VIOX VSP1-D20/1(S)+1 Zásuvné jednopólové SPD
VIOX VSP1-D20/1(S)+1 Pluggable Single-Pole SPD offers comprehensive surge protection for sub-distribution boards. This Class II+III/Type 2+3 device safeguards L-N and N-PE modes with 10kA nominal and 20kA maximum discharge current. Featuring high-energy MOV and GDT elements, it operates from 60V to 400V AC with <25ns response time for L-N and <100ns for N-PE. IEC 61643-11:2011 and EN 61643-11:2012 compliant, it provides voltage protection levels from 0.2kV to 1.8kV. With IP20 protection, thermal safeguards, and optional remote contacts, this versatile SPD suits various electrical installations, combining reliability and performance for enhanced power system protection in diverse applications.
Pošlete nám své požadavky, nabídku vám zašleme do 12 hodin.
- TEL:+8618066396588
- Whatsapp:+8618066396588
- Email:sales@viox.com
VIOX VSP1-D20/1(S)+1 Zásuvné jednopólové SPD
Přehled
The VIOX VSP1-D20/1(S)+1 is a high-performance Pluggable Single-Pole Surge Protective Device (SPD) designed for use in sub-distribution boards. This versatile device offers robust protection for L-N and N-PE modes, making it an ideal solution for various electrical installations.
Klíčové vlastnosti
- Class II, Class III, Type 2, Type 3 device
- Místo použití: Dílčí distribuční desky
- Mode of Protection: L-N, N-PE
- Surge Ratings: In = 10 kA (8/20 μs)
- IEC/EN/UL Category: Class II+III / Type 2+3
- Protective Elements: High Energy MOV and GDT
- Bydlení: Zásuvný design
- Compliance: IEC 61643-11:2011, EN 61643-11:2012
Technické specifikace
IEC Electrical | 75 | 150 | 275 | 320 | 385 | 440 |
---|---|---|---|---|---|---|
Nominal AC Voltage (50/60Hz) | 60 V | 120 V | 230 V | 230 V | 230 V | 400 V |
Maximum Continuous Operating Voltage (AC) (L-N) | 75 V | 150 V | 275V | 320 V | 385 V | 440 V |
Maximum Continuous Operating Voltage (AC) (N-PE) | 255V | |||||
Nominal Discharge Current (8/20 μs) (L-N) / (N-PE) | 10kV / 10kA | |||||
Maximum Discharge Current (8/20 μs) (L-N) / (N-PE) | 20 kA / 20 kA | |||||
Voltage Protection Level (L-N) / (N-PE) | 0.2kV/1.5kV | 0.6kV/1.5kV | 1.3kV/1.5kV | 1.5kV/1.5kV | 1.5kV/1.5kV | 1.8kV/1.5kV |
Follow Current Interrupt Rating (N-PE) | 100Arms | |||||
Response Time (L-N) / (N-PE) | < 25 ns / < 100 ns | |||||
Záložní pojistka (max.) | 125 A gL / gG | |||||
Short-Circuit Current Rating (AC) (L-N) | 10 kA | |||||
TOV Withstand 5s (L-N) | 90V | 180V | 335V | 335V | 335V | 580V |
TOV 120min (L-N) | 115V | 230V | 440V | 440V | 440V | 765V |
mode | Withstand | Withstand | Safe Fail | Safe Fail | Safe Fail | Safe Fail |
TOV Withstand 200ms (N-PE) | 1200V |
Mechanické a environmentální specifikace
- Rozsah provozních teplot: -40°F až +158°F [-40°C až +70°C]
- Přípustná provozní vlhkost: 5%...95%
- Atmosférický tlak a nadmořská výška: 80k Pa ... 106k Pa / -500 m....2000 m
- Krouticí moment šroubu svorky: 39,9 lbf.in [4,5 Nm]
- Průřez vodiče (max.): 2 AWG (plný, slaněný) / 4 AWG (ohebný)
- 35 mm² (plná, laněná) / 25 mm² (ohebná)
- Montáž: 35 mm DIN lišta, EN 60715
- Stupeň ochrany: IP 20 (vestavěný)
- Materiál pouzdra: Stupeň zhášení UL 94 V-0
- Tepelná ochrana: Ano
- Provozní stav / indikace poruchy: Zelená v pořádku / červená závada
Další funkce
- Vzdálené kontakty (RC): Volitelné
- RC Switching Capacity: AC: 250V / 0.5 A; DC: 250V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A
- Průřez vodiče RC (max.): 16 AWG (plný) / 1,5 mm² (plný)