VIOX VRC1-125-B 100A 2P RCCB

VIOX VRC1-125-B RCCB offers superior protection against earth faults and electric leakage for systems up to 100A. This IEC61008-1 and IEC62423 compliant device features a 10kA rated limited short circuit current and supports residual operation currents of 0.03A, 0.1A, and 0.3A. Available in 2P configuration, it operates at 240/415V AC, 50/60Hz. Key advantages include Type B characteristics, IP20 protection, and a 4,000-cycle mechanical life. With its ergonomic design, contact position indication, and finger-protection terminals, this RCCB ensures easy operation and enhanced safety. Suitable for residential, commercial, and industrial applications, it offers automatic circuit cut-off and high short circuit tolerance. The device’s flame-resistant and impact-resistant construction, coupled with its 25mm² terminal capacity and 35.5mm DIN rail mounting, makes it ideal for various earth leakage protection needs in distribution boards and electrical circuits.

ส่งความต้องการของคุณมา เราจะเสนอราคาให้คุณภายใน 12 ชั่วโมง​

เบรกเกอร์ตัดไฟรั่ว VIOX VRC1-125-B 100A 2P RCCB

ภาพรวม

The VIOX VRC1-125-B is a high-performance Residual Current Circuit Breaker (RCCB) designed for superior protection against earth faults and electric leakage. With its advanced features and reliable performance, this RCCB ensures enhanced safety in various electrical installations.

คุณสมบัติหลัก

  • Ergonomic cambered cover and handle for comfortable operation
  • Contact position indication window for easy status checking
  • Transparent clamshell with label for clear identification
  • Quick fault identification with handle tripping to middle position
  • Earth fault, electric leakage, and isolation protection functions
  • High short circuit current tolerance
  • Finger-protection wiring terminal for added safety
  • High flame-resisting, temperature-resisting, and impact-resisting engineering plastic construction
  • Automatic circuit cut-off when earth fault or electric leakage exceeds stipulated value
  • Independent dynamic and wire pressure, unaffected by external disturbances and voltage fluctuations

ข้อมูลจำเพาะทางเทคนิค

  • Standard: IEC61008-1, IEC62423
  • Type: Electronic type (Auxiliary Electromagnetic type)
  • Characteristics of residual operation current: Type B
  • Poles: 2P (1P+N, 3P+N available)
  • Rated operating break capability: 10 InA
  • Rated current: 100A (25A, 40A, 63A also available)
  • Rated voltage: AC 240/415V
  • Rated frequency: 50/60 Hz
  • Rated residual operation current (I△n): 0.03A, 0.1A, 0.3A
  • กระแสไฟฟ้าตกค้างที่ไม่ทำงานที่กำหนด: 0.5I△n
  • Rated limited short circuit current: 10 kA
  • Rated limited residual short circuit current: 10 kA
  • Scope of residual operating current: 0.5I△n~I△n
  • Mechanical electrical life: 4,000 cycles
  • Wiring section area of terminal: conductor of 25 mm² and below
  • Installation: 35.5mm guide rail / Vertical installation
  • Enclosure protection class: IP20

พารามิเตอร์พื้นฐาน

กระแสไฟฟ้าที่กำหนด
of housing
grade Inm(A)
วกเธอคงหัวเสี ความถี่
(Hz)
แรงดันไฟฟ้าที่กำหนด
Ue(V)
กระแสไฟฟ้าที่กำหนด
ใน(ก)
Rated residual
current(A)
Rated limited
ไฟฟ้าลัดวงจร
current Inc(A)
Rated limited
residual short
circuit current
I△C(A)
63 1P+เอ็น 50/60เฮิรตซ์ 240 25 40 63 0.03 0.1 0.3 10000 10000
3พี+เอ็น 415

 

Standard value of breaking time and non-operating time for pulse DC residual current and smooth DC residual current produced by rectifying circuit

ประเภท ใน(ก) I△n(A) Standard value of breaking time and non-operating time for equality of residual
current (I△A ) and following values (S)
2 ไอ△อิน 4 I△n 10 I△n 5A,10A,20A,50A,100A,200A
ประเภททั่วไป ค่าใดๆ ค่าใดๆ 0.3 0.15 0.04 0.04

 

Range of tripping current(Table 1)

แบบอย่าง Tripping  current I△ /A
แอร์ 0.5 I△n<I△n
เป็ Angle of retard I△n>0.01A I△n<0.01A
0.35I△n≤I△≤1.4I△n 0.35I△n≤I△≤2I△n
90° 0.25I△n≤I△≤1.4I△n 0.25I△n≤I△≤2I△n
135° 0.1I△n≤I△≤1.4I△n 0.1I△n≤I△≤2I△n

 

Different from (B type) of 50/60 Hz as per frequency(Table 2)

Frequency(Hz) Residual non-operating current Residual operating current
150 0.5I△n 2.4I△n
400 0.5I△n 6I△n
1000 ฉัน△น 14I△n

แอปพลิเคชั่น

  • ระบบไฟฟ้าที่อยู่อาศัย
  • อาคารพาณิชย์
  • การติดตั้งทางอุตสาหกรรม
  • แผงจ่ายไฟ
  • การป้องกันการรั่วไหลของดินในวงจรไฟฟ้าต่างๆ

นายได้เปรียบอะไรบ้าง

  • Enhanced safety with multiple protection functions
  • High short circuit current tolerance for improved reliability
  • ติดตั้งและบำรุงรักษาง่าย
  • การระบุสถานะที่ชัดเจนเพื่อระบุข้อผิดพลาดอย่างรวดเร็ว
  • Durable construction for long-lasting performance
  • สอดคล้องกับมาตรฐานสากลด้านการประกันคุณภาพ

คุณสมบัติด้านความปลอดภัย

  • การป้องกันไฟฟ้าลัดวงจร
  • Electric leakage protection
  • Isolation protection
  • Finger-protection wiring terminal
  • Automatic circuit cut-off for faults exceeding stipulated values

การรับประกันคุณภาพ

VIOX มุ่งมั่นที่จะจัดหา RCCB คุณภาพสูงที่ได้มาตรฐานสากล ผลิตภัณฑ์ของเราผ่านการทดสอบอย่างเข้มงวดเพื่อให้มั่นใจถึงความน่าเชื่อถือ ความปลอดภัย และประสิทธิภาพระยะยาวในการติดตั้งระบบไฟฟ้าต่างๆ

การติดตั้ง

The VIOX VRC1-125-B RCCB is designed for easy installation on 35.5mm guide rails or vertical mounting. Its compact design and clear labeling facilitate quick and efficient installation in distribution boards and electrical panels.

มิติ

VRC1-125(63A)

VRC1-125(100A)

สินค้าที่เกี่ยวข้อง