VIOX VSP1-C40/4(S) Pluggable Multi-Pole SPD
VIOX VSP1-C40/4(S) Pluggable Multi-Pole SPD offers robust surge protection for sub-distribution boards. This Class II/Type 2/Type 1CA device safeguards L-PE and N-PE modes with 20kA nominal and 40kA maximum discharge current. Featuring high-energy MOV elements, it operates from 120V to 400V AC with < 25ns response time. The pluggable design ensures easy installation on 35mm DIN rails. IEC 61643-11:2011 and EN 61643-11:2012 compliant, it provides voltage protection levels from 1kV to 2kV. With IP20 protection, thermal safeguards, and optional remote contacts, this versatile SPD suits various electrical installations, combining reliability and performance in a compact, user-friendly package for enhanced multi-pole power system protection in demanding applications.
Ipadala ang iyong mga kinakailangan, mag-quote kami para sa iyo sa loob ng 12 oras
- TEL:+8618066396588
- Whatsapp:+8618066396588
- Email:sales@viox.com
VIOX VSP1-C40/4(S) Pluggable Multi-Pole SPD
Pangkalahatang-ideya
The VIOX VSP1-C40/4(S) is a high-performance Pluggable Multi-Pole Surge Protective Device (SPD) designed for use in sub-distribution boards. This versatile device offers robust protection for L-PE and N-PE modes, making it an ideal solution for various electrical installations.
Mga Pangunahing Tampok
- Class II, Type 2, Type 1CA device
- Lokasyon ng Paggamit: Mga Sub-Distribution Board
- Paraan ng Proteksyon: L-PE, N-PE
- Mga Surge Rating: Sa = 20 kA (8/20 μs)
- IEC/EN/UL Kategorya: Class II / Type 2 / Type 1CA
- Mga Elementong Proteksiyon: High Energy MOV
- Pabahay: Pluggable na Disenyo
- Pagsunod: IEC 61643-11:2011, EN 61643-11:2012
Teknikal na Pagtutukoy
IEC Electrical | 150 | 275 | 320 | 385 | 440 |
---|---|---|---|---|---|
Nominal AC Voltage (50/60Hz) | 120 V | 230 V | 230 V | 230 V | 400 V |
Maximum Continuous Operating Voltage (AC) | 150 V | 275V | 320 V | 385 V | 440 V |
Nominal Discharge Current (8/20 μs) | 20 kA | 20 kA | 20 kA | 20 kA | 20 kA |
Maximum Discharge Current (8/20 μs) | 40 kA | 40 kA | 40 kA | 40 kA | 40 kA |
Antas ng Proteksyon ng Boltahe | 1 kV | 1.5 kV | 1.6 kV | 1.8 kV | 2 kV |
Impulse Current (10/350μs) Iimp (LN) | 7kA | ||||
Oras ng Pagtugon | < 25 ns | ||||
Back-Up Fuse (max) | 125 A gL / gG | ||||
Short-Circuit Current Rating (AC) | 25 kA / 50 kA | ||||
TOV Makatiis ng 5s | 180V | 335V | 335V | 335V | 580V |
TOV 120min | 230V | 440V | 440V | 440V | 765V |
mode | Makatiis | Ligtas na Nabigo | Ligtas na Nabigo | Ligtas na Nabigo | Ligtas na Nabigo |
Mga Detalye ng Mekanikal at Pangkapaligiran
- Saklaw ng Operating Temperature: -40°F hanggang +158°F [-40°C hanggang +70°C]
- Pinahihintulutang Operating Humidity: 5%…95%
- Presyon at altitude ng atmospera: 80k Pa … 106k Pa / -500 m….2000 m
- Terminal Screw Torque: 39.9 lbf.in [4.5 Nm]
- Conductor Cross Section (max): 2 AWG (Solid, Stranded) / 4 AWG (Flexible)
- 35 mm² (Solid, Stranded) / 25 mm²(Flexible)
- Pag-mount: 35 mm DIN Rail, EN 60715
- Degree ng Proteksyon: IP 20 (built-in)
- Material ng Pabahay: Thermoplastic: Extinguishing Degree UL 94 V-0
- Thermal Protection: Oo
- Operating State / Fault Indication: Green ok / Red defect
Mga Karagdagang Tampok
- Mga Remote Contact (RC): Opsyonal
- RC Switching Capacity: AC: 250V / 0.5 A; DC: 250V / 0.1 A;125V / 0.2 A;75V / 0.5 A
- RC Conductor Cross Section (max): 16 AWG (Solid) / 1.5 mm²(Solid)