VIOX Elektrik
Language

Peranti Pengesan Kerosakan Arka Magnetik VAF3-40M

The VIOX VAF3-40M magnetic arc fault detection device combines arc-fault detection with Type A residual-current, overload and short-circuit protection. Designed for 240 V AC, 50 Hz final circuits, it is available in 6-40 A ratings, B or C tripping characteristics and 10 or 30 mA sensitivities for residential and commercial installations.

Nilai Semasa
6-40 A
Arus Baki
10, 30 mA
Ciri-ciri pelantikan
B, C
Arus Litar Pintas
6 kA

Gambaran keseluruhan

The VAF3-40M is a magnetic arc fault detection device combining arc-fault detection with Type A residual-current, overload and short-circuit protection. Designed for AC 50 Hz final circuits, it has a rated voltage of 240 V AC and is available in rated currents from 6 A to 40 A. The 1P+N device offers B or C overcurrent tripping characteristics and 10 mA or 30 mA residual-current sensitivities. It is intended for residential and commercial final circuits requiring combined protection against arc faults, electric shock, overload and short circuits.

Ciri-ciri

  • Magnetic version with integrated arc-fault, Type A residual-current, overload and short-circuit protection.
  • Mematuhi IEC/EN 61009-1 dan IEC/EN 62606.
  • Pilihan arus terkadar daripada 6 A hingga 40 A.
  • Ciri-ciri pelantikan arus lebih B dan C.
  • Kepekaan arus baki 10 mA dan 30 mA.
  • Sentuhan pemutus beban dengan arus litar pintas berkadar 6 kA.

Spesifikasi

Data Elektrik

Parameter Spesifikasi
Arus terkadar (In) 6, 10, 13, 16, 20, 25, 32, 40 A
Voltan berkadar (Ue) 240 V AC
Kekerapan operasi 50 Hz
Voltan kendalian litar ujian minimum 196 V
Voltan kendalian litar ujian maksimum 253 V
Voltan penebat berkadar (Ui) 250 V
Voltan tahan impuls berkadar (Uimp) 4 kV
Arus litar pintas berkadar 6 kA
Kapasiti pensuisan berkadar jumlah maksimum 6 kA
Kekuatan tahan arus lonjakan 0.25 kA
Kehilangan kuasa bagi setiap laluan arus 3 W
Fius sandaran litar pintas (SCPD) 100 A
Jenis fius sandaran gG
Kategori voltan lampau III

Data Perlindungan

Parameter Spesifikasi
Konfigurasi produk AFDD dengan perlindungan arus baki Jenis A, beban lampau dan litar pintas bersepadu
Bilangan kutub 1P+N
Jenis arus baki Jenis A
Arus kendalian baki berkadar (IΔn) 10, 30 mA
Ciri pelantikan arus lebih B, C
Spesifikasi litar beban Sentuhan pemutus beban

Data pemasangan

Parameter Spesifikasi
Jenis terminal Terminal jenis skru; sambungan atas atau bawah pada litar beban
Kedudukan pengalir neutral Kiri atau kanan
Panjang kabel sambungan maksimum 70 m antara papan agihan dan soket alur keluar yang paling jauh
Kapasiti pengapit terminal 1-25 mm²
Tork pengetatan terminal 2-2.4 N·m

Data piawaian

Parameter Spesifikasi
Piawaian yang terpakai IEC/EN 61009-1; IEC/EN 62606

Panduan Pemilihan

Kedudukan kod Maknanya Rujukan katalog
V VIOX identification V
AF Keluarga produk perlindungan kerosakan arka AF
3 Design series 3
40 Arus bingkai maksimum 40
M Magnetic version M
C16 Ciri pelantikan C dan arus berkadar 16 A
A30 Perlindungan arus baki Jenis A 30 mA

Nilai Semasa

Pilih kadaran tersenarai daripada 6 A hingga 40 A untuk memadankan kadaran litar akhir.

Ciri-ciri pelantikan

Pilih ciri pelantikan arus lebih B atau C mengikut keperluan litar.

Kepekaan Baki

Pilih kepekaan arus kendalian baki Jenis A sebanyak 10 mA atau 30 mA.

Aplikasi

  • Litar akhir kediaman.
  • Litar akhir komersial.
  • Circuits requiring combined arc-fault and electric-shock protection.
  • Circuits requiring combined overload and short-circuit protection.

Pemasangan

  • Gunakan terminal jenis skru dengan sambungan atas atau bawah pada litar beban.
  • Sahkan sama ada konfigurasi yang dipilih meletakkan konduktor neutral di sebelah kiri atau kanan.
  • Gunakan konduktor dalam kapasiti pengapit terminal yang disenaraikan iaitu 1-25 mm².
  • Gunakan tork pengetatan terminal yang disenaraikan iaitu 2-2.4 N·m.
  • Pastikan panjang kabel yang disambungkan berada dalam lingkungan 70 m antara papan agihan dan soket alur keluar yang paling jauh.
  • Gunakan fius sandaran litar pintas 100 A gG yang disenaraikan.

Soalan Lazim

What distinguishes the VAF3-40M?

The catalog identifies the VAF3-40M as the magnetic version of the arc fault detection device.

Which protection functions are integrated?

Ia menggabungkan pengesanan kerosakan arka dengan perlindungan arus baki Jenis A, beban lampau dan litar pintas.

Apakah arus berkadar dan ciri-ciri pelantikan yang tersedia?

Katalog tersebut menyenaraikan kadaran 6, 10, 13, 16, 20, 25, 32 dan 40 A dengan ciri-ciri pelantikan arus lebih B atau C.

Apakah sensitiviti arus baki yang ditawarkan?

The VAF3-40M provides Type A residual-current protection with 10 mA or 30 mA sensitivity.

What is the rated short-circuit current?

Arus litar pintas berkadar ialah 6 kA.

Which standards are listed for the VAF3-40M?

Piawaian yang terpakai ialah IEC/EN 61009-1 dan IEC/EN 62606.

Perlukan Sebut Harga Produk?
Mari Bina Bersama.

Hantarkan model produk, kadaran teknikal, kuantiti, dan keperluan OEM kepada kami. Pasukan kami akan menyemak permohonan anda dan memberi maklum balas dalam masa satu hari bekerja.

Minta Sebut Harga