VIOX VRO8-63 2P 10kA 63A 30mA RCBO
VIOX VRO8-63 2P RCBO offers advanced protection for electrical systems. This IEC61009-1 compliant device features a 10kA breaking capacity and supports up to 63A at 240V AC. With 30mA residual current sensitivity, it provides comprehensive A/AC type protection against earth faults, short circuits, and overloads. The RCBO offers B, C, and D tripping curves, IP20 protection, and operates from -25°C to +40°C. Key advantages include fault current indication, versatile terminal connections, and 4kV impulse withstand voltage. Boasting 20,000 mechanical and 4,000 electrical life cycles, this RCBO ensures long-lasting, reliable protection for various applications. Easy DIN rail mounting and clear overload/residual current characteristics make it ideal for both residential and commercial installations.
Küldje el igényeit, 12 órán belül árajánlatot adunk Önnek.
- TEL:+8618066396588
- Whatsapp:+8618066396588
- Email:sales@viox.com
VIOX VRO8-63 2P 10kA 63A 30mA RCBO, Túlterhelés elleni védelemmel ellátott megszakító áramkör megszakítója
Áttekintés
The VIOX VRO8-63 is a high-performance 2-pole Residual Current Circuit Breaker with Overcurrent protection (RCBO) designed for reliable protection in electrical systems. With a rated breaking capacity of 10kA and a rated current of 63A, this device offers comprehensive protection against residual current faults and overloads.
Fő jellemzők
- Standard: IEC61009-1
- Mode: Electronic
- Type: A/AC
- Kicsúszási görbe: B, C, D
- Pole No.: 2P
- Rated voltage: 240V~
- Névleges frekvencia: 50/60Hz
- Rated current: 63A
- Rated residual operating current (I△n): 30mA
- Névleges impulzusállósági feszültség (Uimp): 4kV
- Rated breaking capacity (Icn): 10000A
- Energy limiting class: 3
- Electrical and Mechanical life: 4000/20,000 operations
Műszaki specifikációk
- Fault current indicator: YES
- Védelmi fokozat: IP20
- Ambient temperature: -25°C to +40°C (24h average not exceeding +35°C)
- Storage temperature: -25°C to +70°C
- Terminal connection type: Cable/U-type busbar/Pin-type busbar
- Terminal size top for cable: 25mm²
- Tightening torque: 2.5N.m
- Szerelés: DIN sínre EN 60715 (35 mm) gyorsrögzítővel
- Connection: Top and bottom
Túlterhelési áramvédelmi jellemzők
Vizsgálati eljárás | Típus | Tesztáram | Kezdeti állapot | Kioldási vagy nem kioldási időkorlát | Várható eredmény | Megjegyzés |
---|---|---|---|---|---|---|
a | B, C, D | 1.13In | hideg | t≤1h | no tripping | |
b | B, C, D | 1.45In | teszt után | t<1 óra | kioldás | The current steadily rises to the specified value within 5s |
c | B, C, D | 2.55In | hideg | 1s <t <60s | kioldás | |
d | B C D |
3In 5In 10In |
hideg | t≤0.1s | no tripping | Kapcsolja be a segédkapcsolót az áramellátás lezárásához. |
e | B C D |
5In 10In 20In |
hideg | t < 0,1 s | kioldás | Kapcsolja be a segédkapcsolót az áramellátás lezárásához. |
Residual Current Operating Breaking Time
Típus | Be/Be | I△n/A | A maradékáram (I△) a következő megszakítási időnek (S) felel meg: | ||||
AC Type | bármilyen value |
bármilyen value |
1ln | 2 hüvelyk | 5In | 5A,10A,20A,50A 100A,200A,500A |
|
A Type | > 0,01 | 1,4 hüvelyk | 2,8 hüvelyk | 7 hüvelyk | |||
0.3 | 0.15 | 0.04 | Max. szünetidő | ||||
Az általános típusú RCBO, amelynek árama IΔn 0,03 mA vagy kisebb, 0,25 A-t használhat 5IΔn helyett. |