VIOX VSP1-D20/2(S) Zásuvné jednopólové SPD
VIOX VSP1-D20/2(S) Pluggable Single-Pole SPD offers robust surge protection for sub-distribution boards. This Class II/III device safeguards L-PE and N-PE modes with 10kA nominal and 20kA maximum discharge current. Featuring high-energy MOV elements, it operates from 60V to 400V AC with < 25ns response time. The pluggable design ensures easy installation on 35mm DIN rails. IEC 61643-11:2011 and EN 61643-11:2012 compliant, it provides voltage protection levels from 0.2kV to 1.8kV. With IP20 protection, thermal safeguards, and optional remote contacts, this versatile SPD suits various electrical installations, combining reliability and performance in a compact, user-friendly package for enhanced power system protection.
Pošlete nám své požadavky, nabídku vám zašleme do 12 hodin.
- TEL:+8618066396588
- Whatsapp:+8618066396588
- Email:sales@viox.com
VIOX VSP1-D20/2(S) Zásuvné jednopólové SPD
Přehled
The VIOX VSP1-D20/2(S) is a high-performance Pluggable Single-Pole Surge Protective Device (SPD) designed for use in sub-distribution boards. This versatile device offers robust protection for both L-PE and N-PE modes, making it an ideal solution for various electrical installations.
Klíčové vlastnosti
- Class II, Class III, Type 2, Type 3 device
- Místo použití: Dílčí distribuční desky
- Mode of Protection: L-PE, N-PE
- Surge Ratings: In = 10 kA (8/20 μs)
- IEC/EN/UL Category: Class II+III / Type 2+3
- Ochranné prvky: Vysoce energetický MOV
- Bydlení: Zásuvný design
- Compliance: IEC 61643-11:2011, EN 61643-11:2012
Technické specifikace
IEC Electrical | 75 | 150 | 275 | 320 | 385 | 440 |
---|---|---|---|---|---|---|
Nominal AC Voltage (50/60Hz) | 60 V | 120 V | 230 V | 230 V | 230 V | 400 V |
Maximum Continuous Operating Voltage (AC) | 75 V | 150 V | 275V | 320 V | 385 V | 440 V |
Jmenovitý vybíjecí proud (8/20 μs) | 10 kA | 10 kA | 10 kA | 10 kA | 10 kA | 10 kA |
Maximální vybíjecí proud (8/20 μs) | 20 kA | 20 kA | 20 kA | 20 kA | 20 kA | 20 kA |
Úroveň ochrany před napětím | 0.2 kV | 0.6 kV | 1.3 kV | 1.5 kV | 1.5 kV | 1.8 kV |
Doba odezvy | < 25 ns | |||||
Záložní pojistka (max.) | 125 A gL / gG | |||||
Jmenovitý zkratový proud (AC) | 10 kA | |||||
TOV Withstand 5s | 90V | 180V | 335V | 335V | 335V | 580V |
TOV 120min | 115V | 230V | 440V | 440V | 440V | 765V |
mode | Withstand | Withstand | Safe Fail | Safe Fail | Safe Fail | Safe Fail |
Mechanické a environmentální specifikace
- Rozsah provozních teplot: -40°F až +158°F [-40°C až +70°C]
- Přípustná provozní vlhkost: 5%...95%
- Atmosférický tlak a nadmořská výška: 80k Pa ... 106k Pa / -500 m....2000 m
- Krouticí moment šroubu svorky: 39,9 lbf.in [4,5 Nm]
- Průřez vodiče (max.): 2 AWG (plný, slaněný) / 4 AWG (ohebný)
- 35 mm² (plná, laněná) / 25 mm² (ohebná)
- Montáž: 35 mm DIN lišta, EN 60715
- Stupeň ochrany: IP 20 (vestavěný)
- Materiál pouzdra: Stupeň zhášení UL 94 V-0
- Tepelná ochrana: Ano
- Provozní stav / indikace poruchy: Zelená v pořádku / červená závada
Další funkce
- Vzdálené kontakty (RC): Volitelné
- Přepínací kapacita RC: STŘÍDAVÝ PROUD: 250 V / 0,5 A; STEJNOSMĚRNÝ PROUD: 250 V / 0,1 A;125 V / 0,2 A;75 V / 0,5 A
- Průřez vodiče RC (max.): 16 AWG (plný) / 1,5 mm² (plný)