Gambaran keseluruhan
The VAF3-40M is a magnetic arc fault detection device combining arc-fault detection with Type A residual-current, overload and short-circuit protection. Designed for AC 50 Hz final circuits, it has a rated voltage of 240 V AC and is available in rated currents from 6 A to 40 A. The 1P+N device offers B or C overcurrent tripping characteristics and 10 mA or 30 mA residual-current sensitivities. It is intended for residential and commercial final circuits requiring combined protection against arc faults, electric shock, overload and short circuits.
Ciri-ciri
- Magnetic version with integrated arc-fault, Type A residual-current, overload and short-circuit protection.
- Mematuhi IEC/EN 61009-1 dan IEC/EN 62606.
- Pilihan arus terkadar daripada 6 A hingga 40 A.
- Ciri-ciri pelantikan arus lebih B dan C.
- Kepekaan arus baki 10 mA dan 30 mA.
- Sentuhan pemutus beban dengan arus litar pintas berkadar 6 kA.
Spesifikasi
Data Elektrik
| Parameter | Spesifikasi |
|---|---|
| Arus terkadar (In) | 6, 10, 13, 16, 20, 25, 32, 40 A |
| Voltan berkadar (Ue) | 240 V AC |
| Kekerapan operasi | 50 Hz |
| Voltan kendalian litar ujian minimum | 196 V |
| Voltan kendalian litar ujian maksimum | 253 V |
| Voltan penebat berkadar (Ui) | 250 V |
| Voltan tahan impuls berkadar (Uimp) | 4 kV |
| Arus litar pintas berkadar | 6 kA |
| Kapasiti pensuisan berkadar jumlah maksimum | 6 kA |
| Kekuatan tahan arus lonjakan | 0.25 kA |
| Kehilangan kuasa bagi setiap laluan arus | 3 W |
| Fius sandaran litar pintas (SCPD) | 100 A |
| Jenis fius sandaran | gG |
| Kategori voltan lampau | III |
Data Perlindungan
| Parameter | Spesifikasi |
|---|---|
| Konfigurasi produk | AFDD dengan perlindungan arus baki Jenis A, beban lampau dan litar pintas bersepadu |
| Bilangan kutub | 1P+N |
| Jenis arus baki | Jenis A |
| Arus kendalian baki berkadar (IΔn) | 10, 30 mA |
| Ciri pelantikan arus lebih | B, C |
| Spesifikasi litar beban | Sentuhan pemutus beban |
Data pemasangan
| Parameter | Spesifikasi |
|---|---|
| Jenis terminal | Terminal jenis skru; sambungan atas atau bawah pada litar beban |
| Kedudukan pengalir neutral | Kiri atau kanan |
| Panjang kabel sambungan maksimum | 70 m antara papan agihan dan soket alur keluar yang paling jauh |
| Kapasiti pengapit terminal | 1-25 mm² |
| Tork pengetatan terminal | 2-2.4 N·m |
Data piawaian
| Parameter | Spesifikasi |
|---|---|
| Piawaian yang terpakai | IEC/EN 61009-1; IEC/EN 62606 |
Panduan Pemilihan
| Kedudukan kod | Maknanya | Rujukan katalog |
|---|---|---|
| V | VIOX identification | V |
| AF | Keluarga produk perlindungan kerosakan arka | AF |
| 3 | Design series | 3 |
| 40 | Arus bingkai maksimum | 40 |
| M | Magnetic version | M |
| C16 | Ciri pelantikan C dan arus berkadar | 16 A |
| A30 | Perlindungan arus baki Jenis A | 30 mA |
Nilai Semasa
Pilih kadaran tersenarai daripada 6 A hingga 40 A untuk memadankan kadaran litar akhir.
Ciri-ciri pelantikan
Pilih ciri pelantikan arus lebih B atau C mengikut keperluan litar.
Kepekaan Baki
Pilih kepekaan arus kendalian baki Jenis A sebanyak 10 mA atau 30 mA.
Aplikasi
- Litar akhir kediaman.
- Litar akhir komersial.
- Circuits requiring combined arc-fault and electric-shock protection.
- Circuits requiring combined overload and short-circuit protection.
Pemasangan
- Gunakan terminal jenis skru dengan sambungan atas atau bawah pada litar beban.
- Sahkan sama ada konfigurasi yang dipilih meletakkan konduktor neutral di sebelah kiri atau kanan.
- Gunakan konduktor dalam kapasiti pengapit terminal yang disenaraikan iaitu 1-25 mm².
- Gunakan tork pengetatan terminal yang disenaraikan iaitu 2-2.4 N·m.
- Pastikan panjang kabel yang disambungkan berada dalam lingkungan 70 m antara papan agihan dan soket alur keluar yang paling jauh.
- Gunakan fius sandaran litar pintas 100 A gG yang disenaraikan.
Muat turun
Soalan Lazim
What distinguishes the VAF3-40M?
The catalog identifies the VAF3-40M as the magnetic version of the arc fault detection device.
Which protection functions are integrated?
Ia menggabungkan pengesanan kerosakan arka dengan perlindungan arus baki Jenis A, beban lampau dan litar pintas.
Apakah arus berkadar dan ciri-ciri pelantikan yang tersedia?
Katalog tersebut menyenaraikan kadaran 6, 10, 13, 16, 20, 25, 32 dan 40 A dengan ciri-ciri pelantikan arus lebih B atau C.
Apakah sensitiviti arus baki yang ditawarkan?
The VAF3-40M provides Type A residual-current protection with 10 mA or 30 mA sensitivity.
What is the rated short-circuit current?
Arus litar pintas berkadar ialah 6 kA.
Which standards are listed for the VAF3-40M?
Piawaian yang terpakai ialah IEC/EN 61009-1 dan IEC/EN 62606.