Přehled
VOSA00-CU 750V VIOX Electric supplies the 750V DC Fast Acting Semiconductor Protection Fuse, aR class, DC 750V, 100A-630A, ultra-low I²t, strong current limiting, 100kA breaking. Compliant with IEC 60269-4 and GB/T13539.4. For rail transit, energy storage and EV charging.
VIOX Electric makes the 750V DC Fast Acting Semiconductor Protection Fuse for engineers who protect power semiconductors against DC short circuits. Rated for 750V DC service, the series shields IGBT modules, thyristors and rectifier diodes inside EV charging piles, battery storage converters, renewable power station inverters, rail DC systems and industrial converter plants, where a slowly clearing fuse would let fault energy vaporize the very device it is meant to save.
Funkce
- Rated voltage 750VDC and current capacity 100A for ess & semiconductor high-speed fuse applications.
- High interrupting performance (100kA) with rapid current-limiting fault clearing.
- Engineered and tested in accordance with GB/T 13539.4 / GB/T13539.4 / IEC 60269-4 standards.
- Precision-engineered low-power-loss silver-plated contacts and high-temperature ceramic or flame-retardant housing.
- Direct OEM replacement geometry for standardized industrial, solar PV, ESS, and EV protection panels.
Specifikace
VOSA00-CU Technical Specifications
| Sériové číslo | Rated Current A | Pre-arcing I²t A²s | Melting I²t A²s | Power dissipation W |
| 1 | 100 | 420 | 2500 | 21 |
| 2 | 125 | 710 | 4600 | 25 |
| 3 | 160 | 1250 | 8300 | 31 |
| 4 | 200 | 2100 | 15100 | 35 |
| 5 | 250 | 4300 | 25700 | 41 |
| 6 | 315 | 7200 | 48500 | 50 |
| 7 | 350 | 9800 | 63700 | 56 |
| 8 | 400 | 17900 | 108600 | 62 |
| 9 | 450 | 23600 | 143300 | 68 |
| 10 | 500 | 31500 | 191200 | 73 |
| 11 | 550 | 42200 | 256100 | 78 |
| 12 | 630 | 60100 | 364800 | 82 |
VOSA00-CU Ratings & Dimensions Table 2
| Rated Current (A) | Conventional Time (h) | Conventional Current | |
| “gR” | |||
| Inf | lf | ||
| ln≤63 | 1 | 1.13ln | 1.6ln |
| 63<In≤160 | 2 | ||
| 160<ln≤400 | 3 | ||
| 400<ln | 4 | ||
| Note:ln is the rated current of the fuse; lnf is the conventional non-fusing current; if is the conventional fusing current. | |||
Selection & Installation Notes
- Verify system maximum voltage (750VDC) and prospective short-circuit fault current before selecting the fuse link or holder rating.
- Apply ambient-temperature derating when operating inside sealed outdoor combiner boxes or high-density inverter cabinets above 40°C.
- Always de-energize circuits before replacing cylindrical, blade, or bolted fuse links, and use insulated fuse pullers for NH/NT types.
- Explore the complete VIOX Fuse & Fuse Holder catalog for matched holders, bases, and disconnectors.
ČASTO KLADENÉ DOTAZY
What voltage and current ratings does the VIOX VOSA00-CU 750V DC Fast Acting Semiconductor Protection Fuse support?
This VIOX VOSA00-CU series is rated for 750VDC with a current rating of 100A and 100kA breaking performance. Refer to the technical specification table above for individual part numbers and ampere steps.
Which international standards apply to VIOX VOSA00-CU 750V DC Fast Acting Semiconductor Protection Fuse?
The VOSA00-CU series is designed and verified to GB/T 13539.4 / GB/T13539.4 / IEC 60269-4 requirements for safe overcurrent and short-circuit protection.
Where is the VIOX VOSA00-CU 750V DC Fast Acting Semiconductor Protection Fuse typically installed?
It is engineered for ess & semiconductor high-speed fuse circuits, protecting cables, busbars, semiconductors, battery modules, or string feeders against thermal overload and high-energy short-circuit faults.
Can VIOX supply matched fuse holders, bases, or OEM private-label packaging?
Yes. VIOX Electric supplies matched DIN-rail fuse holders, NH/NT fuse bases, disconnectors, and OEM/ODM bulk packaging with technical datasheets upon RFQ.