VIOX VSP1-C40PV/2(S) 600V SPD Kutub Tunggal Boleh Palam
VIOX VSP1-C40PV/2(S) 600V Pluggable Single-Pole SPD offers robust surge protection for photovoltaic systems and sub-distribution boards. This Class II/Type 2/Type 1CA device safeguards L-PE and N-PE modes with 20kA nominal and 40kA maximum discharge current. Featuring high-energy MOV elements, it operates at 600V DC with < 25ns response time. The pluggable design ensures easy installation on 35mm DIN rails. IEC 61643-11:2011 and EN 61643-11:2012 compliant, it provides a voltage protection level of 2.2kV. With IP20 protection, thermal safeguards, and optional remote contacts, this versatile SPD suits various electrical installations, combining reliability and performance for enhanced power system protection in demanding photovoltaic applications.
Hantar keperluan anda, kami akan sebut harga untuk anda dalam masa 12 jam
- TEL:+8618066396588
- Whatsapp:+8618066396588
- E-mel:sales@viox.com
VIOX VSP1-C40PV/2(S) 600V SPD Kutub Tunggal Boleh Palam
Gambaran keseluruhan
The VIOX VSP1-C40PV/2(S) 600V is a high-performance Pluggable Single-Pole Surge Protective Device (SPD) designed for use in sub-distribution boards. This versatile device offers robust protection for L-PE and N-PE modes, making it an ideal solution for various electrical installations, particularly in photovoltaic systems.
Ciri-ciri Utama
- Class II, Type 2, Type 1CA device
- Lokasi Penggunaan: Papan Pengedaran Kecil
- Mod Perlindungan: L-PE, N-PE
- Penilaian Lonjakan: Dalam = 20 kA (8/20 μs)
- IEC/EN/UL Category: Class II / Type 2 / Type 1CA
- Elemen Pelindung: MOV Tenaga Tinggi
- Perumahan: Reka Bentuk Boleh Pasang
- Pematuhan: IEC 61643-11:2011, EN 61643-11:2012
Spesifikasi Teknikal
IEC Elektrik | 600 |
---|---|
Voltan AC Nominal | 600V |
Voltan Kendalian Berterusan Maksimum (DC) | 600V |
Arus Pelepasan Nominal (8/20 μs) | 20 kA |
Arus Pelepasan Maksimum (8/20 μs) | 40 kA |
Arus Pelepasan Impuls (10/350 μs) | 6.25kA |
Tahap Perlindungan Voltan | 2.2kV |
Impulse Current (10/350μs) Iimp (L-N) | 7kA |
Masa Tindak Balas | < 25 ns |
Fius Sandaran (maks) | 125 A gL / gG |
Penilaian Arus Litar pintas (AC) | 25 kA / 50 kA |
TOV Tahan 5s | ? |
TOV 120min | ? |
mod | Withstand, Safe Fail |
Spesifikasi Mekanikal & Persekitaran
- Julat Suhu Operasi: -40°F hingga +158°F [-40°C hingga +70°C]
- Kelembapan Operasi yang Dibenarkan: 5%…95%
- Tekanan atmosfera dan ketinggian: 80k Pa … 106k Pa / -500 m….2000 m
- Tork Skru Terminal: 39.9 lbf.in [4.5 Nm]
- Keratan Rentas Konduktor (maks): 2 AWG (Pepejal, Terkandas) / 4 AWG (Fleksibel)
- 35 mm² (Pepejal, Terdampar) / 25 mm²(Fleksibel)
- Pemasangan: Rel DIN 35 mm, EN 60715
- Darjah Perlindungan: IP 20 (terbina dalam)
- Bahan Perumahan: Termoplastik: Darjah Pemadaman UL 94 V-0
- Perlindungan Terma: Ya
- Keadaan Operasi / Petunjuk Kerosakan: Kecacatan hijau ok / Merah
Ciri Tambahan
- Kenalan Jauh (RC): Pilihan
- Kapasiti Pensuisan RC: AC: 250V / 0.5 A; DC: 250V / 0.1 A;125V / 0.2 A;75V / 0.5 A
- Keratan Rentas Konduktor RC (maks): 16 AWG (Pepejal) / 1.5 mm²(Pepejal)