VIOX ELECTRIC
Dil

VIOX VOPD3-63VAYA / VOPD3-100VAYA Automatic Phase Selector with Current Protection (63A / 100A)

The VIOX VOPD3-63VAYA (63 A) and VOPD3-100VAYA (100 A) are intelligent 3-phase-input to single-phase-output automatic phase selectors with built-in over-voltage, under-voltage, and over-current protection. When the active phase drops out or drifts out of voltage bounds, the internal magnetic latching relay automatically switches your critical single-phase load to the healthiest available phase based on programmable ABC–CBA priority order.

VIOX Modeli
VOPD3-63VAYA / VOPD3-100VAYA
Gerilim
AC 3×220 V In → 1-Phase 220 V Out
Güncel
63 A / 100 A (3–100 A Adj.)
Biçim
102 × 91 × 52 mm

Genel Bakış

The VIOX VOPD3-63VAYA (63 A) and VOPD3-100VAYA (100 A) are intelligent 3-phase-input to single-phase-output automatic phase selectors with built-in over-voltage, under-voltage, and over-current protection. When the active phase drops out or drifts out of voltage bounds, the internal magnetic latching relay automatically switches your critical single-phase load to the healthiest available phase based on programmable ABC–CBA priority order.

Özellikler

  • 3-phase (L1/L2/L3 + N) input to clean single-phase (L + N) output for continuous power to critical single-phase loads.
  • Programmable phase priority sequence: ABC, ACB, BAC, BCA, CAB, or CBA, with optional automatic return to priority phase.
  • Adjustable over-current protection (3–63 A / 3–100 A or OFF) plus over-voltage (230–300 V) and under-voltage (140–210 V) limits.
  • High-endurance magnetic latching relay rated for 100,000 electrical and mechanical operations with ≤1% voltage accuracy.
  • Compliant with EU Low Voltage Directive 2014/35/EU, EMC 2014/30/EU, and RoHS 2011/65/EU.

Teknik Özellikler

VOPD3-63VAYA / VOPD3-100VAYA Technical Specifications

ParametreŞartname
Input / Output Architecture3-Phase AC 3×220 V + N Input → Single-Phase L + N Output (Not for 110 V systems)
Operating Voltage & FrequencyAC 140–300 V L-N · 50/60 Hz · ≤1% accuracy
Max Load & Over-Current RangeVOPD3-63VAYA: 3–63 A (default 40 A) · VOPD3-100VAYA: 3–100 A (default 60 A)
Over-Voltage / Under-VoltageOV: 230–300 V (default 270 V) · UV: 140–210 V (default 170 V)
Phase Priority SelectionABC / ACB / BAC / BCA / CAB / CBA (default ABC)
Transfer Detection & Return DelayOFF / 1–500 s (default 10 s) · Priority-return switch ON/OFF
Relay, Life & InsulationMagnetic latching relay · 100,000 cycles · Ui 450 V · IP20
Dimensions & Directives102 (H) × 91 (W) × 52 (D) mm · LVD / EMC / RoHS

VOPD3-63VAYA / VOPD3-100VAYA Programmable Menu Parameters

KodParametreMenzilFactory Default
Power-On DelayStartup Delay1–500 s10 s
OV / OV RecOver-Voltage Trip / Recovery230–300 V / 225–295 V270 V / 265 V
UV / UV RecUnder-Voltage Trip / Recovery140–210 V / 145–215 V170 V / 175 V
Over-CurrentCurrent Protection & Action Time3–63 A or 3–100 A (OFF) / 0.1–30 s40 A or 60 A / 1.0 s
Priority OrderPhase Selection SequenceABC / ACB / BAC / BCA / CAB / CBAABC
Return ModePriority Phase Auto-Return & DelayON / OFF · OFF–500 sON / 10 s

Wiring & Setup Guide

  • IN Terminals: connect Neutral (N) plus all three incoming phases (L1, L2, L3) from a 3×220/380 V supply.
  • OUT Terminals: connect single-phase Neutral (N) and switched Live (L) directly to the protected single-phase distribution board.
  • Not suitable for 110 V networks. Install on a 35 mm DIN rail with adequate ventilation.
  • Explore the complete VIOX Voltage Protectors catalog for matched DIN-rail switchgear.

SSS

Can VOPD3-63VAYA power a 3-phase motor?

No. VOPD3-63VAYA/100VAYA takes 3-phase input and outputs single-phase (L + N) power by automatically selecting the healthiest phase. For 3-phase motor loads, use VOPD3-63VA or VOPD3-63VAS.

What happens if all three incoming phases have voltage faults simultaneously?

If no healthy phase is available within the configured voltage window, VOPD3-63VAYA disconnects the output completely and illuminates the Fault LED until a valid phase returns.

Ürün Teklifi mi İstiyorsunuz?
Birlikte İnşa Edelim.

Bize ürün modelini, teknik değerleri, miktarı ve OEM gereksinimlerini gönderin. Ekibimiz başvurunuzu inceleyecek ve bir iş günü içinde yanıt verecektir.

Teklif İsteyin