Основные выводы
- Standard Distance: 12/2 wire on a 20-amp breaker can safely run 50-60 feet at full load while maintaining the NEC-recommended 3% voltage drop
- Maximum Safe Distance: Up to 93 feet is possible with 3% voltage drop at 240V, but only 50-57 feet at 120V
- Load Matters: Actual usable distance depends heavily on the connected load—lower amperage allows longer runs
- Safety Critical: Beyond recommended distances, fault loop impedance increases, potentially preventing circuit breakers from tripping during short circuits
- Upgrade Rule: For runs exceeding 60 feet at 20 amps, upgrade to 10 AWG; for 100+ feet, consider 8 AWG wire
Understanding the Two Limits: Ampacity vs. Voltage Drop
When electricians and engineers discuss how far you can run 12/2 wire on a 20-amp breaker, they’re actually addressing two completely different limitations:
The Thermal Limit (Ampacity)
According to NEC Table 310.16, 12 AWG copper wire is rated for 20 amperes at 60°C and 25 amperes at 90°C (for THHN/THWN-2 insulation). This rating ensures the wire won’t overheat and melt its insulation—regardless of length.

The Performance Limit (Voltage Drop)
Voltage drop is the silent killer of electrical performance. As current flows through wire, resistance causes voltage to decrease. The NEC recommends limiting voltage drop to:
- 3% maximum for branch circuits (NEC 210.19(A)(1) FPN No. 4)
- 5% maximum combined for feeders and branch circuits
- 2% maximum for sensitive electronic equipment (NEC 647.4(D))
This voltage drop limit—not ampacity—determines the practical maximum distance for 12/2 wire.
The Math Behind Maximum Wire Distance
Формула расчета падения напряжения
The fundamental formula for calculating voltage drop in a two-wire circuit is:
VD = (2 × R × I × L) / 1000
Где:
- VD = Voltage drop (volts)
- R = Resistance per 1,000 feet (ohms)
- I = Ток (ампер)
- L = One-way distance (feet)
- 2 = Accounts for both hot and neutral conductors
For 12 AWG copper wire: R = 1.93 ohms per 1,000 feet (NEC Chapter 9, Table 8)
Maximum Distance Formula
Rearranging the formula to solve for maximum distance:
Maximum Distance (feet) = (Maximum VD × 1000) / (2 × R × I)

Maximum Distance Table: 12/2 Wire on 20-Amp Breaker
| Напряжение системы | Ток нагрузки | Max Distance (3% VD) | Max Distance (5% VD) | Actual Voltage at Load (3%) |
|---|---|---|---|---|
| 120В | 20A (100%) | 51 feet | 85 feet | 116.4V |
| 120В | 16A (80%) | 64 feet | 106 feet | 116.4V |
| 120В | 12A (60%) | 85 feet | 142 feet | 116.4V |
| 120В | 8A (40%) | 128 feet | 213 feet | 116.4V |
| 240V | 20A (100%) | 93 feet | 155 feet | 232.8V |
| 240V | 16A (80%) | 116 feet | 194 feet | 232.8V |
Note: Distances are one-way measurements from panel to load
Why the 80% Rule Matters
The NEC requires continuous loads (operating for 3+ hours) to be calculated at 125% of the actual load, meaning a 20-amp circuit should only carry 16 amps continuously (80% of rated capacity). This provides a safety margin and extends the practical maximum distance.
Real-World Distance Scenarios
Scenario 1: Outdoor Workshop (Full 20A Load)
Настройка: Running 12/2 wire from main panel to outdoor workshop with power tools (table saw, air compressor) drawing 18-20 amps.
Расстояние: 75 feet
Расчет:
- VD = (2 × 1.93 × 20 × 75) / 1000 = 5.79 volts
- Voltage drop percentage = 5.79V / 120V = 4.8%
Результат: ❌ Exceeds 3% recommendation (but within 5% maximum)
Рекомендация: Upgrade to 10 AWG wire to reduce voltage drop to 2.9% (3.6V)

Scenario 2: Landscape Lighting (Low Amperage)
Настройка: LED landscape lighting drawing only 3 amps, 150 feet from panel.
Расчет:
- VD = (2 × 1.93 × 3 × 150) / 1000 = 1.74 volts
- Voltage drop percentage = 1.74V / 120V = 1.45%
Результат: ✅ Well within 3% limit
Ключевое понимание: Load current matters more than wire rating. Even though 12/2 wire is rated for 20 amps, low-amperage loads can travel much farther distances.
Scenario 3: EV Charger Installation
Настройка: Level 2 EV charger (16A continuous) at 85 feet from panel.
Расчет:
- VD = (2 × 1.93 × 16 × 85) / 1000 = 5.25 volts
- Voltage drop percentage = 5.25V / 120V = 4.4%
Результат: ❌ Exceeds 3% recommendation
Профессиональное решение: Использование 10 AWG wire or run at 240V (which halves the percentage voltage drop) citation
The Hidden Danger: Fault Loop Impedance
Beyond voltage drop, there’s a critical safety issue that most DIYers overlook: fault loop impedance.
What Is Fault Loop Impedance?
When a short circuit occurs, the circuit breaker must detect a massive current surge (typically 5-10 times the rated current) to trigger its magnetic trip mechanism instantly. For a 20-amp breaker, this means 100-200 amps of fault current.
Проблема: As wire length increases, total circuit resistance increases, which reduces short-circuit current.
Why This Is Dangerous
Сценарий: You run 500 feet of 12/2 wire to a remote building.
- Total circuit resistance = (2 × 1.93 × 500) / 1000 = 1.93 ohms
- Short circuit current = 120V / 1.93Ω = 62 amps
Critical Issue: 62 amps may not be enough to trigger the magnetic trip. The breaker might rely on its slower thermal trip mechanism, which could take 30-60 секунд to activate.
Последствие: During those 30-60 seconds, the wire becomes a giant heating element, potentially igniting surrounding materials before the breaker trips.

Профессиональное решение
For long-distance runs, always verify that ожидаемый ток короткого замыкания exceeds the breaker’s instantaneous trip threshold. This often requires:
- Upsizing conductors beyond voltage drop requirements
- Installing sub-panels closer to loads
- Using higher voltage (240V instead of 120V)
Wire Size Upgrade Comparison Table
| Расстояние | 120V @ 20A | 120V @ 16A | 240V @ 20A | Recommended Wire Size |
|---|---|---|---|---|
| 0-50 ft | 2.6% VD | 2.1% VD | 1.3% VD | 12 AWG ✅ |
| 51-75 ft | 3.9% VD | 3.1% VD | 1.9% VD | 10 AWG ⚠️ |
| 76-100 ft | 5.2% VD | 4.1% VD | 2.6% VD | 10 AWG ⚠️ |
| 101-150 ft | 7.7% VD | 6.2% VD | 3.9% VD | 8 AWG ⚠️ |
| 151-200 ft | 10.3% VD | 8.3% VD | 5.2% VD | 6 AWG ⚠️ |
Legend: ✅ Acceptable | ⚠️ Upgrade Required
Practical Installation Guidelines
When 12/2 Wire Is Acceptable
- ✅ Цепи ответвления жилых помещений under 50 feet
- ✅ Light-duty loads (lighting, receptacles) under 10 amps
- ✅ Short runs from sub-panels to nearby outlets
- ✅ 240V circuits where voltage drop is halved
When to Upgrade from 12/2
- ⚠️ Distances exceeding 60 feet at full 20A load
- ⚠️ Нагрузки двигателя (air compressors, power tools) requiring high starting current
- ⚠️ EV chargers operating continuously at 16A+
- ⚠️ Чувствительная электроника requiring stable voltage
- ⚠️ Outdoor buildings 100+ feet from main panel

NEC Code Compliance Checklist
When planning your 12/2 wire installation, verify compliance with these NEC requirements:
| Раздел кода | Требование | Compliance Check |
|---|---|---|
| NEC 210.19(A)(1) | Branch circuit voltage drop ≤ 3% recommended | Calculate VD at maximum load |
| NEC 240.4(D) | 12 AWG protected by max 20A overcurrent device | Use 20A breaker (not 25A or 30A) |
| NEC 310.16 | Conductor ampacity adequate for load | 12 AWG = 20A at 60°C, 25A at 90°C |
| NEC 110.14(C) | Termination temperature ratings | Most devices rated 60°C or 75°C |
| NEC 334.80 | NM cable support every 4.5 feet | Secure Romex properly |
Cost-Benefit Analysis: When to Upsize Wire
Material Cost Comparison (per 100 feet)
| Размер провода | Approximate Cost | Voltage Drop @ 20A/100ft | Long-Term Energy Loss |
|---|---|---|---|
| 12 AWG | $45-65 | 5.2% | $15-25/year* |
| 10 AWG | $75-95 | 3.3% | $10-15/year* |
| 8 AWG | $125-165 | 2.1% | $6-10/year* |
*Based on continuous 16A load at $0.12/kWh
Расчет ROI (окупаемости инвестиций): For a 100-foot run carrying 16A continuously:
- Upgrading from 12 AWG to 10 AWG costs $30 more
- Annual energy savings: $10-15
- Payback period: 2-3 years
- Equipment lifespan improvement: Motors and electronics last longer with stable voltage
Профессиональная рекомендация: For any permanent installation exceeding 75 feet, upsize wire by one gauge. The marginal cost is minimal compared to long-term performance and safety benefits.
Special Considerations for Different Applications
HVAC and Heat Pump Circuits
Electric heating and cooling equipment is particularly sensitive to voltage drop:
- Compressor motors draw high starting current (LRA = Locked Rotor Amps)
- Reduced voltage causes motors to overheat and fail prematurely
- Рекомендация: Limit voltage drop to 2% maximum for HVAC circuits
Станции зарядки электромобилей
Level 2 EV chargers present unique challenges:
- Непрерывная нагрузка: Operates at 80% of breaker rating for hours
- Расстояние: Often located in garages or driveways far from panel
- Решение: Использование 240V circuits to halve voltage drop percentage, or install dedicated sub-panel
Solar PV and Battery Systems
DC circuits have different considerations:
- No reactive impedance: Only resistance matters
- Более высокие напряжения: 48V systems more tolerant of voltage drop
- Рекомендация: Follow NEC 690.8 requirements for PV source circuits
Troubleshooting Voltage Drop Issues
Symptoms of Excessive Voltage Drop
- 🔴 Lights dimming when appliances start
- 🔴 Motors running hot or failing to start
- 🔴 Electronics resetting or malfunctioning
- 🔴 GFCI nuisance tripping on long runs
- 🔴 Appliances underperforming (slow heating, weak cooling)
Этапы диагностики
- Measure voltage at panel: Should be 118-122V (nominal 120V)
- Measure voltage at load under operation: Should be within 3% of panel voltage
- Calculate actual voltage drop: Panel voltage – Load voltage
- Compare to NEC recommendations: 3% = 3.6V for 120V circuits
Remediation Options
Вариант 1: Upsize conductors (most permanent solution)
Вариант 2: Install sub-panel closer to loads
Option 3: Перераспределить нагрузки to shorter circuits
Option 4: Convert to 240V (for compatible equipment)
VIOX Solutions for Long-Distance Wiring
When upgrading wire size to overcome voltage drop, you’ll encounter a common problem: larger wires don’t fit standard device terminals.
VIOX Product Applications
1. Terminal Blocks and Distribution Strips
When transitioning from 8 AWG or 10 AWG feeder wire to 12 AWG branch circuits, VIOX terminal blocks provide:
- Secure connections for mixed wire gauges
- Code-compliant wire-to-wire transitions
- Easy troubleshooting with accessible connection points
2. Heavy-Duty Junction Boxes
For outdoor long-distance runs, VIOX weatherproof junction boxes offer:
- IP65/IP67 ratings для жестких условий эксплуатации
- Large wire capacity for upsized conductors
- Снятие напряжения for underground conduit transitions
3. Sub-Panel Solutions
Installing a sub-panel reduces branch circuit distances:
- Main panel → Sub-panel: Use 6 AWG or larger
- Sub-panel → Loads: Standard 12 AWG for short runs
- Результат: Optimal voltage drop on all circuits
Вопросы и ответы
Can I run 12/2 wire 100 feet on a 20-amp breaker?
Yes, but with limitations. At full 20A load, voltage drop will be approximately 5.2%, exceeding the NEC’s 3% recommendation. This is acceptable for:
- Infrequent use loads
- Circuits drawing less than 12 amps
- 240V circuits (voltage drop percentage is halved)
For continuous 20A loads, upgrade to 10 AWG wire.
Does wire length affect circuit breaker tripping?
Да, значительно. Longer wire runs increase circuit resistance, which reduces short-circuit current. In extreme cases (200+ feet), fault current may be too low to trigger the breaker’s instantaneous magnetic trip, creating a fire hazard. Always verify that prospective short-circuit current exceeds 5× the breaker rating.
What’s the difference between 12/2 and 12/3 wire for distance?
Wire distance capacity is identical. The numbers refer to conductor count (2 or 3 insulated conductors), not wire gauge. Both use 12 AWG conductors with the same resistance. Use 12/3 when you need:
- Three-way switch circuits
- Multi-wire branch circuits
- Separate hot conductors for 240V + neutral
Can I use aluminum wire instead to save money on long runs?
Yes, but upsize by one gauge. Aluminum has higher resistance than copper:
- Используйте 10 AWG aluminum instead of 12 AWG copper
- Требуется anti-oxidant compound on connections
- Must use AL-rated devices (CO/ALR marking)
- Cost savings: 30-40% less expensive for large wire sizes
How do I calculate voltage drop for multiple outlets on one circuit?
Use the farthest outlet и maximum simultaneous load. For example:
- Circuit has 8 outlets over 120 feet
- Assume 80% of breaker rating (16A for 20A circuit)
- Calculate voltage drop to the last outlet at 16A
- This provides a conservative worst-case scenario
Does wire type (THHN vs. Romex) affect maximum distance?
Нет. Voltage drop depends only on:
- Wire gauge (AWG)
- Conductor material (copper vs. aluminum)
- Current (amperes)
- Distance (feet)
Insulation type (THHN, THWN, NM-B) affects ampacity и installation method, but not resistance or voltage drop.
Conclusion: The Engineering Approach to Wire Sizing
The question “How far can you run 12/2 wire on a 20-amp breaker?” doesn’t have a single answer—it depends on:
- Напряжение системы (120V vs. 240V)
- Actual load current (not just breaker rating)
- Acceptable voltage drop (3% recommended, 5% maximum)
- Application sensitivity (motors and electronics need tighter tolerances)
- Меры безопасности (fault loop impedance for proper breaker operation)
General Guidelines:
- Under 50 feet: 12 AWG is appropriate for 20A circuits
- 50-75 feet: Consider 10 AWG for full-load applications
- 75-100 feet: Use 10 AWG for 20A loads
- Over 100 feet: Use 8 AWG or install a sub-panel
Professional Best Practice: When in doubt, upsize by one gauge. The marginal cost is minimal compared to the long-term benefits of:
- Reduced energy waste
- Extended equipment lifespan
- Improved safety margins
- Future-proofed capacity
For complex installations or commercial applications, consult a licensed electrician and consider using VIOX electrical components designed for reliable long-distance power distribution.
Internal Links
For related technical guidance, see these VIOX resources:
- Руководство по выбору размера провода на 50 ампер. – Comprehensive wire sizing for high-amperage circuits
- Electrical Derating: Temperature, Altitude, and Grouping Factors – How environmental conditions affect wire capacity
- Руководство по снижению номинальных характеристик автоматических выключателей по высоте – Critical considerations for high-elevation installations
- Cable Size Types: mm² vs AWG vs BS Conversion Guide – International wire sizing standards
- Номинальные значения температуры окружающей среды и коэффициенты снижения номинальных характеристик для MCB. – Temperature effects on circuit protection
- Как рассчитать ток короткого замыкания для автоматического выключателя (MCB) – Understanding fault current calculations
- Standard Breaker Sizes – Complete guide to circuit breaker ratings
- Руководство для домовладельцев по определению номинала автоматического выключателя и расчету нагрузки – Practical residential wiring guidance
О компании VIOX Electric: VIOX Electric is a leading B2B manufacturer of electrical equipment, specializing in circuit protection devices, terminal blocks, junction boxes, and distribution solutions for residential, commercial, and industrial applications. Our products meet or exceed NEC, UL, and IEC standards for safety and performance.