Tổng quan
VOSA3-PK 1500V VIOX supplies the 1500V DC Heavy-Duty Semiconductor Protection Fuse, aR class, DC 1500V, 400A-1000A, low I²t, 150kA breaking at ≤15ms time constant. CE marked to IEC 60269-4 and GB/T13539.4. For utility-scale solar, storage and rail power.
Direct-current plants running at 1500V leave a protection engineer very little margin: a fault must be cleared before the semiconductor junction heats past recovery. VIOX Electric builds the 1500V DC Heavy-Duty Semiconductor Protection Fuse for that duty, an aR-class element that shields IGBTs, thyristors and rectifier diodes in utility-scale solar and wind collection systems, grid-scale storage converters, high-power charging hubs, rail traction equipment and heavy industrial DC plants.
Đặc trưng
- Rated voltage 1500VDC and current capacity 400A for ess & semiconductor high-speed fuse applications.
- High interrupting performance (150kA) with rapid current-limiting fault clearing.
- Engineered and tested in accordance with GB/T 13539.4 / GB/T13539.4 / IEC 60269-4 standards.
- Precision-engineered low-power-loss silver-plated contacts and high-temperature ceramic or flame-retardant housing.
- Direct OEM replacement geometry for standardized industrial, solar PV, ESS, and EV protection panels.
Thông số kỹ thuật
VOSA3-PK Technical Specifications
| Số seri | Rated Current A | Pre-arcing I²t A²s | Melting I²t A²s | Power dissipation W |
| 1 | 400 | 38900 | 172000 | 163 |
| 2 | 450 | 56700 | 280000 | 169 |
| 3 | 500 | 62500 | 324000 | 176 |
| 4 | 550 | 69400 | 387000 | 183 |
| 5 | 630 | 73700 | 433000 | 191 |
| 6 | 700 | 90900 | 589000 | 200 |
| 7 | 800 | 119000 | 746000 | 208 |
| 8 | 900 | 161000 | 913000 | 217 |
| 9 | 1000 | 252000 | 1308000 | 226 |
VOSA3-PK Ratings & Dimensions Table 2
| Rated Current (A) | Conventional Time (h) | Conventional Current | |
| “gR” | |||
| Inf | lf | ||
| ln≤63 | 1 | 1.13ln | 1.6ln |
| 63<In≤160 | 2 | ||
| 160<ln≤400 | 3 | ||
| 400<ln | 4 | ||
| Note:ln is the rated current of the fuse; lnf is the conventional non-fusing current; if is the conventional fusing current. | |||
Selection & Installation Notes
- Verify system maximum voltage (1500VDC) and prospective short-circuit fault current before selecting the fuse link or holder rating.
- Apply ambient-temperature derating when operating inside sealed outdoor combiner boxes or high-density inverter cabinets above 40°C.
- Always de-energize circuits before replacing cylindrical, blade, or bolted fuse links, and use insulated fuse pullers for NH/NT types.
- Explore the complete VIOX Fuse & Fuse Holder catalog for matched holders, bases, and disconnectors.
Câu hỏi thường gặp
What voltage and current ratings does the VIOX VOSA3-PK 1500V DC Heavy-Duty Semiconductor Protection Fuse support?
This VIOX VOSA3-PK series is rated for 1500VDC with a current rating of 400A and 150kA breaking performance. Refer to the technical specification table above for individual part numbers and ampere steps.
Which international standards apply to VIOX VOSA3-PK 1500V DC Heavy-Duty Semiconductor Protection Fuse?
The VOSA3-PK series is designed and verified to GB/T 13539.4 / GB/T13539.4 / IEC 60269-4 requirements for safe overcurrent and short-circuit protection.
Where is the VIOX VOSA3-PK 1500V DC Heavy-Duty Semiconductor Protection Fuse typically installed?
It is engineered for ess & semiconductor high-speed fuse circuits, protecting cables, busbars, semiconductors, battery modules, or string feeders against thermal overload and high-energy short-circuit faults.
Can VIOX supply matched fuse holders, bases, or OEM private-label packaging?
Yes. VIOX Electric supplies matched DIN-rail fuse holders, NH/NT fuse bases, disconnectors, and OEM/ODM bulk packaging with technical datasheets upon RFQ.