VIOX VSP1-D20/2 (S) SPD Kutub Tunggal yang Dapat Dicolokkan
VIOX VSP1-D20/2(S) Pluggable Single-Pole SPD offers robust surge protection for sub-distribution boards. This Class II/III device safeguards L-PE and N-PE modes with 10kA nominal and 20kA maximum discharge current. Featuring high-energy MOV elements, it operates from 60V to 400V AC with < 25ns response time. The pluggable design ensures easy installation on 35mm DIN rails. IEC 61643-11:2011 and EN 61643-11:2012 compliant, it provides voltage protection levels from 0.2kV to 1.8kV. With IP20 protection, thermal safeguards, and optional remote contacts, this versatile SPD suits various electrical installations, combining reliability and performance in a compact, user-friendly package for enhanced power system protection.
Kirimkan kebutuhan Anda, kami akan mengutip untuk Anda dalam waktu 12 jam
- TEL:+8618066396588
- Whatsapp:+8618066396588
- Email:sales@viox.com
VIOX VSP1-D20/2 (S) SPD Kutub Tunggal yang Dapat Dicolokkan
Ikhtisar
The VIOX VSP1-D20/2(S) is a high-performance Pluggable Single-Pole Surge Protective Device (SPD) designed for use in sub-distribution boards. This versatile device offers robust protection for both L-PE and N-PE modes, making it an ideal solution for various electrical installations.
Fitur Utama
- Perangkat Kelas II, Kelas III, Tipe 2, Tipe 3
- Lokasi Penggunaan: Papan Sub-Distribusi
- Mode Perlindungan: L-PE, N-PE
- Peringkat Lonjakan: Dalam = 10 kA (8/20 μs)
- Kategori IEC/EN/UL: Kelas II + III / Tipe 2 + 3
- Elemen Pelindung: MOV Energi Tinggi
- Perumahan: Desain yang Dapat Dicolokkan
- Kepatuhan: IEC 61643-11: 2011, EN 61643-11: 2012
Spesifikasi Teknis
IEC Electrical | 75 | 150 | 275 | 320 | 385 | 440 |
---|---|---|---|---|---|---|
Tegangan AC Nominal (50/60Hz) | 60 V | 120 V | 230 V | 230 V | 230 V | 400 V |
Tegangan Operasi Kontinu Maksimum (AC) | 75 V | 150 V | 275V | 320 V | 385 V | 440 V |
Arus Pelepasan Nominal (8/20 μs) | 10 kA | 10 kA | 10 kA | 10 kA | 10 kA | 10 kA |
Arus Pelepasan Maksimum (8/20 μs) | 20 kA | 20 kA | 20 kA | 20 kA | 20 kA | 20 kA |
Tingkat Perlindungan Tegangan | 0.2 kV | 0,6 kV | 1,3 kV | 1,5 kV | 1,5 kV | 1,8 kV |
Waktu Tanggapan | <25 ns | |||||
Sekering Cadangan (maks) | 125 A gL / gG | |||||
Peringkat Arus Hubung Singkat (AC) | 10 kA | |||||
TOV Tahan 5s | 90V | 180V | 335V | 335V | 335V | 580V |
TOV 120 menit | 115V | 230V | 440V | 440V | 440V | 765V |
mode | Menahan | Menahan | Aman Gagal | Aman Gagal | Aman Gagal | Aman Gagal |
Spesifikasi Mekanik & Lingkungan
- Kisaran Suhu Pengoperasian: -40°F hingga +158°F (-40°C hingga +70°C)
- Kelembaban Pengoperasian yang Diizinkan: 5%... 95%
- Tekanan atmosfer dan ketinggian: 80k Pa ... 106k Pa / -500 m....2000 m
- Torsi Sekrup Terminal: 39,9 lbf.in [4,5 Nm]
- Penampang Konduktor (maks): 2 AWG (Padat, Terdampar) / 4 AWG (Fleksibel)
- 35 mm² (Padat, Terdampar) / 25 mm² (Fleksibel)
- Pemasangan: Rel DIN 35 mm, EN 60715
- Tingkat Perlindungan: IP 20 (built-in)
- Bahan Perumahan: Termoplastik: Derajat Pemadaman UL 94 V-0
- Perlindungan Termal: Ya
- Status Operasi / Indikasi Kesalahan: Hijau ok / Cacat merah
Fitur Tambahan
- Kontak Jarak Jauh (RC): Opsional
- Kapasitas Pengalihan RC: AC: 250V / 0,5 A; DC: 250V / 0,1 A; 125V / 0,2 A; 75V / 0,5 A
- Penampang Konduktor RC (maks): 16 AWG (Padat) / 1,5 mm² (Padat)