Επισκόπηση
VOSA5-PK-1500V VIOX AC/DC1500V High-Power Semiconductor Protection Fuse: aR class, 1400A-3000A, 200kA breaking on AC and 250kA on DC (≤15ms), CE marked to IEC 60269-4 and GB/T 13539.4. For megawatt converters and storage.
Above 1400A the choice of aR fuses narrows sharply, exactly where the largest converters begin. VIOX Electric builds the AC/DC1500V High-Power Semiconductor Protection Fuse to cover that upper band, with ratings from 1400A to 3000A for IGBT stacks, thyristor bridges and rectifier diodes in rail traction, renewable power stations, telecom plants, metallurgy lines and utility-scale power conversion.
Χαρακτηριστικά
- Rated voltage 1500V and current capacity 1400A for ess & semiconductor high-speed fuse applications.
- High interrupting performance (200kA) with rapid current-limiting fault clearing.
- Engineered and tested in accordance with GB/T 13539.4 / GB/T13539.4 / IEC 60269-4 standards.
- Precision-engineered low-power-loss silver-plated contacts and high-temperature ceramic or flame-retardant housing.
- Direct OEM replacement geometry for standardized industrial, solar PV, ESS, and EV protection panels.
Προδιαγραφές
VOSA5-PK-1500V Technical Specifications
| Σειριακός αριθμός | Rated Current A | Pre-arcing I²t A²s | Melting I²t A²s | Power dissipation W |
| 1 | 1400 | 243000 | 2320000 | 352 |
| 2 | 1600 | 830000 | 5750000 | 358 |
| 3 | 1800 | 1430000 | 9550000 | 365 |
| 4 | 2000 | 2100000 | 14200000 | 375 |
| 5 | 2500 | 3110000 | 21100000 | 390 |
| 6 | 2800 | 3860000 | 30200000 | 406 |
| 7 | 3000 | 4540000 | 42100000 | 425 |
VOSA5-PK-1500V Ratings & Dimensions Table 2
| Rated Current (A) | Conventional Time (h) | Conventional Current | |
| “gR” | |||
| Inf | lf | ||
| ln≤63 | 1 | 1.13ln | 1.6ln |
| 63<In≤160 | 2 | ||
| 160<ln≤400 | 3 | ||
| 400<ln | 4 | ||
| Note:ln is the rated current of the fuse; lnf is the conventional non-fusing current; if is the conventional fusing current. | |||
Selection & Installation Notes
- Verify system maximum voltage (1500V) and prospective short-circuit fault current before selecting the fuse link or holder rating.
- Apply ambient-temperature derating when operating inside sealed outdoor combiner boxes or high-density inverter cabinets above 40°C.
- Always de-energize circuits before replacing cylindrical, blade, or bolted fuse links, and use insulated fuse pullers for NH/NT types.
- Explore the complete VIOX Fuse & Fuse Holder catalog for matched holders, bases, and disconnectors.
ΣΥΧΝΈΣ ΕΡΩΤΉΣΕΙΣ
What voltage and current ratings does the VIOX VOSA5-PK-1500V AAC/DC1500V High-Power Semiconductor Protection Fuse support?
This VIOX VOSA5-PK-1500V series is rated for 1500V with a current rating of 1400A and 200kA breaking performance. Refer to the technical specification table above for individual part numbers and ampere steps.
Which international standards apply to VIOX VOSA5-PK-1500V AAC/DC1500V High-Power Semiconductor Protection Fuse?
The VOSA5-PK-1500V series is designed and verified to GB/T 13539.4 / GB/T13539.4 / IEC 60269-4 requirements for safe overcurrent and short-circuit protection.
Where is the VIOX VOSA5-PK-1500V AAC/DC1500V High-Power Semiconductor Protection Fuse typically installed?
It is engineered for ess & semiconductor high-speed fuse circuits, protecting cables, busbars, semiconductors, battery modules, or string feeders against thermal overload and high-energy short-circuit faults.
Can VIOX supply matched fuse holders, bases, or OEM private-label packaging?
Yes. VIOX Electric supplies matched DIN-rail fuse holders, NH/NT fuse bases, disconnectors, and OEM/ODM bulk packaging with technical datasheets upon RFQ.