:

  • Cracks, discoloration, or melted plastic (indicates overheating)
  • Burn marks around terminals or on the device face
  • Loose mounting on the DIN rail
  • Damaged test button or handle
  • Faded or illegible labeling

Step 2: Terminal Connection Check
With power OFF and following lockout/tagout procedures:

  • Verify all terminal screws are tight (use manufacturer’s specified torque)
  • Check for signs of arcing at connections (blackening, pitting)
  • Ensure conductors are properly stripped and fully inserted
  • Verify correct wire gauge for the AFDD rating

Step 3: LED Diagnostic Interpretation
Modern AFDDs use LED patterns to communicate status:

LED Pattern Význam Požadovaná akce
Solid green Normal operation Žádný
Flashing green Self-test in progress None (automatic)
Solid red Arc fault detected Investigate circuit, identify fault source
Flashing red Device malfunction Replace AFDD immediately
No LED Power failure or device failure Check supply, test device
Alternating red/green Nuisance trip threshold reached Review circuit loading, check for interference

Consult your specific AFDD manufacturer’s documentation for exact LED interpretations, as patterns vary between brands.

Step 4: Thermal Inspection
Using a non-contact infrared thermometer or thermal imaging camera:

  • Measure AFDD surface temperature during normal operation
  • Temperature should not exceed 40°C (104°F) above ambient
  • Hot spots indicate poor connections or internal component failure
  • Compare temperature to adjacent circuit breakers for reference

Step 5: Busbar and Neutral Connection Verification

  • Ensure the AFDD is properly seated on the přípojnice
  • Verify neutral connections are secure (AFDDs require neutral for electronics)
  • Check for corrosion on busbar contacts
  • Confirm proper Montáž na lištu DIN

Method 3: Professional Testing with Specialized Equipment (Annual)

This testing should only be performed by qualified electricians with appropriate test equipment.

Step 1: Insulation Resistance Testing

  • Důležité: Disconnect AFDDs before performing 500V DC insulation tests
  • AFDDs contain sensitive electronics that can be damaged by high test voltages
  • Test the circuit wiring separately from the AFDD
  • Reconnect AFDD after testing and verify operation

Step 2: Arc Fault Simulation Testing
Specialized AFDD testers can simulate actual arc fault conditions:

  • Generate controlled series arc signatures
  • Generate parallel arc fault waveforms
  • Verify trip time is within IEC 62606 specifications (≤120ms for high-current arcs)
  • Test at various current levels and arc characteristics
  • Confirm the AFDD discriminates between normal switching transients and dangerous arcs

Step 3: RCD Function Testing (for AFDD+RCBO combinations)
If your AFDD is combined with an RCD:

  • Use a calibrated RCD tester
  • Test at 1× rated residual current (should not trip)
  • Test at 5× rated residual current (should trip within 40ms)
  • Verify test button operation independently tests RCD function
  • Confirm proper earth fault discrimination

Step 4: Load Current Verification

  • Measure actual circuit current under normal operating conditions
  • Verify current is within AFDD rating (typically 6A, 10A, 16A, 20A, 32A, 40A)
  • Check for overloading that could cause nuisance tripping
  • Ensure proper dimenzováním jističů koordinace

Step 5: Waveform Analysis
Using a power quality analyzer:

  • Capture voltage and current waveforms during operation
  • Look for harmonic distortion that might affect AFDD operation
  • Identify sources of electrical noise that could cause false tripping
  • Verify proper neutral-to-earth voltage (should be <0.2V under load)

Troubleshooting Common AFDD Testing Issues

Problem 1: AFDD Won’t Trip When Test Button Is Pressed

Možné Příčiny:

  • Internal electronic failure
  • Test button mechanism broken
  • Power supply to AFDD electronics interrupted
  • Device has reached end of life

Řešení:

  • Verify AFDD has power (check LED indicators)
  • Try test button multiple times
  • Check neutral connection (required for AFDD electronics)
  • Replace the AFDD immediately—this is a critical safety failure

Problem 2: AFDD Trips Immediately After Reset

Možné Příčiny:

  • Actual arc fault present in the circuit
  • Damaged appliance or equipment
  • Compromised wiring insulation
  • AFDD malfunction causing false positives

Řešení:

  • Odpojte všechny zátěže od obvodu
  • Reset AFDD with no load connected
  • If it holds, reconnect loads one at a time to identify the faulty device
  • Inspect circuit wiring for damage, especially at junction boxes and outlets
  • If AFDD trips with no load, replace the device

Problem 3: Frequent Nuisance Tripping

Možné Příčiny:

  • Normal motor starting currents (power tools, compressors)
  • High-frequency switching devices (LED dimmers, variable speed drives)
  • Electrical noise from nearby equipment
  • Incorrect AFDD type for the application
  • Loose connections causing intermittent arcing

Řešení:

  • Review circuit loading and connected equipment
  • Ensure AFDD is rated for the application (some are optimized for lighting, others for socket circuits)
  • Check all connections for tightness
  • Consider installing filters for noisy equipment
  • Consult manufacturer’s guidance on compatible loads
  • May need to relocate sensitive equipment to non-AFDD circuit

Problem 4: LED Shows Fault Indication

Možné Příčiny:

  • Self-test failure detected
  • Internal component degradation
  • Memory of previous arc fault event
  • Voltage supply issues

Řešení:

  • Consult manufacturer’s manual for specific LED code interpretation
  • Some AFDDs require manual reset after fault indication
  • If fault persists after reset, replace the device
  • Document fault codes for warranty claims

Problem 5: AFDD Gets Hot During Operation

Možné Příčiny:

  • Loose terminal connections (most common)
  • Overloading beyond rated current
  • Poor contact with busbar
  • Porucha vnitřní součásti
  • Inadequate ventilation in electrical panel

Řešení:

  • Turn off power immediately if temperature exceeds 60°C (140°F)
  • Check and tighten all terminal connections to manufacturer’s torque specifications
  • Verify circuit current is within AFDD rating
  • Ensure proper electrical panel ventilation
  • Replace AFDD if overheating persists after correcting connections

Understanding AFDD Test Results and LED Indicators

Modern AFDDs incorporate sophisticated self-diagnostic capabilities that communicate device status through LED indicators and test responses. Understanding these signals is crucial for proper maintenance.

Self-Test Function

Many AFDDs feature automatic self-testing that occurs:

  • At power-up (when breaker is switched on)
  • At regular intervals (typically once every 24 hours)
  • Before and after arc detection events

During self-test, the AFDD:

  • Verifies the arc detection algorithm is functioning
  • Checks internal memory and processor operation
  • Tests the trip mechanism readiness
  • Confirms power supply to electronics is adequate

If the self-test fails, the AFDD will typically indicate this through LED patterns and may either trip immediately (fail-safe mode) or display a warning while remaining operational (depending on manufacturer design philosophy).

Manual Test Button vs. Automatic Testing

Funkce Manual Test Button Automatic Self-Test
Frekvence User-initiated (monthly recommended) Automatic (daily or at power-up)
What It Tests Complete arc detection and trip mechanism Internal electronics and algorithm only
User Intervention Requires button press and manual reset No user action required
Přerušení obvodu Yes—power disconnected No—circuit remains energized
Dodržování předpisů Required by BS 7671 for manual-test devices Satisfies testing requirement if no manual button
Reliability Verification Confirms end-to-end functionality Detects electronic failures only

Důležité: AFDDs with automatic testing still benefit from periodic manual test button operation to verify the complete trip mechanism, not just the electronics. citace


AFDD Testing in Different Applications

Rezidenční instalace

In homes, AFDDs are increasingly required for:

  • Bedroom circuits (highest fire risk due to occupancy during sleep)
  • Circuits supplying socket outlets
  • Lighting circuits in timber-framed buildings
  • Home offices with extensive electronic equipment
  • Circuits in areas with limited fire detection

Testing Considerations:

  • Schedule testing during daytime hours to avoid disrupting sleep
  • Coordinate with household members to save computer work
  • Test bedroom circuits first (highest priority)
  • Document testing for insurance compliance

Komerční a průmyslové prostředí

Commercial installations require more rigorous testing protocols:

  • Documented testing schedules with sign-off
  • Integration with preventive maintenance programs
  • Coordination with facility operations to minimize disruption
  • Compliance with occupational safety regulations
  • Integration with building management systems for remote monitoring

Zvláštní aspekty:

  • Test during scheduled maintenance windows
  • Coordinate with IT departments for server room circuits
  • Notify security systems before testing (may trigger alarms)
  • Zvážit arc flash hazards during professional testing
  • Maintain detailed records for regulatory compliance

Solární fotovoltaické systémy

AFDDs in photovoltaic systems face unique challenges:

  • DC arc faults are more persistent than AC arcs
  • High voltage (up to 1500V) increases arc intensity
  • Outdoor installations expose devices to harsh environments
  • Rapid shutdown requirements add complexity

Testovací protokol:

  • Test during daylight hours when system is energized
  • Use DC-rated AFDDs specifically designed for PV applications
  • Verify coordination with DC jističe a isolators
  • Inspect for UV degradation and moisture ingress
  • Zkontrolujte slučovací box connections annually

Instalace nabíjení EV

Electric vehicle charging circuits benefit from AFDD protection:

  • High current loads (up to 80A continuous)
  • Frequent connection/disconnection cycles
  • Outdoor or garage installations with moisture exposure
  • Long cable runs increase arc fault risk

Testing Recommendations:

  • Test before and after EV charging sessions
  • Verify AFDD is rated for continuous high current
  • Zkontrolujte, zda proper circuit protection coordination
  • Inspect charging cable connections for wear
  • Consider Type B RCD requirements for DC fault protection

AFDD Maintenance Best Practices

Beyond testing, proper maintenance extends AFDD service life and ensures reliable protection.

Úvahy o životním prostředí

Řízení teploty:

  • Maintain electrical panel ambient temperature below 40°C (104°F)
  • Ensure adequate ventilation—avoid overcrowded panels
  • Consider panel cooling fans in hot environments
  • Derate AFDD current capacity in high-temperature installations

Humidity Control:

  • Keep electrical panels dry—moisture causes corrosion and false tripping
  • Použijte weatherproof enclosures pro venkovní instalace
  • Instalace breathable cable glands to prevent condensation
  • Consider dehumidifiers in damp locations

Dust and Contamination:

  • Clean electrical panels annually using compressed air
  • Avoid oil, chemical, or conductive dust exposure
  • Maintain proper Krytí IP for the environment
  • Seal cable entries to prevent contamination ingress

Connection Integrity

Loose connections are the leading cause of AFDD problems:

Specifikace točivého momentu:

  • Vždy používejte hodnoty momentu specifikované výrobcem
  • Typical range: 1.0-2.5 Nm for terminal screws
  • Use a calibrated torque screwdriver for critical connections
  • Re-torque connections annually or after any circuit work

Příprava drátů:

  • Strip conductors to exact length specified (typically 10-12mm)
  • Use ferrules on stranded conductors
  • Ensure no stray strands that could cause short circuits
  • Verify correct wire gauge for AFDD rating

Firmware and Technology Updates

Some modern AFDDs feature updateable firmware:

  • Check manufacturer websites for firmware updates
  • Updates may improve arc detection algorithms
  • May add compatibility with new load types
  • Professional installation required for firmware updates

Vedení záznamů

Maintain comprehensive documentation:

  • Installation date and installer details
  • Testing log with dates, results, and tester identification
  • Any fault conditions and corrective actions
  • Manufacturer warranty information
  • Historie výměn

When to Replace an AFDD

AFDDs don’t last forever. Replace devices when:

Nutná okamžitá výměna:

  • Failed test button operation
  • Visible damage, cracks, or melting
  • Persistent overheating (>60°C)
  • LED indicates internal fault
  • Časté nevysvětlitelné zakopnutí
  • After exposure to lightning strike or major surge

Scheduled Replacement:

  • Age exceeds 10-15 years (even if functioning)
  • Manufacturer discontinues support
  • Updated standards require new features
  • Building use changes (e.g., residential to commercial)
  • Circuit modifications exceed AFDD rating

Upgrade Considerations:

  • Newer models offer improved arc detection algorithms
  • Reduced nuisance tripping with modern designs
  • Smaller form factors (single-module AFDDs now available)
  • Enhanced diagnostics and remote monitoring capabilities
  • Better coordination with inteligentní jističe

Často kladené otázky (FAQ)

Q: How is testing an AFDD different from testing an RCD?
A: While both use test buttons, they verify different protection functions. An RCD test button injects a small current to earth to simulate a ground fault, testing shock protection. An AFDD test button simulates an arc fault signature to verify the arc detection electronics and trip mechanism. If you have an AFDD+RCBO combination device, it may have two test buttons—one for each function—or a single button that tests both simultaneously.

Q: Can I test an AFDD with a standard circuit breaker tester?
A: No. Standard circuit breaker testers cannot simulate arc fault conditions. AFDD testing requires either the built-in test button (for basic verification) or specialized arc fault simulation equipment (for comprehensive professional testing). Using inappropriate test equipment may damage the AFDD or provide false results.

Q: What should I do if my AFDD keeps tripping but passes the test button check?
A: This indicates a real arc fault condition in your circuit, not an AFDD malfunction. Systematically disconnect loads to identify the faulty appliance or circuit segment. Common culprits include damaged extension cords, failing appliances with worn brushes (power tools, vacuum cleaners), or deteriorated wiring. If tripping occurs with no load connected, the circuit wiring itself is compromised and requires professional inspection.

Q: Do AFDDs need to be tested if they have automatic self-test features?
A: Yes. While automatic self-testing verifies the internal electronics, manual test button operation confirms the complete trip mechanism functions correctly. BS 7671:2018+A2:2022 recommends six-monthly manual testing even for AFDDs with automatic self-test capabilities. The manual test provides end-to-end verification that automatic testing cannot fully replicate.

Q: Can AFDDs be tested while the circuit is under load?
A: Yes, but it’s not recommended for routine testing. When you press the test button, the AFDD will trip and disconnect power immediately, which could damage sensitive electronic equipment or cause data loss. Always inform building occupants, save computer work, and ensure no critical loads are operating before testing.

Q: How long should an AFDD take to trip when the test button is pressed?
A: An AFDD should trip within 0.5-1.0 seconds of pressing the test button. If the response is slower (2+ seconds) or the device doesn’t trip at all, it has failed and must be replaced immediately. The test button simulates a severe arc fault condition that should trigger instant disconnection.

Q: Are AFDDs required by electrical codes?
A: Requirements vary by jurisdiction. In the UK, BS 7671:2018 Amendment 2 (effective September 2022) requires AFDDs for AC final circuits in higher-risk premises and strongly recommends them for all residential installations. In the US, the National Electrical Code (NEC) requires AFCIs (similar devices) in dwelling unit bedrooms and other specified locations. Always consult local electrical codes and regulations for specific requirements in your area.


Conclusion: AFDD Testing Is Non-Negotiable for Electrical Safety

Arc Fault Detection Devices represent the cutting edge of electrical fire prevention technology, but they’re only effective if they’re functioning correctly. Regular testing—monthly test button operation, six-monthly visual inspections, and annual professional verification—ensures these critical safety devices remain ready to protect lives and property.

The few minutes invested in AFDD testing can prevent catastrophic consequences. Electrical fires cause billions in property damage annually and claim hundreds of lives—many of which could be prevented with properly maintained arc fault protection. As a B2B manufacturer committed to electrical safety, VIOX Electric emphasizes that AFDD testing isn’t just a regulatory checkbox—it’s a fundamental responsibility of electrical system ownership.

Implement a documented testing schedule, train personnel on proper procedures, maintain detailed records, and never ignore warning signs of AFDD malfunction. The test button on your AFDD is there for a reason—use it regularly, and ensure the device that protects you is itself protected through proper maintenance and timely replacement.

For more information on electrical protection devices and safety standards, explore our comprehensive guides on výběrem ochrany obvodů, electrical panel safetya industrial maintenance programs.


O společnosti VIOX Electric: As a leading B2B manufacturer of electrical protection equipment, VIOX Electric produces IEC 62606-compliant Arc Fault Detection Devices engineered for reliability, safety, and ease of installation. Our AFDDs feature advanced arc detection algorithms, robust construction, and comprehensive diagnostic capabilities to protect lives and property from electrical fires. Contact our technical team for specification assistance, bulk procurement, or custom panel solutions.

Autor obrázku

Ahoj, já jsem Joe, profesionál s 12 let zkušeností v elektrotechnickém průmyslu. Na VIOX Elektrické, moje zaměření je na poskytování vysoce kvalitní elektrické řešení šité na míru potřebám našich klientů. Moje zkušenosti se klene průmyslové automatizace, bytové elektroinstalace a obchodních elektrických systémů.Kontaktujte mě [email protected] pokud se u nějaké dotazy.

Obsah
    Přidejte záhlaví pro zahájení generování obsahu
    Požádejte o cenovou nabídku nyní