VIOX VSP1-C40PV/3(S) 1000V(D4) Pluggable Multi-Pole SPD
VIOX VSP1-C40PV/3(S) 1000V(D4) Pluggable Multi-Pole SPD offers robust surge protection for high-voltage photovoltaic systems and DC applications. This Class I+II/Type 1+2 device safeguards (DC+) – PE and (DC-) – PE modes with 20kA nominal and 40kA maximum discharge current. Featuring high-energy MOV elements, it operates at 1000V DC with < 25ns response time. The pluggable design ensures easy installation on 35mm DIN rails. Compliant with IEC 61643-31:2018 and EN 50539-11:2013+A1:2014, it provides a voltage protection level of 3.6kV. With IP20 protection, thermal safeguards, and optional remote contacts, this versatile multi-pole SPD combines reliability and performance for enhanced power system protection in demanding high-voltage DC and photovoltaic applications.
Ipadala ang iyong mga kinakailangan, mag-quote kami para sa iyo sa loob ng 12 oras
- TEL:+8618066396588
- Whatsapp:+8618066396588
- Email:[email protected]
VIOX VSP1-C40PV/3(S) 1000V(D4) Pluggable Multi-Pole SPD
Pangkalahatang-ideya
The VIOX VSP1-C40PV/3(S) 1000V(D4) is a high-performance Pluggable Multi-Pole Surge Protective Device (SPD) designed for use in sub-distribution boards. This versatile device offers robust protection for (DC+) – PE and (DC-) – PE modes, making it an ideal solution for high-voltage photovoltaic systems and other DC applications requiring multi-pole protection.
Mga Pangunahing Tampok
- Class I, Class II, Type 1, Type 2 device
- Lokasyon ng Paggamit: Mga Sub-Distribution Board
- Mode ng Proteksyon: (DC+) – PE, (DC-) – PE
- Mga Surge Rating: Sa = 20 kA (8/20 μs)
- IEC/EN/UL Kategorya: Class I+II / Type 1+2
- Mga Elementong Proteksiyon: High Energy MOV
- Pabahay: Pluggable na Disenyo
- Pagsunod: IEC 61643-31:2018, EN 50539-11:2013+A1:2014
Teknikal na Pagtutukoy
| IEC Electrical | 1000 |
|---|---|
| Nominal AC Boltahe | 1000 V |
| Maximum Continuous Operating Voltage (DC) | 1000 V |
| Nominal Discharge Current (8/20 μs) | 20 kA |
| Maximum Discharge Current (8/20 μs) | 40 kA |
| Impulse Discharge Current (10/350 μs) | 6.25 kA |
| Antas ng Proteksyon ng Boltahe | 3.6 kV |
| Oras Ng Pagtugon | < 25 ns |
| Back-Up Fuse (max) | 125 A gL / gG |
| Short-Circuit Current Rating (AC) | 25 kA / 50 kA |
Mga Detalye ng Mekanikal at Pangkapaligiran
- Saklaw ng Operating Temperature: -40°F hanggang +158°F [-40°C hanggang +70°C]
- Pinahihintulutang Operating Humidity: 5%…95%
- Presyon at altitude ng atmospera: 80k Pa … 106k Pa / -500 m….2000 m
- Terminal Screw Torque: 39.9 lbf.in [4.5 Nm]
- Conductor Cross Section (max): 2 AWG (Solid, Stranded) / 4 AWG (Flexible)
- 35 mm² (Solid, Stranded) / 25 mm²(Flexible)
- Pag-mount: 35 mm DIN Rail, EN 60715
- Degree ng Proteksyon: IP 20 (built-in)
- Material ng Pabahay: Thermoplastic: Extinguishing Degree UL 94 V-0
- Thermal Protection: Oo
- Operating State / Fault Indication: Green ok / Red defect
Mga Karagdagang Tampok
- Mga Remote Contact (RC): Opsyonal
- RC Switching Capacity: AC: 250V / 0.5 A; DC: 250V / 0.1 A;125V / 0.2 A;75V / 0.5 A
- RC Conductor Cross Section (max): 16 AWG (Solid) / 1.5 mm²(Solid)