VIOX V50L-32G biztonsági megszakító RCBO
VIOX V50L-32G RCBO offers comprehensive protection for AC 50Hz applications up to 240V and 32A. This IEC/EN 60898 compliant device features a 2500A breaking capacity and provides dual-pole protection against overloads, short circuits, and leakage currents. Available in 16A, 20A, 25A, and 32A ratings with C and D tripping curves, it’s ideal for modern household appliances and single-phase industrial circuits. Key advantages include compact design, zero line and fire line protection, and reliable operation even with reversed wiring. Operating from -5°C to +40°C and suitable for altitudes up to 2000m, this versatile RCBO ensures safety in various environments. Its infrequent operation capability and simultaneous pole disconnection make it a truly reliable choice for both residential and light industrial applications.
Küldje el igényeit, 12 órán belül árajánlatot adunk Önnek.
- TEL:+8618066396588
- Whatsapp:+8618066396588
- Email:sales@viox.com
VIOX V50L-32G biztonsági megszakító maradóáramú megszakító túláramvédelemmel
Áttekintés
The VIOX V50L-32G RCBO series is designed for AC 50Hz applications with rated voltage up to 240V and rated current up to 32A. These devices offer comprehensive protection against overload and short circuit for various modern household appliances, while also providing functionality for infrequent operation and control.
Fő jellemzők
- High breaking capacity
- Zero line and fire line intermittent protection
- Leakage protection even in case of fire line reversal
- Compact size with double pole structure design
- Simultaneous connection and disconnection of both poles
- Truly safe and reliable for civilian and industrial single-phase applications
- Suitable for infrequent operation and control
Műszaki specifikációk
- Szabvány: IEC/EN 60898
- Type: RCBO V50L-32G
- Védelem: Túlterhelés és rövidzárlat
- Rated current: 16A, 20A, 25A, 32A
- Characteristic: C curve (32A), D curve (16A, 20A, 25A)
- Rudak: 2 rudak
- Breaking capacity: 2500A
- Rated voltage: 110VAC, 230VAC
- Környezeti hőmérséklet: -5°C és +40°C között (24 órás átlag legfeljebb 35°C)
- Tengerszint feletti magasság: 2000 m vagy kevesebb
- Telepítési osztály: III
- Szennyezettségi szint: II
Over-Load | |||||
---|---|---|---|---|---|
Test No. | Curve Type | Load Current | Kezdeti állapot | Time Limit To Trip | Estimated Result |
1 | C,D | 1.13In | hideg állapot | t≤1h | Not trip |
2 | C,D | 1.45In | conntinuing the test | t < 1 | trip |
3 | C,D | 2.55In | hideg állapot | 1s < t < 60s | trip |
Rövidzárlat | |||||
---|---|---|---|---|---|
Test No. | Curve Type | Load Current | Kezdeti állapot | Time Limit To Trip | Estimated Result |
4 | C | 5In | hideg állapot | t≤0.1s | Not trip |
D | 10In | ||||
5 | C | 10In | hideg állapot | t < 0.1s | trip |
D | 20In |
Ambiment temperature Rated current(A) | -10°C | 0°C | 10°C | 20°C | 30°C | 40°C | 50°C | 60°C |
---|---|---|---|---|---|---|---|---|
16 | 19.20 | 18.40 | 17.76 | 16.96 | 16.00 | 15.36 | 14.88 | 14.24 |
20 | 24.00 | 23.00 | 22.20 | 21.20 | 20.00 | 19.20 | 18.60 | 17.80 |
25 | 30.00 | 28.75 | 27.75 | 26.50 | 25.00 | 24.00 | 23.25 | 22.25 |
32 | 38.72 | 37.12 | 35.52 | 33.92 | 32.00 | 30.72 | 29.76 | 28.16 |
Telepítési követelmények
- The magnetic field near the installation site should not be more than five times the magnetic field in any direction
Alkalmazások
- Protection of modern household appliances
- Civilian and industrial single-phase circuits
- Infrequent operation and control scenarios
Biztonsági jellemzők
- Dual pole protection
- Leakage protection in various wiring scenarios
- Simultaneous pole operation for enhanced safety