SPD unipolar enchufable VIOX VSP1-D20/1(S)
VIOX VSP1-D20/1(S) Pluggable Single-Pole SPD offers robust surge protection for sub-distribution boards. This Class II/III device safeguards L-PE and N-PE modes with 10kA nominal discharge current. Featuring high-energy MOV elements, it operates from 60V to 400V AC. The pluggable design ensures easy installation on 35mm DIN rails. IEC 61643-11:2011 and EN 61643-11:2012 compliant, it provides voltage protection levels from 0.2kV to 1.8kV. With IP20 protection, thermal safeguards, and optional remote contacts, this versatile SPD suits various electrical installations, combining reliability and performance in a compact, user-friendly package.
Envíenos sus requisitos, le haremos un presupuesto en 12 horas
- TEL:+8618066396588
- Whatsapp:+8618066396588
- Email:sales@viox.com
SPD unipolar enchufable VIOX VSP1-D20/1(S)
Visión general
The VIOX VSP1-D20/1(S) is a high-performance Pluggable Single-Pole Surge Protective Device (SPD) designed for use in sub-distribution boards. This versatile device offers robust protection for both L-PE and N-PE modes, making it an ideal solution for various electrical installations.
Características principales
- Class II, Class III, Type 2, Type 3 device
- Localización de uso: Subdistribution Boards
- Modo de protección: L-PE, N-PE
- Surge Ratings: In = 10 kA (8/20 μs)
- IEC/EN/UL Category: Class II+III / Type 2+3
- Elementos de protección: MOV de alta energía
- Carcasa: Diseño enchufable
- Conformidad: IEC 61643-11:2011, EN 61643-11:2012
Especificaciones técnicas
IEC Eléctrica | 75 | 150 | 275 | 320 | 385 | 440 |
---|---|---|---|---|---|---|
Tensión nominal de CA (50/60 Hz) | 60 V | 120 V | 230 V | 230 V | 230 V | 400 V |
Tensión máxima de funcionamiento continuo (CA) | 75 V | 150 V | 275V | 320 V | 385 V | 440 V |
Corriente nominal de descarga (8/20 μs) | 10 kA | 10 kA | 10 kA | 10 kA | 10 kA | 10 kA |
Corriente máxima de descarga (8/20 μs) | 20 kA | 20 kA | 20 kA | 20 kA | 20 kA | 20 kA |
Nivel de protección de tensión | 0.2 kV | 0.6 kV | 1.3 kV | 1,5 kV | 1,5 kV | 1,8 kV |
Especificaciones mecánicas y medioambientales
- Operating Temperature Range: -40°F to +158°F (-40°C to +70°C)
- Humedad de funcionamiento admisible: 5%...95%
- Presión atmosférica y altitud: 80k Pa ... 106k Pa / -500 m....2000 m
- Par de apriete del tornillo del terminal: 39.9 lbf.in [4.5 Nm]
- Sección del conductor (máx.) 2 AWG (sólido, trenzado) / 4 AWG (flexible)
- Montaje: Carril DIN de 35 mm, EN 60715
- Grado de protección: IP 20 (integrado)
- Material de la carcasa: Termoplástico: Grado de extinción UL 94 V-0
- Protección térmica: Sí
- Estado de funcionamiento / Indicación de fallo: Verde correcto / Rojo defectuoso
Características adicionales
- Contactos remotos (RC): Opcional
- RC Switching Capacity: AC: 250V / 0.5 A; DC: 250V / 0.1 A; 125V / 0.2 A; 75V / 0.5 A
Sección del conductor RC (máx.) 16 AWG (sólido) / 1,5 mm²(sólido)