VIOX VOPD1-63DK Dual-Pole (L+N Cutoff) Adjustable Voltage & Current Protector (63A)

The VIOX VOPD1-63DK is a 63 A dual-pole adjustable voltage and current protector engineered to disconnect BOTH Live (L) and Neutral (N) conductors simultaneously during faults. Supporting 110 V and 230 V AC grids, it eliminates neutral-shift hazards in TN-S/TT installations and reversible-polarity utility feeds.

VIOX Model
VOPD1-63DK
แรงดันไฟฟ้า
AC 110 V / 230 V (50/60 Hz)
ปัจจุบัน
1–63 A Adjustable
รูปแบบ
ราง DIN 35 mm

ภาพรวม

The VIOX VOPD1-63DK is a 63 A dual-pole adjustable voltage and current protector engineered to disconnect BOTH Live (L) and Neutral (N) conductors simultaneously during faults. Supporting 110 V and 230 V AC grids, it eliminates neutral-shift hazards in TN-S/TT installations and reversible-polarity utility feeds.

คุณสมบัติ

  • Simultaneous dual-pole L + N disconnection provides complete circuit isolation during over-voltage, under-voltage, or over-current faults.
  • Supports both 110 V and 230 V AC grids with adjustable OV (230–300 V, default 270 V), UV (140–210 V, default 170 V), and OC (1–63 A, default 40 A).
  • Configurable action and auto-recovery delays (0.1–500 s) with dual live V/A display.
  • Standard 35 mm DIN-rail mounting for high-safety residential and commercial boards.

ข้อมูลจำเพาะ

VOPD1-63DK Technical Specifications

พารามิเตอร์ข้อมูลจำเพาะ
Isolation ArchitectureDual-pole simultaneous Live (L) + Neutral (N) disconnection
Supported GridsAC 110 V / 230 V, 50/60 Hz
Over-Voltage / Under-Voltage230–300 V (default 270 V) / 140–210 V (default 170 V)
Over-Current Range1–63 A adjustable (default 40 A)
Delays & Mounting0.1–500 s configurable action & recovery · 35 mm DIN rail

Wiring & Setup Guide

  • Connect incoming L and N to top IN terminals and load L and N to bottom OUT terminals. Both poles break simultaneously on trip.
  • Explore the complete VIOX Voltage Protectors catalog for matched DIN-rail switchgear.

คำถามที่พบบ่อย

When is dual-pole L+N disconnection (VOPD1-63DK) required?

Use VOPD1-63DK in TT earthing systems, unstable neutral grids, or markets where electrical codes mandate simultaneous isolation of both live and neutral conductors.