VIOX VRO3-40 RCBO offers comprehensive protection for single-phase systems. This IEC61009-1 compliant device features a 6kA breaking capacity and supports currents from 6A to 40A at 230V AC. With adjustable sensitivity from 10mA to 500mA, it provides A and AC type protection against residual currents, overloads, and short circuits. The RCBO offers B, C, and D tripping curves, IP20 protection, and operates from -5°C to +40°C. Key advantages include combined MCB/RCD functionality, 1P+N configuration, and 4,000 electrical/10,000 mechanical life cycles. Ideal for residential and commercial applications, this versatile RCBO ensures reliable protection with fault current indication, 4kV impulse withstand voltage, and easy DIN rail mounting. Its compact design and top connection make it suitable for various low-voltage distribution systems.

ສົ່ງຄວາມຕ້ອງການຂອງທ່ານ, ພວກເຮົາຈະອ້າງອີງໃຫ້ທ່ານພາຍໃນ 12 ຊົ່ວໂມງ

VIOX VRO3-40 1P+N RCBO ELCB ເຄື່ອງຕັດວົງຈອນກະແສໄຟຟ້າທີ່ເຫຼືອດ້ວຍການປ້ອງກັນກະແສໄຟຟ້າເກີນ

ພາບລວມ

The VIOX VRO3-40 is a versatile Residual Current Circuit Breaker with Overcurrent Protection (RCBO) designed for AC 50Hz/60Hz systems with rated voltage 230/400V and rated current from 6A to 40A. This device combines the functions of an MCB and RCD, offering comprehensive protection against electric shock, overload, and short circuits in low voltage terminal distribution systems.

ຄຸນນະສົມບັດທີ່ສໍາຄັນ

  • Combined MCB and RCD functionality
  • Protection against electric shock and indirect human contact
  • ການປ້ອງກັນການໂຫຼດເກີນແລະວົງຈອນສັ້ນ
  • Suitable for non-frequent circuit operation
  • Widely used in residential and commercial applications
  • Compliant with IEC61009-1 standard

ຂໍ້ມູນຈໍາເພາະ

  • Standard: IEC/EN 61009-1
  • Mode: Electro-magnetic type, electronic type
  • Type: A, AC (wave form of earth leakage sensed)
  • Thermo-magnetic release characteristic: B, C, D
  • Rated current (In): 6, 10, 16, 20, 25, 32, 40A
  • Poles: 1P+N
  • Rated voltage (Ue): AC 230V
  • ລະດັບຄວາມອ່ອນໄຫວ (I△n): 0.01, 0.03, 0.1, 0.3, 0.5A
  • Rated residual making and breaking capacity (I△m): 500A
  • Rated short-circuit capacity (Icn): 6000A
  • Break time under I△n: ≤0.1s
  • ຄວາມຖີ່ການຈັດອັນດັບ: 50/60Hz
  • Rated impulse withstand voltage (Uimp): 4000V
  • Dielectric test voltage: 2kV for 1 min
  • Insulation voltage (Ui): 250V
  • ລະດັບມົນລະພິດ: 2

ລັກສະນະກົນຈັກ

  • ຊີວິດໄຟຟ້າ: 4000 ການດໍາເນີນງານ
  • ຊີວິດກົນຈັກ: 10000 ການດໍາເນີນງານ
  • Fault current indicator: Yes
  • ລະດັບການປົກປ້ອງ: IP20
  • Ambient temperature: -5~+40°C (daily average ≤35°C)
  • Storage temperature: -25~+70°C

ການຕິດຕັ້ງ

  • Terminal connection type: Cable/Pin-type busbar/U-type busbar
  • Terminal size for cable: 25mm² (AWG 18-5)
  • Terminal size for busbar: 25mm² (AWG 18-3)
  • ການຕິດຕັ້ງ: ໃນ DIN rail EN 60715 (35mm) ໂດຍອຸປະກອນ clip ໄວ
  • Connection: From top

ຄໍາຮ້ອງສະຫມັກ

  • Residential electrical systems
  • ອາຄານພານິດ
  • Low voltage terminal distribution systems

ຄຸນນະສົມບັດຄວາມປອດໄພ

  • Electric shock protection
  • ການປ້ອງກັນການໂຫຼດເກີນ
  • ການປ້ອງກັນວົງຈອນສັ້ນ
  • Leakage current detection

ເສັ້ນໂຄ້ງລັກສະນະ

ແຜນຜັງສາຍ

ຂະໜາດ

ຜະລິດຕະພັນທີ່ກ່ຽວຂ້ອງ

ຂໍ Quote ດຽວນີ້

ຂໍ Quote ດຽວນີ້