RCBO VIOX VL16-40 AC loại 1P+N
VIOX VL16-40 AC Type 1P+N RCBO offers comprehensive protection for household and commercial distribution systems. This IEC/EN61009-1 compliant device safeguards against earth faults, short-circuits, and overloads with a 10kA rated short-circuit capacity. Available in 1A to 40A ratings, it operates at 240V AC, 50/60Hz, with residual current options of 30mA, 100mA, or 300mA. Featuring B, C, or D tripping curves and instantaneous tripping ≤0.1s, it provides efficient protection against insulation failures and direct human contact. With easy DIN rail mounting and 4000 cycle electro-mechanical endurance, this versatile RCBO ensures reliable electrical safety for various applications.
Gửi yêu cầu của bạn, chúng tôi sẽ báo giá cho bạn trong vòng 12 giờ
- ĐT: +8618066396588
- Bạn+8618066396588
- Email:[email protected]
VIOX VL16-40 AC Type 1P+N Residual Current Circuit Breaker with Overcurrent Protection RCBO
Tổng quan
The VIOX VL16-40 RCBO provides comprehensive protection for household and commercial distribution systems. It offers protection against earth fault/leakage current, short-circuit, overload, and functions as an isolation device. This device effectively safeguards electric equipment against insulating failure and provides complementary protection against direct contact by human body.
Các tính năng chính
- Standards: IEC/EN61009-1
- Type: Electro-magnetic type
- Residual current characteristics: AC A
- Pole No.: 1P+N
- Đường cong vấp ngã: B, C, D
- Rated short-circuit capacity: 10kA
- Rated current (A): 1A, 2A, 3A, 4A, 6A, 10A, 16A, 20A, 25A, 32A, 40A
- Rated voltage: 240V AC
- Tần số định mức: 50/60Hz
- Rated residual operating current(mA): 0.03, 0.1, 0.3
- Tripping duration: instantaneous≤0.1s
- Độ bền cơ điện: 4000 chu kỳ
Thông số kỹ thuật
- Connection terminal: pillar terminal with clamp
- Connection capacity: Rigid conductor 16mm²
- Terminal connection height: 21.5mm
- Installation: On symmetrical DIN rail 35mm or Panel mounting
Đặc điểm bảo vệ dòng điện quá tải
| Test procedure | Loại | Kiểm tra dòng điện | Trạng thái ban đầu | Tripping or Non-tripping Time Limit | Expected Result | Nhận xét |
|---|---|---|---|---|---|---|
| Một | B, C, D | 1,13 Trong | cold | t≥1h | No tripping | |
| b | 1,45 inch | after test a | t<1h | tripping | Current in the 5s in the increase of stability | |
| c | 2,55 inch | cold | 1s<t<60s | tripping | ||
| ngày | B C D |
3Trong 5 trong 10 trong |
cold | t≥0.1s | No tripping | Turn on the auxiliary switch to close the current |
| e | B C D |
5 trong 10 trong 20 Trong |
cold | t<0.1s | tripping | Turn on the auxiliary switch to close the current |
The terminology “cold state” refers to that no load is carried before testing at the reference setting temperature.
Thời gian ngắt dòng điện dư
| Loại | In/A | I△n/A | Residual Current (I△) Is Corresponding To The Following Breaking Time (S) | ||||
| AC type | any value | any value | TRONG | 2In | 5 trong | 5A, 10A, 20A, 50A, 100A, 200A, 500A | |
| A type | any value | >0.01 | 1.4In | 2.8In | 7In | ||
| 0.3 | 0.15 | 0.04 | 0.04 | Thời gian nghỉ giải lao tối đa | |||
| The general type RCBO whose current IΔn is 0.03mA or less can use 0.25A instead of 5IΔn. | |||||||