VIOX VSP1-D20/2(S) Podłączany jednobiegunowy SPD
VIOX VSP1-D20/2(S) Pluggable Single-Pole SPD offers robust surge protection for sub-distribution boards. This Class II/III device safeguards L-PE and N-PE modes with 10kA nominal and 20kA maximum discharge current. Featuring high-energy MOV elements, it operates from 60V to 400V AC with < 25ns response time. The pluggable design ensures easy installation on 35mm DIN rails. IEC 61643-11:2011 and EN 61643-11:2012 compliant, it provides voltage protection levels from 0.2kV to 1.8kV. With IP20 protection, thermal safeguards, and optional remote contacts, this versatile SPD suits various electrical installations, combining reliability and performance in a compact, user-friendly package for enhanced power system protection.
Wyślij swoje wymagania, wycenimy je w ciągu 12 godzin
- TEL:+8618066396588
- Whatsapp:+8618066396588
- Email:sales@viox.com
VIOX VSP1-D20/2(S) Podłączany jednobiegunowy SPD
Przegląd
The VIOX VSP1-D20/2(S) is a high-performance Pluggable Single-Pole Surge Protective Device (SPD) designed for use in sub-distribution boards. This versatile device offers robust protection for both L-PE and N-PE modes, making it an ideal solution for various electrical installations.
Kluczowe cechy
- Class II, Class III, Type 2, Type 3 device
- Miejsce użytkowania: Podrozdzielnice
- Mode of Protection: L-PE, N-PE
- Surge Ratings: In = 10 kA (8/20 μs)
- IEC/EN/UL Category: Class II+III / Type 2+3
- Elementy ochronne: High Energy MOV
- Obudowa: Konstrukcja wtykowa
- Compliance: IEC 61643-11:2011, EN 61643-11:2012
Specyfikacja techniczna
IEC Electrical | 75 | 150 | 275 | 320 | 385 | 440 |
---|---|---|---|---|---|---|
Nominal AC Voltage (50/60Hz) | 60 V | 120 V | 230 V | 230 V | 230 V | 400 V |
Maximum Continuous Operating Voltage (AC) | 75 V | 150 V | 275V | 320 V | 385 V | 440 V |
Nominalny prąd rozładowania (8/20 μs) | 10 kA | 10 kA | 10 kA | 10 kA | 10 kA | 10 kA |
Maksymalny prąd rozładowania (8/20 μs) | 20 kA | 20 kA | 20 kA | 20 kA | 20 kA | 20 kA |
Poziom ochrony napięciowej | 0.2 kV | 0.6 kV | 1.3 kV | 1.5 kV | 1.5 kV | 1.8 kV |
Czas reakcji | < 25 ns | |||||
Bezpiecznik zapasowy (maks.) | 125 A gL / gG | |||||
Prąd zwarciowy (AC) | 10 kA | |||||
TOV Withstand 5s | 90V | 180V | 335V | 335V | 335V | 580V |
TOV 120min | 115V | 230V | 440V | 440V | 440V | 765V |
mode | Withstand | Withstand | Safe Fail | Safe Fail | Safe Fail | Safe Fail |
Specyfikacje mechaniczne i środowiskowe
- Zakres temperatur pracy: od -40°F do +158°F [od -40°C do +70°C].
- Dopuszczalna wilgotność robocza: 5%...95%
- Ciśnienie atmosferyczne i wysokość: 80k Pa ... 106k Pa / -500 m....2000 m
- Moment dokręcenia śrub zaciskowych: 39,9 lbf.in [4,5 Nm]
- Przekrój przewodu (maks.): 2 AWG (lite, skręcone) / 4 AWG (elastyczne)
- 35 mm² (lite, skręcane) / 25 mm² (elastyczne)
- Montaż: 35 mm szyna DIN, EN 60715
- Stopień ochrony: IP 20 (wbudowany)
- Materiał obudowy: Tworzywo termoplastyczne: Stopień gaszenia UL 94 V-0
- Ochrona termiczna: Tak
- Stan pracy / wskazanie usterki: Zielony ok / Czerwony usterka
Dodatkowe funkcje
- Styki zdalne (RC): Opcjonalnie
- Zdolność przełączania RC: AC: 250V / 0.5 A; DC: 250V / 0.1 A;125V / 0.2 A;75V / 0.5 A
- Przekrój przewodu RC (maks.): 16 AWG (lity) / 1,5 mm²(lity)