VIOX ELECTRIC
Bahasa

Aksesori Kontaktor VIOX CJX2s

Select compatible accessories for VIOX CJX2s and CJX2s-M
contactors.

  • KAT/KAS auxiliary contact blocks
  • KTD pneumatic delay heads and KMI interlocks
  • FS coil suppression modules and KDC dust covers
  • JR28s thermal overload relays with discrete adjustment ranges

Gambaran keseluruhan

VIOX CJX2s contactor accessories support auxiliary signalling,
time-delay control, interlocking, coil transient suppression and motor
overload protection. Select each accessory by its function and the exact
contactor frame; the items shown are individually selected components,
not a bundled kit.

Blok Sesentuh Tambahan

KAT blocks mount on the front/top of the contactor. KAS blocks are
side-mounted. NO and NC quantities refer to auxiliary contacts.

Miniature model Standard model NO NC
KAT-M20 KAT-20 2 0
KAT-M11 KAT-11 1 1
KAT-M02 KAT-02 0 2
KAT-M40 KAT-40 4 0
KAT-M31 KAT-31 3 1
KAT-M22 KAT-22 2 2
KAT-M13 KAT-13 1 3
KAT-M04 KAT-04 0 4
  • KAT-M: CJX2s-M06–M16 miniature contactors.
  • Standard KAT: CJX2s-09–630, according to the supplied compatibility
    table.
  • KAS-20: 2NO; KAS-11: 1NO + 1NC; KAS-02: 2NC. Listed for
    CJX2s-09–630.

Pneumatic Time-Delay Heads

Model Delay function Julat pelarasan
KTD-C1 Tunda hidup 0.1–3 s
KTD-C2 Tunda hidup 0.1–30 s
KTD-C3 Tunda hidup 10–180 s
KTD-D1 Tunda mati 0.1–3 s
KTD-D2 Tunda mati 0.1–30 s
KTD-D3 Tunda mati 10–180 s

The KTD heads provide pneumatic time delay with 1NO + 1NC auxiliary
contacts. The catalogue lists CJX2s-09–630 compatibility.

Interlocks and Dust Covers

Aksesori Catalogue compatibility
KMI mechanical interlock CJX2s-09–38
KMI electrical interlock CJX2s-09–95
KDC-1 front dust cover CJX2s-09–38
KDC-2 front dust cover CJX2s-40–95

Select interlocks for the actual paired-contactor arrangement. A
front dust cover does not establish a new enclosure IP rating.

Coil Surge Suppression
Modul

Module Contactor frame
FS-M CJX2s-M06–M16
FS-18 CJX2s-09–18
FS-32 CJX2s-25–32
FS-65 CJX2s-40–65
FS-95 CJX2s-80–95

The catalogue lists AC/DC voltage bands of 24–48 V, 100–250 V and
380–440 V. Select the module voltage version to match the coil supply as
well as the contactor frame. These coil suppression accessories are not
distribution-panel surge protective devices.

Geganti Beban Terma

Geganti Available adjustment ranges (A) Listed contactor frames
JR28s-25 0.1–0.16; 0.16–0.25; 0.25–0.4; 0.4–0.63; 0.63–1; 1–1.6; 1.25–2;
1.6–2.5; 2.5–4; 4–6; 5.5–8; 7–10; 9–13; 12–18; 17–25
CJX2s-09, 12, 18, 25
JR28s-36 23–32; 28–36 CJX2s-32, 38
JR28s-93 23–32; 30–40; 37–50; 48–65; 55–70; 63–80; 80–93 CJX2s-40, 50, 65, 80, 95

Each adjustment range is a separate selection. Choose a relay range
that includes the motor nameplate current and coordinate it with the
contactor and short-circuit protective device.

Maklumat Pesanan

Provide the exact contactor model, accessory model, required NO/NC
arrangement, delay range or relay current range, coil supply voltage
where applicable, and quantity. Confirm mounting compatibility for the
supplied contactor version before ordering.

Perlukan Sebut Harga Produk?
Mari Bina Bersama.

Hantarkan model produk, kadaran teknikal, kuantiti, dan keperluan OEM kepada kami. Pasukan kami akan menyemak permohonan anda dan memberi maklum balas dalam masa satu hari bekerja.

Minta Sebut Harga