Trên trang này
On a standard 11-pin circular relay base (undecal DIN-rail socket), coil power is fixed on Pin 2 and Pin 10. The remaining nine terminals follow one of two standard wiring architectures: a Type A 3PDT general-purpose relay (three independent changeover contact sets: 1-3-4, 6-7-5, and 11-9-8) or a Type B 11-pin multifunction timer relay (two DPDT timed output contacts plus Pin 5, 6, and 7 external Gate, Start, and Reset control inputs).
Safety & Scope Notice: Always verify exact pin numbers, coil polarity, and contact ratings against the wiring diagram printed on the side of your specific relay housing before energizing. This guide focuses exclusively on 11-pin socket pinouts, 3PDT vs. 11-pin timer wiring, and 24 V DC / AC coil wiring under IEC 61810-1 và IEC 61812-1:2023. For general time-delay operating modes (On-Delay, Off-Delay, Interval), refer to our dedicated timer relay function modes guide.
11-Pin Relay Base Pinout Quick Reference
Every standard 11-pin circular (undecal) relay socket numbers its terminals from 1 to 11 around a keyed center spigot. Viewed from the bottom of the relay with the alignment keyway notch at 6 o’clock, pins count clockwise from Pin 1 to Pin 11—so top-view socket screw terminals appear mirrored unless you read the numerals molded onto the base.
| Pin Number | Type A: Standard 3PDT General-Purpose Relay | Type B: 11-Pin Multifunction Timer Relay | Lưu Ý Quan Trọng Về Đi Dây |
|---|---|---|---|
| Pin 1 | Pole 1 Common (COM 1) | Timed Output 1 Common (COM 1) | Shared feed terminal for Pole 1 |
| Pin 2 | Coil Power Terminal (A2 / – or N) | Power Supply + Signal Common | Fixed power pin; also serves as dry-contact reference on Type B timers |
| Pin 3 | Pole 1 Normally Open (NO 1) | Timed Output 1 Normally Open (NO 1) | Closes with Pin 1 when energized / timed out |
| Pin 4 | Pole 1 Normally Closed (NC 1) | Timed Output 1 Normally Closed (NC 1) | Closed with Pin 1 in de-energized state |
| Pin 5 | Pole 2 Normally Closed (NC 2) | Gate Input (Pause Timing) | Dry contact to Pin 2 on timers — never apply line voltage |
| Pin 6 | Pole 2 Common (COM 2) | Start Input (Trigger Timing) | Dry contact to Pin 2 on timers — never apply line voltage |
| Pin 7 | Pole 2 Normally Open (NO 2) | Reset Input (Clear Timer) | Dry contact to Pin 2 on timers — never apply line voltage |
| Pin 8 | Pole 3 Normally Closed (NC 3) | Timed Output 2 Normally Closed (NC 2) | Closed with Pin 11 in de-energized state |
| Pin 9 | Pole 3 Normally Open (NO 3) | Timed Output 2 Normally Open (NO 2) | Closes with Pin 11 when energized / timed out |
| Pin 10 | Coil Power Terminal (A1 / + or L) | Power Supply Input (L / +V) | Fixed power pin paired with Pin 2 |
| Pin 11 | Pole 3 Common (COM 3) | Timed Output 2 Common (COM 2) | Shared feed terminal for Pole 3 / Output 2 |
Pinout Rule: Never assume two 11-pin relays share the same middle pins (Pins 5, 6, and 7): on a 3PDT relay they form an isolated power-switching contact set, whereas on an 11-pin multifunction timer they are low-voltage logic inputs referenced to Pin 2.
Type A — Standard 3PDT 11-Pin Relay Wiring Diagram
A standard 3PDT (three-pole double-throw) 11-pin general-purpose relay uses Pins 2 and 10 to energize its electromagnetic coil and devotes the remaining nine pins to three electrically isolated Form C changeover switches. Because all three poles switch simultaneously from one coil, a single 3PDT relay can drive a contactor coil, trigger a PLC status input, and interlock a warning circuit in one compact socket.
- Coil Power: Connect control supply voltage across Pin 2 và Pin 10. (If using a 24 V DC coil fitted with an internal LED indicator or flyback diode, observe the + and – polarity printed on the housing.)
- Pole 1 Contact Set: Pin 1 (COM) — Pin 4 (NC) — Pin 3 (NO)
- Pole 2 Contact Set: Pin 6 (COM) — Pin 5 (NC) — Pin 7 (NO)
- Pole 3 Contact Set: Pin 11 (COM) — Pin 8 (NC) — Pin 9 (NO)
For quick bench verification and electrical exam reference, the standard 3PDT contact pairs are fixed as follows:
- Normally Closed (NC) Pin Pairs: 1–4, 6–5, Và 11–8 (continuous when coil power is off).
- Normally Open (NO) Pin Pairs: 1–3, 6–7, Và 11–9 (continuous when coil power is on).

3PDT Verification Rule: Before applying load power to a freshly wired 11-pin base, verify zero-ohm continuity across pairs 1–4, 6–5, and 11–8 with the coil de-energized—any open reading indicates a mirrored socket reading or loose terminal clamp.
Type B — 11-Pin Multifunction Timer Relay Wiring Diagram
An 11-pin multifunction timer relay retains power input on Pins 2 and 10 and two timed DPDT output contact sets on 1–4–3 và 11–8–9, but repurposes Pins 5, 6, and 7 as dedicated external control inputs (Gate, Start, and Reset). This architecture enables remote cycle triggering, timing pause, and mid-cycle reset without cutting main power to the timer—capabilities impossible on an 8-pin octal base.
When specifying or wiring panel-mounted industrial timers from the Dòng rơ-le thời gian VIOX, always wire the 11-pin external control inputs strictly as dry (voltage-free) contacts:
- Power Supply (Pins 2 & 10): Connect rated AC or DC supply voltage to Pin 2 (N / 0 V) and Pin 10 (L / +V).
- Signal Common (Pin 2): Use Pin 2 as the shared return rail for all external control switches.
- Start Input (Pin 6 to Pin 2): Closing a dry pushbutton or PLC relay output between Pin 6 and Pin 2 initiates the preset timing cycle.
- Reset Input (Pin 7 to Pin 2): Bridging Pin 7 to Pin 2 immediately resets elapsed time to zero and returns timed output contacts to their resting state.
- Gate Input (Pin 5 to Pin 2): Bridging Pin 5 to Pin 2 pauses the active countdown while retaining elapsed time until the gate switch re-opens.
- Timed DPDT Outputs: Wire Output 1 across Pin 1 (COM) / Pin 4 (NC) / Pin 3 (NO) and Output 2 across Pin 11 (COM) / Pin 8 (NC) / Pin 9 (NO).
Cảnh báo an toàn quan trọng: Never apply external 120 V AC, 230 V AC, or live +24 V DC supply voltage directly to Pin 5 (Gate), Pin 6 (Start), or Pin 7 (Reset). These pins connect directly to the internal low-voltage timing logic—feeding line voltage across them instantly destroys the timer circuit.

For a broader overview across 8-pin, 11-pin, and DIN-rail relay architectures, see our hướng dẫn sơ đồ đấu nối rơ-le thời gian.
How to Wire a 24V DC vs 120V/230V AC 11-Pin Relay
Wiring a 24 V DC 11-pin relay differs critically from wiring a 120 V AC or 230 V AC version because DC coils can include polarity-sensitive internal components and generate high inductive voltage spikes upon de-energization. Matching coil voltage, polarity, and transient suppression protects upstream PLC transistor outputs from premature failure.
- 24 V DC Coil Polarity Check: Plain electromechanical DC coils without accessories are non-polarized, but most industrial 24 V DC 11-pin relays include an internal status LED or built-in suppression diode across Pins 2 and 10. Always check the housing diagram for explicit + and – markings (commonly Pin 10 as +24 V DC and Pin 2 as 0 V DC, though model markings govern). Reversing DC polarity on a diode-equipped relay creates a direct short across the internal diode when energized.
- External Flyback Diode Suppression (DC Only): If your 24 V DC 11-pin relay lacks internal suppression and is driven by a PLC solid-state output, install a reverse-biased diode (such as a 1N4007) across the coil terminals with the cathode band connected to +24 V DC and the anode to 0 V DC. Never install a standard DC diode across an AC coil—use an RC snubber or varistor rated for AC instead.
- 120 V AC / 230 V AC Coil Wiring: AC coils have no DC polarity, so Line (L) and Neutral (N) connect to Pins 10 and 2 respectively (keeping Neutral on Pin 2 is essential on Type B timers so dry-contact Start/Reset/Gate switches reference the neutral side rather than hot line potential).
For detailed voltage-tolerance and coil-selection trade-offs across control panels, see our timer relay voltage selection guide (12V, 24V, 120V, 230V).
8-Pin Octal vs 11-Pin Relay Base — When Do You Need 11 Pins?
Panel builders choose between an 8-pin octal base, an 11-pin undecal base, và một modern 18 mm DIN-rail modular timer based on required pole count, external control inputs, and available cabinet width. While 8-pin sockets suffice for basic DPDT power-on timing, 11-pin sockets become mandatory whenever a circuit needs a third independent pole or remote Start/Reset/Gate control.
| Comparison Axis | 8-Pin Octal Base | 11-Pin Undecal Base | 18 mm Modular DIN-Rail Timer |
|---|---|---|---|
| Coil / Supply Pins | Pin 2 & Pin 7 | Pin 2 & Pin 10 | Dedicated A1 & A2 screw terminals |
| General-Purpose Relay Poles | DPDT (2 changeover poles) | 3PDT (3 changeover poles) | Typically 1 SPDT or 2 DPDT |
| Timer External Control Inputs | None (power-on trigger only) | Dedicated Start (Pin 6), Reset (Pin 7), Gate (Pin 5) | Dedicated Y1 / S / R control terminals |
| Typical Panel Width | ~40 mm circular socket | ~40–45 mm circular socket | 17.5 mm to 18 mm (saves over 50% DIN-rail space) |
| Best Application Fit | Legacy 2-pole replacement panels (e.g., VIOX AH2 và AH3 8-pin circular timers) | Legacy 3PDT switching or plug-in timers needing Start/Reset/Gate | New compact industrial control cabinets and OEM builds |
Upgrade Rule: Choose an 8-pin octal timer such as the AH2 multi-timer relay hay AH3 multi-timer relay for straightforward power-on timing without external signal inputs; keep an 11-pin circular socket when replacing existing plug-in 3PDT relays or legacy 11-pin timers; and for new space-constrained control panels requiring multifunction timing without bulky circular bases, upgrade directly to a slim 18 mm DIN-rail unit such as the VIOX FCT18-M multifunction timer relay. For contact-pole trade-offs between single- and double-pole timer outputs, compare SPDT vs. DPDT time relays.
Common 11-Pin Socket Wiring Mistakes & Troubleshooting
Most commissioning failures on 11-pin circular relay bases stem from three repeatable field errors rather than defective coils or contacts: mirrored top-view socket reading, live voltage misapplied to timer control pins, and unverified contact continuity. Running a structured power-off multimeter check catches these faults before energizing the control panel.
- Mirrored Socket Pin Numbering (Top View vs. Bottom View): Reading a relay’s bottom-view pinout chart and wiring the front-facing DIN-rail socket in the same clockwise direction mirrors every terminal except Pin 6. Always read the physical numerals molded beside each screw clamp on the socket rather than counting visually around the ring.
- Applying Live Voltage to Timer Control Pins (5, 6, 7): Technicians accustomed to 3PDT relays sometimes wire live 24 V or 230 V load feeds onto Pin 6 (which is COM 2 on a 3PDT relay) after plugging in an 11-pin timer—instantly burning out the Start input circuit. Always confirm whether the socket hosts a Type A 3PDT relay or a Type B timer before energizing.
- Confusing Coil Continuity with Contact Continuity During Testing: With power locked out, verify expected NC continuity across 1–4, 6–5, and 11–8 (3PDT) or 1–4 and 11–8 (11-pin timer), and verify infinite resistance across NO pairs 1–3, 6–7, and 11–9. Then apply rated coil voltage across Pins 2 and 10 and confirm every contact transfers cleanly. For step-by-step multimeter testing procedures, follow our guide on how to test a time delay relay.
Những Câu Hỏi Thường
Which pins are normally closed on an 11-pin relay base?
On a standard Type A 3PDT 11-pin relay base, the three normally closed (NC) contact pairs are Pins 1–4, Pins 6–5, Và Pins 11–8 (where 1, 6, and 11 are common terminals). On a Type B 11-pin multifunction timer, the two timed NC pairs are Pins 1–4 và Pins 11–8, because Pins 5, 6, and 7 are reassigned to Gate, Start, and Reset inputs.
Which pins are the coil on an 11-pin relay?
On virtually all standard 11-pin circular (undecal) general-purpose relays and 11-pin multifunction timers, the coil or power supply connects to Pin 2 and Pin 10. Always confirm exact polarity on the relay housing when wiring a 24 V DC coil fitted with an internal LED indicator or flyback diode.
What is the difference between an 8-pin and 11-pin timer relay?
An 8-pin octal timer uses Pins 2 and 7 for power and provides two DPDT output poles with no external signal pins, limiting it to power-on timing. An 11-pin timer moves power to Pins 2 and 10 and adds three dedicated dry-contact control pins—Start (Pin 6), Reset (Pin 7), and Gate (Pin 5)—for remote cycle triggering and pausing.
Can I use a 24V DC 11-pin relay on an AC circuit?
No. A 24 V DC relay coil cannot be powered by 24 V AC, 120 V AC, or 230 V AC because DC coils lack the shading ring and higher AC inductive impedance needed to prevent severe chattering and rapid coil burnout. However, a 24 V DC relay’s isolated contacts can safely switch an AC load circuit provided the contacts carry an explicit AC voltage and current rating.
Nguồn tham khảo
- IEC 61810-1 — Rơ le điện cơ sơ cấp: các yêu cầu chung và an toàn
- IEC 61812-1:2023 — Time relays and coupling relays for industrial and residential use: requirements and tests
- VIOX Electric — Timer Relay Product Center
- VIOX Electric — AH2 Multi-Timer Relay
- VIOX Electric — AH3 Multi-Timer Relay
- VIOX Electric — FCT18-M Multifunction Timer Relay



