The VIOX VOPD3-63VAYA (63 A) and VOPD3-100VAYA (100 A) are intelligent 3-phase-input to single-phase-output automatic phase selectors with built-in over-voltage, under-voltage, and over-current protection. When the active phase drops out or drifts out of voltage bounds, the internal magnetic latching relay automatically switches your critical single-phase load to the healthiest available phase based on programmable ABC–CBA priority order.
คุณสมบัติ
- 3-phase (L1/L2/L3 + N) input to clean single-phase (L + N) output for continuous power to critical single-phase loads.
- Programmable phase priority sequence: ABC, ACB, BAC, BCA, CAB, or CBA, with optional automatic return to priority phase.
- Adjustable over-current protection (3–63 A / 3–100 A or OFF) plus over-voltage (230–300 V) and under-voltage (140–210 V) limits.
- High-endurance magnetic latching relay rated for 100,000 electrical and mechanical operations with ≤1% voltage accuracy.
- Compliant with EU Low Voltage Directive 2014/35/EU, EMC 2014/30/EU, and RoHS 2011/65/EU.
ข้อมูลจำเพาะ
VOPD3-63VAYA / VOPD3-100VAYA Technical Specifications
| พารามิเตอร์ | ข้อมูลจำเพาะ |
|---|---|
| Input / Output Architecture | 3-Phase AC 3×220 V + N Input → Single-Phase L + N Output (Not for 110 V systems) |
| Operating Voltage & Frequency | AC 140–300 V L-N · 50/60 Hz · ≤1% accuracy |
| Max Load & Over-Current Range | VOPD3-63VAYA: 3–63 A (default 40 A) · VOPD3-100VAYA: 3–100 A (default 60 A) |
| Over-Voltage / Under-Voltage | OV: 230–300 V (default 270 V) · UV: 140–210 V (default 170 V) |
| Phase Priority Selection | ABC / ACB / BAC / BCA / CAB / CBA (default ABC) |
| Transfer Detection & Return Delay | OFF / 1–500 s (default 10 s) · Priority-return switch ON/OFF |
| Relay, Life & Insulation | Magnetic latching relay · 100,000 cycles · Ui 450 V · IP20 |
| Dimensions & Directives | 102 (H) × 91 (W) × 52 (D) mm · LVD / EMC / RoHS |
VOPD3-63VAYA / VOPD3-100VAYA Programmable Menu Parameters
| รหัส | พารามิเตอร์ | พิสัย | Factory Default |
|---|---|---|---|
| Power-On Delay | Startup Delay | 1–500 s | 10 s |
| OV / OV Rec | Over-Voltage Trip / Recovery | 230–300 V / 225–295 V | 270 V / 265 V |
| UV / UV Rec | Under-Voltage Trip / Recovery | 140–210 V / 145–215 V | 170 V / 175 V |
| Over-Current | Current Protection & Action Time | 3–63 A or 3–100 A (OFF) / 0.1–30 s | 40 A or 60 A / 1.0 s |
| Priority Order | Phase Selection Sequence | ABC / ACB / BAC / BCA / CAB / CBA | ABC |
| Return Mode | Priority Phase Auto-Return & Delay | ON / OFF · OFF–500 s | ON / 10 s |
Wiring & Setup Guide
- IN Terminals: connect Neutral (N) plus all three incoming phases (L1, L2, L3) from a 3×220/380 V supply.
- OUT Terminals: connect single-phase Neutral (N) and switched Live (L) directly to the protected single-phase distribution board.
- Not suitable for 110 V networks. Install on a 35 mm DIN rail with adequate ventilation.
- Explore the complete VIOX Voltage Protectors catalog for matched DIN-rail switchgear.
คำถามที่พบบ่อย
Can VOPD3-63VAYA power a 3-phase motor?
No. VOPD3-63VAYA/100VAYA takes 3-phase input and outputs single-phase (L + N) power by automatically selecting the healthiest phase. For 3-phase motor loads, use VOPD3-63VA or VOPD3-63VAS.
What happens if all three incoming phases have voltage faults simultaneously?
If no healthy phase is available within the configured voltage window, VOPD3-63VAYA disconnects the output completely and illuminates the Fault LED until a valid phase returns.